1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Issued: June 2017 Revision: D 1. Application Forcing of binary inputs and outputs is a convenient way to SEMOD155704-4 v6 The REG670 is used for protection, control and monitoring of test wiring in substations as well as testing configuration logic generators and generator-transformer blocks from relatively in the IEDs.
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 2. Available functions Main protection functions GUID-66BAAD98-851D-4AAC-B386-B38B57718BD2 v12 Table 1. Example of quantities = number of basic instances = option quantities 3-A03 = optional function included in packages A03 (refer to ordering details) IEC 61850 ANSI Function description...
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Generator REG670 (Customized) Multipurpose protection CVGAPC General current and voltage protection 1-12 General calculation SMAIHPAC Multipurpose filter 67 requires voltage 67N requires voltage...
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v12.1.1 IEC 61850 ANSI Function description Generator REG670 Control SESRSYN Synchrocheck, energizing check and synchronizing APC30 Apparatus control for up to 6 bays, max 30 apparatuses (6CBs) 1-H09 1-H09 1-H09...
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Generator REG670 DRPRDRE, Disturbance report A1RADR- A4RADR, B1RBDR-B8RBDR SPGAPC Generic communication function for Single Point indication SP16GAPC Generic communication function for Single Point indication 16 inputs MVGAPC Generic communication function for Measured Value...
Page 13
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 2. Total number of instances for basic configurable logic blocks Basic configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SRMEMORY TIMERSET Table 3. Total number of instances for configurable logic blocks Q/T Configurable logic blocks Q/T Total number of instances ANDQT...
Page 14
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v12.1.1 IEC 61850 ANSI Function description Generator REG670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC 60870-5-103 for SLM RS485PROT Operation selection for RS485...
Page 15
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Generator REG670 (Customized) SYSLLN0 IEC 61850 SYS LLN0 LPHD Physical device information PCMACCS IED Configuration Protocol SECALARM Component for mapping security events on protocols such as DNP3 and IEC103 FSTACCS Field service tool access via SPA protocol over ethernet...
Page 16
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v9 Table 5. Basic IED functions IEC 61850 or function Description name INTERRSIG SELFSUPEVLST Self supervision with internal event list TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN, Time synchronization SYNCHGPS,...
Page 17
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 5. Basic IED functions, continued IEC 61850 or function Description name RUNTIME IED Runtime Comp CAMCONFIG Central account management configuration CAMSTATUS Central account management status TOOLINF Tools Information component SAFEFILECOPY Safe file copy function Table 6.
Page 18
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 are provided with percentage bias restraint features, making currents.By introducing the load tap changer position, the the IED suitable for two- or three-winding transformer in differential protection pick-up can be set to optimum multi-breaker station arrangements.
Page 19
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 The operation of the phase-selection is primarily based on a current change criteria (i.e. delta quantities), however there is YNdx also a phase selection criterion operating in parallel which bases its operation on voltage and current phasors exclusively.
Page 20
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 generator will accelerate so much, that the synchronism Loss of excitation LEXPDIS cannot be maintained. SEMOD151269-4 v8 There are limits for the under-excited operation of a synchronous machine. A reduction of the excitation current Undamped oscillations occur in the power system, where weakens the coupling between the rotor and the stator.
Page 21
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 The magnitude of the injected voltage signal is measured on A second harmonic blocking level can be set for the function the secondary side of the neutral point voltage transformer or and can be used to block each step individually.
Page 22
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 NS4PTOC can be used as main protection for unsymmetrical A current check with extremely short reset time is used as fault; phase-phase short circuits, phase-phase-earth short check criterion to achieve high security against inadvertent circuits and single phase earth faults.
Page 23
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 A separate definite time delayed output is available as an Voltage-restrained time overcurrent protection VRPVOC alarm feature to warn the operator of a potentially dangerous GUID-935E1CE8-601F-40E2-8D22-2FF68420FADF v6 Voltage-restrained time overcurrent protection (VRPVOC) situation.
Page 24
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 For its operation the function either measures the true RMS Reset delay ensures operation for intermittent earth faults. current of the excitation transformer or calculates the DC Overexcitation protection OEXPVPH current in the rotor winding.
Page 25
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 point 3rd harmonic undervoltage principle or the terminal side these two measuring principles provides coverage for entire 3rd harmonic overvoltage principle can be applied. However, stator winding against earth faults. differential principle is strongly recommended.
