Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by the third party testing laboratory Intertek in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Self-healing Ethernet ring............24 Ethernet redundancy..............25 Process bus.................27 Secure communication..............29 Protection communication and supervision......... 29 Section 3 RED615 standard configurations........31 Standard configurations..............31 Addition of control functions for primary devices and the use of binary inputs and outputs............34 Connection diagrams................35 Standard configuration C..............37...
This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering. The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as protection schemes and principles. RED615 Application Manual...
1.3.2 Document revision history Document revision/date Product version History A/2014-05-14 First release B/2014-09-12 4.1.1 Content updated to correspond to the product version C/2019-04-30 5.0 FP1 Content updated Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. RED615 Application Manual...
Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices. RED615 Application Manual...
When the function starts, the START output is set to TRUE. • This document assumes that the parameter setting visibility is "Advanced". 1.4.3 Functions, codes and symbols Table 1: RED615 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection...
Page 15
3Ith>T/G/C (1) 49T/G/C (1) protection, two time constants Binary signal transfer BSTGGIO1 BST (1) BST (1) Circuit breaker failure protection CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1) Three-phase inrush detector INRPHAR1 3I2f> (1) 68 (1) Table continues on next page RED615 Application Manual...
Page 16
I <-> O DC (3) I <-> O DC (3) Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1) ESSXSWI2 I <-> O ES (2) I <-> O ES (2) Table continues on next page RED615 Application Manual...
RED615 relays communicate between substations over a fiber ® optic link or a galvanic pilot wire connection. RED615 is a member of ABB’s Relion product family and part of its 615 protection and control product series. The 615 series relays are characterized by their compactness and withdrawable-unit design.
Additional timer, set-reset and analog value scaling functions 2.1.2 PCM600 and relay connectivity package version • Protection and Control IED Manager PCM600 2.9 Hotfix 1 or later • RED615 Connectivity Package Ver.5.1 or later • Parameter Setting • Signal Monitoring •...
Section 2 1MRS758127 C RED615 overview Download connectivity packages from the ABB Web site http://www.abb.com/substationautomation or directly with Update Manager in PCM600. Operation functionality 2.2.1 Optional functions • Autoreclosing • Modbus TCP/IP or RTU/ASCII • IEC 60870-5-103 • Admittance-based earth-fault protection (configuration D only) •...
Section 2 1MRS758127 C RED615 overview Main Slot ID Content options Case X130 AI/BI module Only with configuration D: 3 phase voltage inputs (60...210 V) 1 residual voltage input (60...210 V) 4 binary inputs AI/RTD/mA module Only with configuration D: 3 phase voltage inputs (60...210 V)
Section 2 1MRS758127 C RED615 overview The display view is divided into four basic areas. A070705 V3 EN Figure 3: Display layout 1 Header 2 Icon 3 Content 4 Scroll bar (displayed when needed) 2.4.2 LEDs The LHMI includes three protection indicators above the display: Ready, Start and Trip.
Section 2 1MRS758127 C RED615 overview A071176 V1 EN Figure 4: LHMI keypad with object control, navigation and command push buttons and RJ-45 communication port Web HMI The WHMI allows secure access to the protection relay via a Web browser. When the Secure Communication parameter in the protection relay is activated, the Web server is forced to take a secured (HTTPS) connection to WHMI using TLS encryption.The...
Section 2 1MRS758127 C RED615 overview GUID-38AF6905-4903-4C61-B22C-8509D99398E0 V1 EN Figure 5: Example view of the WHMI The WHMI can be accessed locally and remotely. • Locally by connecting the laptop to the protection relay via the front communication port. •...
Section 2 1MRS758127 C RED615 overview Table 6: Predefined user categories Username User rights VIEWER Read only access OPERATOR • Selecting remote or local state with (only locally) • Changing setting groups • Controlling • Clearing indications ENGINEER • Changing settings •...
Page 28
Section 2 1MRS758127 C RED615 overview Table 7: Audit trail events Audit trail event Description Configuration change Configuration files changed Firmware change Firmware changed Firmware change fail Firmware change failed Attached to retrofit test case Unit has been attached to retrofit case...
