Summary of Contents for Honeywell OneWireless XYR 6000
Page 1
(a) to persons who are not Honeywell employees, or (b) to Honeywell employees for whom such information is not necessary in connection with their assigned responsibilities.
Page 2
Added Multiple DI and Temperature DI to Table 1 p) Added note in French to Section 3.1 q) Added Table 7 for XYR 6000 with N connectors Added information for installation in Thailand OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008...
Table 14 – DSSS Transmit Power Settings for the antennas and cable lengths specified above for FCC, IC, ETSI, ACMA and TNTC approvals ............................22 Table 15 – Reference documents..........................28 OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008...
Honeywell OneWireless XYR 6000 Transmitters. 1.3 Preface This manual covers professional installation of the Honeywell OneWireless XYR 6000 Transmitters. See the Getting Started with Honeywell OneWireless, Honeywell OneWireless Planning Guide and Honeywell OneWireless XYR 6000 User’s Guides for general information on overall system implementation, configuration, and management of these devices.
Page 7
See Sections 13 and 14 for more information. OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008 Professional Installation Guide 50021956 Page 7 of 28...
1.5 Abbreviations & Definitions The term Honeywell XYR 6000 Transmitter will be used to describe the composite unit which includes the Honeywell FHSS or DSSS RF Module and all subassemblies housed within the XYR 6000 Transmitter enclosure. Table 2 –Table of Abbreviations and Definitions...
Furthermore, when using integral antenna(s) the XYR 6000 unit must not be co-located with any other antenna or transmitter device and have a separation distance of at least 20cm from all persons. OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B...
Denmark Norway Estonia Poland Finland Portugal France Romania Germany Slovakia Greece Slovenia Hungary Spain Iceland Sweden Ireland Switzerland Italy United Kingdom OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008 Professional Installation Guide 50021956 Page 11 of 28...
XYR 6000 TRANSMITTER GENERAL DESCRIPTION 7.1 Intended Use The XYR 6000 Transmitter is a key component of the Honeywell Wireless Network for Secure Industrial Application (WNSIA). These transmitters are available for various sensor types including Digital Inputs, Temperature, High Level Analog Inputs, Pressure and Corrosion.
+7.6 Vdc. An optional external +24 Volt power supply option will be available at a future date. 8.5 Weight The weight of the complete XYR 6000 Transmitter units shall be 14.0 lb. (6.4 kg) maximum. This weight does not include remote cables and antennas. OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008...
8.6 Dimensions Figure 2 – Dimensions of the XYR 6000 Transmitter with Right-angle -2 dBi Integral Antenna Option OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008 Professional Installation Guide 50021956 Page 15 of 28...
N male to N male 50018278-003 400 Series N male to N male 50018278-010 400 Series N male to N male OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008 Professional Installation Guide 50021956 Page 16 of 28...
1. The Centurion antenna listed in Table 10 has a specified gain of 2.2 dBi. Through EIRP measurements performed during antenna qualification testing, this antenna when installed in the Honeywell Radome and attached to the XYR 6000 Transmitter body in either the right-angle or straight integral antenna options has an actual gain of -2 dBi. This value is used in determining the maximum EIRP for Agency Compliance.
2454-2482.5 MHz FCC, IC 14 dBi Point to ETSI, ACMA, TNTC Directiona Multi- Remote France Point 2400-2454 MHz France Do not use OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008 Professional Installation Guide 50021956 Page 18 of 28...
France must limit EIRP to 10 dBm for operating modes utilizing frequencies in the range of 2,454 – 2,483.5MHz. For this reason, Honeywell does not recommend configuring frequency hopping modes that use this frequency range. For installations in France, use only the following OneWireless Frequency Hopping (FH) Mode Selections: EU Channel #1, EU Channel #7, NA/EU Guard Bands and NA/EU Channel 3 (FH Mode selections #4, 5, 8 and 10).
Page 20
14 dBi. Antenna types not included in this list or having a gain greater than 14 dBi are strictly prohibited for use with this device. The required antenna impedance is 50 ohms. OneWireless XYR 6000 Transmitter Honeywell Proprietary...
D 0 3 1 0 or D 1 0 0 3 3+10, 10+3 suppressor 14 dBi directional with D 1 0 1 0 10+10 suppressor OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008 Professional Installation Guide 50021956 Page 21 of 28...
All cables are 400 series types as specified in Table 6 and Table 7. 3. TX Power is set by the Honeywell factory producing the XYR 6000 to the values shown in the above tables. These factory values are determined by the customer’s model number selections in Table III for antenna type, cables and the...
TX Power setting is accomplished with the Authentication Device when a special application (app) is installed. This app is considered to be Honeywell sensitive material and is made available only to the qualified Professional Installer. When this app is installed in the AD, the XYR 6000 TX power setting, normally a read-only parameter, becomes a read/write parameter.
When using integral antenna(s) the XYR 6000 Transmitter unit must not be co-located with any other antenna or transmitter device and have a separation distance of at least 20 cm from all persons. OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B...
Factory Mutual Approval Standard Class No. 3611, “Electrical Equipment for Use in Class I, Division 2, Class II, Division 2 and Class III, Division 1 and 2 Hazardous (Classified) Locations • Temperature code: T4 (135°C) based on the maximum specified ambient of 85°C. OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008...
Radio Antenna: A Primer White Paper Honeywell OneWireless System Administration Guide Honeywell OneWireless Field Network Dictionary OneWireless Builder Parameter Reference OneWireless Builder User’s Guide OneWireless XYR 6000 Model Selection Guides OneWireless XYR 6000 Transmitter Honeywell Proprietary Rev B 27 August 2008...