Page 26
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Additionally two overvoltage and two undervoltage steps, Rate-of-change frequency protection SAPFRC either with definite time or inverse time characteristic, are M14965-3 v12 The rate-of-change frequency protection function SAPFRC available within each function.
Page 27
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 RXTTE4 and an optional protective resistor on plate are These functions can operate unintentionally, if a fault occurs required for correct rotor earth fault protection operation. in the secondary circuits between voltage instrument transformers and the IED.
Page 28
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 evaluation of conditions from other functions such as Switch controller SCSWI interlocking, synchrocheck, operator place selection and M13486-3 v7 The Switch controller (SCSWI) initializes and supervises all external or internal blockings. functions to properly select and operate switching primary apparatuses.
Page 29
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 11. Logic Logic rotating switch for function selection and LHMI presentation SLGAPC Tripping logic SMPPTRC SEMOD114908-4 v9 M12275-3 v10 The logic rotating switch for function selection and LHMI A function block for protection tripping is always provided as presentation SLGAPC (or the selector switch function block) basic for each circuit breaker involved in the tripping of the...
Page 30
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 • OR function block. Each block has up to six inputs and two a certain level/value, or for creating certain logic. Boolean, outputs where one is inverted. integer, floating point, string types of signals are available. •...
Page 31
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 ITBGAPC function block. The input BLOCK will freeze the The Disturbance report functionality is a common name for output at the last received value and blocks new integer several functions: values to be received and converted to binary coded outputs.
Page 32
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 The event recorder logs all selected binary input signals Analog and double indication values are also transferred connected to the Disturbance recorder function. Each through EVENT function. recording can contain up to 150 time-tagged events. Generic communication function for Single Point indication The event recorder information is available for the SPGAPC...
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 tEnergy . The integration of active and reactive energy time Event counter with limit supervison L4UFCNT values will happen in both forward and reverse directions. GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v5 The 30 limit counter L4UFCNT provides a settable counter These energy values are available as output signals and also with four independent limits where the number of positive as pulse outputs.
Product version: 2.1 The LHMI is used for setting, monitoring and controlling. SEMOD120134-5 v1 A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation 15. Basic IED functions automation systems but the main use is for Substation Monitoring Systems SMS.
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M16073-3 v6 km/1.9 miles away. The LDCM module sends and receives The optical fast-ethernet module is used for fast and data, to and from another LDCM module. The IEEE/ANSI interference-free communication of synchrophasor data over C37.94 standard format is used.
Page 36
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 IRIG-B Time synchronizing module SEMOD141113-4 v7 The IRIG-B time synchronizing module is used for accurate time synchronizing of the IED from a station clock. The Pulse Per Second (PPS) input shall be used for synchronizing when IEC 61850-9-2LE is used.
Connectivity package DVD as part of the product delivery. injection unit REX060 1MRK002504-BA The latest versions of the connection diagrams can be Connection diagram, Injection unit REX060 and coupling downloaded from http://www.abb.com/substationautomation. capacitor unit REX061 1MRK002504-CA Connection diagrams for Customized products Connection diagram, Injection unit REX060 and optional Connection diagram, 670 series 2.11MRK002801-AF...
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 20. Technical data General M10993-1 v3 IP11376-1 v2 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range...
Page 40
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 8. TRM - Energizing quantities, rated values and limits for measuring transformer modules Quantity Rated value Nominal range Current = 1 or 5 A (0-1.8) × I at I = 1 A (0-1.6) ×...
Page 41
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Binary inputs and outputs M12576-1 v7 IP15844-1 v1 Table 12. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V...
Page 42
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M12573-1 v8 Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. Table 14. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V...
Page 43
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M12318-1 v6 Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. Table 15. IOM - Binary input/output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and signal relays Fast signal relays (parallel...
Page 44
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 15. IOM - Binary input/output module contact data (reference standard: IEC 61810-2), continued Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A Breaking capacity for DC with L/R <...
Page 45
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 SEMOD175395-2 v6 Table 17. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Static binary output trip Rated voltage 48 - 60 VDC 110 - 250 VDC Number of outputs Impedance open state...
Page 46
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M12441-1 v7 Table 19. BOM - Binary output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Binary outputs Max system voltage 250 V AC, DC Test voltage across open contact, 1 min 1000 V rms Current carrying capacity...
Page 47
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 22. Frequency influence (reference standard: IEC 60255–1) Dependence on Within nominal range Influence Frequency dependence, operate value ±2.5 Hz for 50 Hz ±1.0% / Hz ±3.0 Hz for 60 Hz Frequency dependence for distance protection operate value ±2.5 Hz for 50 Hz ±2.0% / Hz...