Section 2 1MRS758127 C RED615 overview (so-called horizontal communication) using the IEC 61850-8-1 GOOSE profile, where the highest performance class with a total transmission time of 3 ms is supported. Furthermore, the protection relay supports sending and receiving of analog values using GOOSE messaging.
HSR applies the PRP principle to rings and to the rings of rings to achieve cost- effective redundancy. Thus, each device incorporates a switch element that forwards frames from port to port. The HSR/PRP option is available for all 615 series protection relays. However, RED615 supports this option only over fiber optics. RED615 Application Manual...
Page 32
Section 2 1MRS758127 C RED615 overview IEC 62439-3:2012 cancels and replaces the first edition published in 2010. These standard versions are also referred to as IEC 62439-3 Edition 1 and IEC 62439-3 Edition 2. The protection relay supports IEC 62439-3:2012 and it is not compatible with IEC 62439-3:2010.
Section 2 1MRS758127 C RED615 overview • Via an external redundancy box (RedBox) or a switch capable of connecting to PRP and normal networks • By connecting the node directly to LAN A or LAN B as SAN • By connecting the node to the protection relay's interlink port HSR applies the PRP principle of parallel operation to a single ring, treating the two directions as two virtual LANs.
Page 34
Section 2 1MRS758127 C RED615 overview UniGear Digital switchgear concept relies on the process bus together with current and voltage sensors. The process bus enables several advantages for the UniGear Digital like simplicity with reduced wiring, flexibility with data availability to all devices, improved diagnostics and longer maintenance cycles.
The process bus option is available for all 615 series protection relays equipped with phase voltage inputs. Another requirement is a communication card with IEEE 1588 v2 support (COM0031...COM0037). However, RED615 supports this option only with the communication card variant having fiber optic station bus ports. See the IEC 61850 engineering guide for detailed system requirements and configuration details.
Page 36
Section 2 1MRS758127 C RED615 overview Apart from the continued protection communication, the communication channel can also be used for binary signal transfer (BST) that is, transferring of user configurable binary information between the relays. There are a total of eight BST signals available for user definable purposes.
The relay is delivered from the factory with default connections described in the functional diagrams for binary inputs, binary outputs, function-to-function connections and alarm LEDs. Some of the supported functions in RED615 must be added with the Application Configuration tool to be available in the Signal Matrix tool and in the relay.
Page 39
Section 3 1MRS758127 C RED615 standard configurations Function IEC 61850 Trip circuit supervision TCSSCBR Current circuit supervision CCSPVC Advanced current circuit supervision for line differential LNCTSRCTF Fuse failure supervision SEQSPVC1 Protection communication supervision PCSITPC1 Runtime counter for machines and devices...
Section 3 1MRS758127 C RED615 standard configurations 3.1.1 Addition of control functions for primary devices and the use of binary inputs and outputs If extra control functions intended for controllable primary devices are added to the configuration, additional binary inputs and/or outputs are needed to complement the standard configuration.
Section 3 1MRS758127 C RED615 standard configurations Connection diagrams RED615 X120 X100 BI 1 Positive Current Direction BI 2 BI 3 BI 4 Protection Core 1/5A 1/5A 1/5A 1/5A Earth Fault and CT Supervision Reference Current X110 BI 1 BI 2...
Page 42
Section 3 1MRS758127 C RED615 standard configurations RED615 X120 X100 BI 1 Positive Current Direction BI 2 BI 3 BI 4 1/5A 1/5A 1/5A 1/5A X130 BI 1 BI 2 TCS1 BI 3 BI 4 TCS2 60 - 210V U12B...
Section 3 1MRS758127 C RED615 standard configurations Standard configuration C 3.3.1 Applications The standard configuration for line current differential protection including non- directional earth-fault protection and autoreclosing is mainly intended for cable feeder applications in the distribution networks. The standard configuration for line current differential protection includes support for in-zone transformers.
Section 3 1MRS758127 C RED615 standard configurations 3.3.2 Functions RED615 LINE DIFFERENTIAL PROTECTION AND CONTROL RELAY STANDARD With in-zone power transformer support CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Binary Signal Transfer function (BST) 2× - Disturbance and fault recorder...
Page 45
Section 3 1MRS758127 C RED615 standard configurations Table 11: Default connections for analog inputs Analog input Description Connector pins Phase A current X120:7-8 Phase B current X120:9-10 Phase C current X120:11-12 Residual current X120:13-14 Table 12: Default connections for binary inputs...