Page 48
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 23. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III Ring wave immunity test, 100 kHz 2-4 kV...
Page 49
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 25. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C IEC 60068-2-1 Dry heat operation test Test Bd for 16 h at +70°C...
Page 50
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Injection equipment GUID-87197CB5-8590-4872-A5B6-8C6D2A815C9E v3 Table 28. Electromagnetic compatibility tests Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III Surge withstand capability test...
Page 51
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 30. Insulation tests, REX061 Test Type test values Reference standard Dielectric test 7.48 kV DC, 1min IEEE 421.3 (connections to rotor) 2.8 kV DC, 1 min IEC 60255-27 Impulse voltage test 12.0 kV, 1.2/50 µs, 0.5 J IEC 60664-1...
Page 52
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-9D1F44FC-896B-4907-9609-C32781CA1798 v2 Table 33. Auxiliary DC supply voltage influence Test Type test values Influence Auxiliary voltage dependence, operate value ±20% of EL 0.01% /% Ripple in DC auxiliary voltage, operate value 15% of EL 0.01% /% GUID-A1BED9A8-2791-4ACF-8400-B20206F057A8 v2...
Page 53
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Differential protection SEMOD175004-2 v9 Table 36. Generator differential protection GENPDIF Function Range or value Accuracy IBase Unrestrained differential current limit (1-50)p.u. of ±1.0% of set value Reset ratio >...
Page 54
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M13046-1 v11 Table 37. Transformer differential protection T2WPDIF, T3WPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of Ir at I ≤ Ir ±1.0% of I at I > Ir Reset ratio >...
Page 55
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M13081-1 v11 Table 39. 1Ph High impedance differential protection HZPDIF Function Range or value Accuracy Operate voltage (10-900) V ±1.0% of I at I ≤ I I=U/R ±1.0% of I at I > I Reset ratio >95% at (30-900) V Maximum continuous power...
Page 56
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Impedance protection SEMOD173242-2 v13 Table 40. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Range or value Accuracy Number of zones, Ph-E Max 4 with selectable direction Minimum operate current (10–30)% of IBase Positive sequence impedance, (0.005–3000.000) W/phase...
Page 57
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v4 Table 41. High speed distance protection ZMFPDIS, ZMFCPDIS Function Range or value Accuracy Number of zones 3 selectable directions, 3 fixed directions Minimum operate current, Ph-Ph (5-6000)% of IBase ±1.0% of I and Ph-E...
Page 58
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-16656307-6B43-47B5-8817-48638FFB5999 v3 Table 42. Distance zones quad with high speed distance for series compensated networks ZMFCPDIS Function Range or value Accuracy Number of zones 3 selectable directions, 3 fixed directions Minimum operate current, Ph-Ph (5 - 6000)% of IBase...
Page 59
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 SEMOD175144-2 v9 Table 45. Loss of excitation LEXPDIS Function Range or value Accuracy X offset of Mho top point for (–1000.00–1000.00)% of Z ±5.0% of U Base Zone 1 and Zone 2 Diameter of Mho circle for Zone (0.0–3000.00)% of Z ±5.0% of U...
Page 60
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-956187E5-A466-47BF-B671-F46548A5DF2E v3 Table 47. STTIPHIZ technical data Function Range or value Accuracy Fault resistance sensitivity Can be reached at steady state 50 kΩ operating condition of the machine Typically 10 kΩ...
Page 61
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Current protection M12336-1 v11 Table 49. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
Page 62
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M12342-1 v16 Table 50. Four-step phase overcurrent protection OC4PTOC Function Setting range Accuracy Operate current, step 1 - 4 (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
Page 63
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M15223-1 v14 Table 52. Four step residual overcurrent protection EF4PTOC technical data Function Range or value Accuracy Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of I at I ≤...
Page 64
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v5 Table 53. Four step negative sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of I at I £...
Page 65
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 SEMOD173350-2 v13 Table 54. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of lBase Operate level for 3I ·cosj ±1.0% of I at I £...
Page 66
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M13266-2 v8 Table 55. Thermal overload protection, two time constants TRPTTR Function Range or value Accuracy Base current 1 and 2 (30–250)% of IBase ±1.0% of I Operate time: = load current before overload ±5.0% or ±200 ms whichever is greater occurs...
Page 67
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M13279-1 v9 Table 57. Pole discordance protection CCPDSC Function Range or value Accuracy Operate current (0–100)% of IBase ±1.0% of I Independent time delay (0.000-60.000) s ±0.2% or ± 25 ms whichever is greater between trip condition and trip signal SEMOD175152-2 v10...
Page 68
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-E5718F80-556D-4852-A8F2-90E0F578D763 v8 Table 60. Negative sequence time overcurrent protection for machines NS2PTOC Function Range or value Accuracy Operate current, step 1 - 2 (3-500)% of IBase ±1.0% of I at I ≤...
Page 69
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-9B1C0C10-8AF9-4D9E-8076-B3E1C238D29A v7 Table 61. Accidental energizing protection for synchronous generator AEGPVOC Function Range or value Accuracy Operate value, overcurrent (5-900)% of IBase ±1.0% of I at I≤I ±1.0% of I at I>I Reset ratio, overcurrent >95% at (20–900)% of IBase Transient overreach, overcurrent function...
Page 70
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-A1CB5B4F-768E-4B1B-937E-B91EC3EFA2CC v3 Table 63. Generator rotor overload protection GRPTTR Function Range or value Accuracy Overcurrent start level for (105.0–900.0)% of IBase ±1.0% of I at I ≤ I overload protection ±1.0% of I at I >...
Page 71
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Voltage protection M13290-1 v14 Table 64. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U Absolute hysteresis (0.0–50.0)% of UBase...
Page 72
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M13304-1 v12 Table 65. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
Page 73
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M13317-2 v12 Table 66. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 and step 2 (1.0-200.0)% of UBase ± 0.5% of U at U ≤...
Page 74
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 SEMOD166919-2 v6 Table 68. Voltage differential protection VDCPTOV Function Range or value Accuracy Voltage difference for alarm and (2.0–100.0) % of UBase ±0.5% of U trip UBase Under voltage level (1.0–100.0) % of ±0.5% of U Independent time delay for...
Page 75
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Frequency protection M13360-1 v13 Table 70. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function, at symmetrical three (35.00-75.00) Hz ±2.0 mHz phase voltage Operate time, start at f + 0.02 Hz to f - 0.02 Hz Min.
Page 76
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M14976-1 v8 Table 72. Rate-of-change frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz Definite restore time delay (0.000-60.000) s...
Page 78
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 74. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2- phase3, phase3-phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh-Ph Measuring voltage input...
Page 79
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 74. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, undervoltage at 1.2 to 0.8 x U , step 1 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater...
Page 80
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 SEMOD175176-2 v5 Table 75. Rotor earth fault protection based on General current and voltage protection (CVGAPC) and RXTTE4 Function Range or value For machines with: • rated field voltage up to 350 V DC •...
Page 81
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v7 Table 76. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
Page 82
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Secondary system supervision M12358-1 v8 Table 77. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I >...
Page 83
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v4 Table 79. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main (10.0-80.0)% of UBase ±0.5% of Ur fuse failure Reset ratio <110% Operate time, block of main fuse Min.
Page 84
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Control M12359-1 v12 Table 80. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of U at U ≤...
Page 85
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 SEMOD175215-2 v12 Table 81. Voltage control TCMYLTC and TLCYLTC Function Range or value Accuracy Transformer reactance (0.1–200.0)Ω, primary Time delay for lower command when fast step down mode is activated (1.0–100.0) s Voltage control set voltage (85.0–120.0)% of UBase...
Page 86
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 81. Voltage control TCMYLTC and TLCYLTC , continued Function Range or value Accuracy Time after position change before the value is accepted (1–60) s ±0.2% or ±200 ms whichever is greater Tap changer constant time-out (1–120) s...
Page 87
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Logic M12380-1 v9 Table 82. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater...
Page 88
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v1 Table 89. Number of GATE instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GATE GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v1 Table 90. Number of INV instances Logic block Quantity with cycle time 3 ms...
Page 89
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v1 Table 97. Number of XOR instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1 Table 98. Number of ANDQT instances Logic block Quantity with cycle time 3 ms...
Page 90
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-94C803B4-6C5A-4072-AB5C-20DDE98C9A70 v1 Table 105. Number of RSMEMORYQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms RSMEMORYQT GUID-341562FB-6149-495B-8A63-200DF16A5590 v1 Table 106. Number of SRMEMORYQT instances Logic block Quantity with cycle time 3 ms...
Page 91
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-3820F464-D296-4CAD-8491-F3F997359D79 v1 Table 111. Number of BTIGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms BTIGAPC GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v1 Table 112. Number of IB16 instances Function Quantity with cycle time 3 ms...