Section 3 1MRS758127 C RED615 standard configurations Binary output Description Connector pins X110-SO4 X110:23-24 X130-SO1 X130:10-12 X130-SO2 X130:13-15 X130-SO3 X130:16-18 Table 14: Default connections for LEDs Description Line differential protection biased stage operate Line differential protection instantaneous stage operate Line differential protection is not available...
Page 47
Section 3 1MRS758127 C RED615 standard configurations Table 16: Default disturbance recorder binary channels Channel ID text Level trigger mode LNPLDF1 - start Positive or Rising LNPLDF1 - operate Positive or Rising PHIPTOC1 - start Positive or Rising PHHPTOC1 - start...
Page 48
Section 3 1MRS758127 C RED615 standard configurations Channel ID text Level trigger mode X110-BI3 - gas pressure alarm Level trigger off X120-BI3 - CB open Level trigger off X120-BI2 - CB closed Level trigger off X120-BI1 - ext OC blocking...
Section 3 1MRS758127 C RED615 standard configurations 3.3.3 Functional diagrams The functional diagrams describe the default input, output, alarm LED and function- to-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements. The analog channels have fixed connections to the different function blocks inside the protection relay’s standard configuration.
Page 51
Section 3 1MRS758127 C RED615 standard configurations PHIPTOC1_START UPSTREAM_OC_BLOCKING PHHPTOC1_START PHHPTOC2_START GUID-FFE28D0E-8985-4E5C-A14B-CB6DE0B30D72 V1 EN Figure 17: Upstream blocking logic Four stages are provided for non-directional earth-fault protection. According to the order code, the configuration can also include optional harmonics-based earth-fault protection HAEFPTOC1.
Page 52
Section 3 1MRS758127 C RED615 standard configurations INRPHAR1 BLOCK BLK2H INRPHAR1_BLK2H GUID-7F2BFC97-5C00-40C0-ABBA-3FC501D58D5D V1 EN Figure 19: Inrush detector function Two negative-sequence overcurrent protection stages NSPTOC1 and NSPTOC2 are provided for phase unbalance protection. These functions are used to protect the feeder against phase unbalance.
Page 53
Section 3 1MRS758127 C RED615 standard configurations T1PTTR1 BLK_OPR OPERATE T1PTTR1_OPERATE ENA_MULT START T1PTTR1_START TEMP_AMB ALARM T1PTTR1_ALARM BLK_CLOSE T1PTTR1_BLK_CLOSE T2PTTR1 BLOCK OPERATE T2PTTR1_OPERATE TEMP_AMB START T2PTTR1_START ALARM T2PTTR1_ALARM BLK_CLOSE T2PTTR1_BLK_CLOSE GUID-C71ADCD1-5E9F-47CF-AF75-D8CD007C423A V1 EN Figure 22: Thermal overcurrent protection function The negative-sequence overcurrent protection, phase discontinuity protection and earth-fault protection are all used as backup protection against line differential protection.
Section 3 1MRS758127 C RED615 standard configurations lockout and latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, binary input X120:BI4 can be assigned to RST_LKOUT input of both the trip logic to enable external reset with a push button.
Page 57
Section 3 1MRS758127 C RED615 standard configurations Set the parameters for SSCBR1 properly. SSCBR1 BLOCK TRV_T_OP_ALM SSCBR1_TRV_T_OP_ALM POSOPEN TRV_T_CL_ALM X120_BI3_CB_OPENED SSCBR1_TRV_T_CL_ALM POSCLOSE SPR_CHR_ALM X120_BI2_CB_CLOSED SSCBR1_SPR_CHR_ALM OPEN_CB_EXE OPR_ALM CB_OPEN_COMMAND SSCBR1_OPR_ALM CLOSE_CB_EXE OPR_LO CB_CLOSE_COMMAND SSCBR1_OPR_LO PRES_ALM_IN IPOW_ALM X110_BI3_GAS_PRESSURE_ALARM SSCBR1_IPOW_ALM PRES_LO_IN IPOW_LO SSCBR1_IPOW_LO...