Page 92
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 117. Number of TEIGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms TEIGAPC GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1 Table 118. Running hour-meter TEILGAPC Function Range or value Accuracy Time limit for alarm supervision, tAlarm (0 - 99999.9) hours...
Page 93
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Monitoring M12386-1 v13 Table 119. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U≤ 50 V ±0.2% of U at U>...
Page 94
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v5 Table 122. Phase-neutral voltage measurement VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V Phase angle (5 to 175) V ±0.5 degrees at U ≤...
Page 95
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M12760-1 v9.1.1 Table 126. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out Time tagging resolution 1 ms...
Page 96
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v6 Table 128. Insulation liquid monitoring function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value Oil lockout level 1.00-100.00 ±10.0% of set value Temperature alarm level -40.00-200.00 ±2.5% of set value...
Page 97
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M12702-1 v4 Table 132. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report Maximum number of disturbance reports Resolution 1 ms Accuracy Depending on time synchronizing M13747-1 v5 Table 133.
Page 98
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Metering M13404-2 v5 Table 136. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value SEMOD153707-2 v4 Table 137.
Page 99
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Station communication M15031-1 v7 Table 138. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0 Communication speed for the IEDs...
Page 100
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 SEMOD117441-2 v5 Table 144. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000ft m typically *) Plastic fiber: 7 dB (25m/80ft m typically *) Fiber diameter Glass fiber: 62.5/125 mm...
Page 101
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 M12756-1 v8 Remote communication Table 148. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Graded-index Singlemode 9/125 Singlemode 9/125 µm...
Page 102
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Hardware M11778-1 v4 SEMOD53385-1 v1 Table 149. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v3 Table 150.
Page 103
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Injection equipment hardware GUID-EDF13DA3-4658-4A20-8641-CD62F6C3BE0F v3 Table 155. Injection unit REX060 Specifications Values Case size 6U, 1/2 19”; 223.7 x 245 x 267 mm (W x D x H) Weight 8.0 kg Burden, binary inputs...
Page 104
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 GUID-E7B9192F-ABD5-4395-94F2-ED0B2F0DFEB7 v3 Table 157. Shunt resistor unit REX062 Specifications Values Case size 218 x 150 x 243 mm (W x D x H) Weight 4.5 kg Assembling 6 x 5 mm screws (3 at bottom and 3 at top) Rated stator injection voltage 240 V Rated stator voltage...
Page 105
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Basic IED functions M11963-1 v5 Table 158. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v7 Table 159.
Page 106
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 SEMOD141136-2 v8 Table 162. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
Page 107
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Inverse characteristic M12388-1 v17 Table 163. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 ANSI/IEEE C37.112 , 1.5 x I ≤...
Page 108
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 164. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is greater æ...
Page 109
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 SEMOD116978-2 v8 Table 166. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
Page 110
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 167. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
Page 111
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 168. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater 0.01 æ...
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 21. Ordering for customized IED GUID-0076B561-1FF1-4A89-AC04-DF53A413E2AF v4.2.1 Table 169. General guidelines Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
Page 113
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 173. Differential protection Position Table 174. Differential functions Function Function Ordering no Positi Available Selected Notes and identification rules Transformer differential protection, two winding T2WPDIF 1MRK005904-FB Transformer differential protection, three winding T3WPDIF 1MRK005904-GA 1Ph High impedance differential protection...
Page 114
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 178. Current functions Function Function Ordering no Positi Available Selected Notes and identification rules Instantaneous phase overcurrent protection PHPIOC 1MRK005910-AC Four step phase overcurrent protection OC4PTOC 1MRK005910-BB Instantaneous residual overcurrent protection EFPIOC 1MRK005910-DC...
Page 115
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 185. General calculation Position Table 186. General calculation functions Function Function Ordering no Positi Available Selected Notes and identification rules Frequency tracking filter SMAIHPAC 1MRK005915-KA Table 187. Secondary system supervision Position Table 188.
Page 116
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 196. Station communication Position Table 197. Station communication functions Function Function Ordering no Position Available qty Selected Notes and rules identification Process Bus communication IEC 61850-9-2 1MRK005930-TA 0 if F00 is Note: REG670 selected, 6 if...
Page 117
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 202. Auxiliary power supply Selection Notes and Rules 24-60 VDC 90-250 VDC Selected Table 203. Human machine interface selection Human machine hardware interface Selection Notes and Rules Medium size - graphic display, IEC keypad symbols Medium size - graphic display, ANSI keypad symbols Selected...
Page 118
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 204. Analog system selection Analog system Selection Notes and Rules No first TRM included Note: Only valid in REG670–N00 Compression terminals Note: Only the same type of TRM (compression or ringlug) in the Ringlug terminals same terminal.
Page 119
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 205. Maximum quantity of I/O modules Note: When ordering I/O modules, observe the maximum quantities according to the table below Case sizes BOM/ Maximum in case 1/1 x 19”, one (1) TRM 14 cards, including a combination of four cards of type BOM, SOM and MIM 1/1 x 19”, two (2) TRM 11 cards, including a combination of four cards of type BOM, SOM and MIM...
Page 120
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 206. Binary input/output module selection Binary input/output Selection Notes and Rules modules Slot position (rear view) Note! Max 3 positions in 1/2 rack, 8 in 3/4 rack with 1 TRM, 5 in 3/4 rack with 2 TRM, 11 in 1/1 rack 1/2 Case with 1 TRM █...
Page 121
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Table 206. Binary input/output module selection, continued Binary input/output Selection Notes and Rules modules SOM Static output Note: SOM must not be placed in module, 12 outputs, the following positions: 1/2 case 48-60 VDC slot X51, 3/4 case 1 TRM slot X101, 3/4 case 2 TRM slot X71,...
Configuration alternatives Notes and Rules Generator differential and back-up Generator differential and generator/transformer back-up Generator/transformer differential and back-up ACT configuration ABB standard configuration Selection for position #2. Software options Notes and Rules No option All fields in the ordering form do...
Page 123
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 First local HMI user dialogue language Notes and Rules HMI language, English IEC Additional local HMI user dialogue language No additional HMI language HMI language, English US Selection for position #4. Casing Notes and Rules 1/2 x 19"...
Page 124
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Analog input system Notes and Rules Compression terminals Ringlug terminals First TRM, 9I+3U 1A, 110/220V Note: Only for B30/C30 First TRM, 9I+3U 5A, 110/220V Note: Only for B30/C30 First TRM, 5I, 1A+4I, 5A+3U, 110/220V Note: Only for B30/C30 First TRM, 7I+5U 1A, 110/220V...
Page 125
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Binary input/output module, mA and time synchronization boards. Notes and Rules Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfills additional standards. As a consequence the EMC withstand capability is further increased.
Page 126
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Remote end communication, DNP serial comm. and time synchronization Notes and Rules modules Slot position (rear view) Note: The maximum number and type of LDCM modules supported depend on the total amount of modules (BIM, BOM, LDCM, OEM, GTM, SLM, RS485, IRIG- B) in the IED.
Please refer to the website: (ordering number RK926 315-BH). www.abb.com/substationautomation for detailed information. Three winding transformer with internal neutral on current Due to the high flexibility of our product and the wide variety circuits (ordering number RK926 315-BX).
Page 128
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 External resistor unit SEMOD120228-4 v7 High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100V operating voltage Quantity: RK 795 101-MA High impedance resistor unit 3-ph with resistor and voltage dependent resistor for Quantity: RK 795 101-MB 20-100V operating voltage...
Page 129
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Injection equipment GUID-3447C871-562C-46B4-A36C-0B8B62D38E48 v5 Rule: If injection equipment is ordered, ROTIPHIZ or STTIPHIZSensitive rotor earth fault protection, injection based (option B31) or 100% stator earth fault protection, injection based (option B32) is required in the IED. Injection unit, REX060 Quantity: 1MRK 002 500-AA...
Page 130
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Combiflex IP15161-1 v1 Key switch for settings SEMOD130356-4 v5 Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used. SEMOD130267-5 v6 Mounting kit Ordering number...
Page 131
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 User documentation Rule: Specify the number of printed manuals requested Application manual Quantity: 1MRK 502 065-UEN ANSI Quantity: 1MRK 502 051-UUS Technical manual Quantity: 1MRK 502 066-UEN ANSI Quantity: 1MRK 502 052-UUS Commissioning manual...
Page 132
1MRK 502 068-BEN D Generator protection REG670 2.1 IEC Product version: 2.1 Engineering manual, 670 series Quantity: 1MRK 511 355-UEN ANSI Quantity: 1MRK 511 355-UUS Cyber security guideline Quantity: 1MRK 511 356-UEN Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name:...
Page 134
Contact us For more information please contact: Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. ABB AB ABB AB does not accept any responsibility whatsoever for potential Substation Automation Products errors or possible lack of information in this document.