Page 58
Section 3 1MRS758127 C RED615 standard configurations TCSSCBR1 BLOCK ALARM TCSSCBR_BLOCKING TCSSCBR1_ALARM TCSSCBR2 BLOCK ALARM TCSSCBR_BLOCKING TCSSCBR2_ALARM TCSSCBR1_ALARM TCSSCBR_ALARM TCSSCBR2_ALARM GUID-521ECF9A-25C2-4582-8D40-1EA572E4C847 V1 EN Figure 32: Trip circuit supervision function TRPPTRC1_TRIP TCSSCBR_BLOCKING TRPPTRC2_TRIP X120_BI3_CB_OPENED GUID-36DBAACC-5D67-414F-89E1-DAB5F6411181 V1 EN Figure 33: Logic for blocking of trip circuit supervision Protection communication supervision PCSITPC1 is used in the configuration to block the operation of the line differential function.
Section 3 1MRS758127 C RED615 standard configurations As a consequence of sending interlocking information to remote end, also receiving of same information locally is needed. Therefore, remote feeder ready, remote circuit breaker open and remote current transformer failure are connected to the binary signal transfer function outputs.
Page 60
Section 3 1MRS758127 C RED615 standard configurations If REMOTE_FEEDER_READY information is missing, for example, in case of protection communication not connected, it disables the breaker closing in the local protection relay. Any additional signals required by the application can be connected for opening and closing of circuit breaker.
Page 61
Section 3 1MRS758127 C RED615 standard configurations REMOTE_FEEDER_READY CBXCBR1_ENA_CLOSE LOCAL_FEEDER_READY AND6 DCSXSWI1_OKPOS LOCAL_FEEDER_READY ESSXSWI1_OPENPOS X110_BI4_CB_SPRING_CHARGED TRPPTRC1_TRIP TRPPTRC2_TRIP X110_BI3_GAS_PRESSURE_ALARM GUID-BB477666-A6B7-43C1-AE6B-D20528F6EDFC V1 EN Figure 41: Circuit breaker 1 close enable logic Connect higher-priority conditions before enabling the circuit breaker. These conditions cannot be bypassed with bypass feature of the function.
Section 3 1MRS758127 C RED615 standard configurations CONTROL_LOCAL FALSE CBXBCR1_AU_OPEN CONTROL_REMOTE FALSE GUID-B2A3DFEB-8777-40F7-AA7B-39FD2EEF3F09 V1 EN Figure 44: External opening command for circuit breaker 1 3.3.3.5 Functional diagrams for measurement functions The phase current inputs to the protection relay are measured by the three-phase current measurement function CMMXU1.
Section 3 1MRS758127 C RED615 standard configurations FLTRFRC1 BLOCK CB_CLRD GUID-557D77EF-39F9-4E45-B681-4214A621ABBF V2 EN Figure 48: Other measurement: Data monitoring LDPRLRC1 RSTMEM MEM_WARN MEM_ALARM GUID-86C0CEA1-CD8A-4D98-83DE-D9F56D43A917 V2 EN Figure 49: Other measurement: Load profile record 3.3.3.6 Functional diagrams for I/O and alarm LEDs X110_BI1_EXT_CCBRBRF_START X110 (BIO).X110-Input 1...
Section 3 1MRS758127 C RED615 standard configurations TPGAPC2 OUT1 BACKUP_PROT_OPERATE BACKUP_PROT_OPERATE_PULSE OUT2 EFxPTOC_OPERATE BACKUP_PROT_OPERATE PHxPTOC_OPERATE NSPTOC_OPERATE PDNSPTOC1_OPERATE GUID-E7E999CE-55E3-443A-95A2-4BF9339375AD V1 EN Figure 56: Timer logic for backup protection operate pulse 3.3.3.8 Other functions The configuration includes few instances of multipurpose protection MAPGAPC,...
Section 3 1MRS758127 C RED615 standard configurations 3.4.2 Functions RED615 LINE DIFFERENTIAL PROTECTION AND CONTROL RELAY STANDARD With in-zone power transformer support CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Binary Signal Transfer function (BST) 2× - Disturbance and fault recorder...
Section 3 1MRS758127 C RED615 standard configurations 3.4.2.1 Default I/O connections Connector pins for each input and output are presented in the Protection relay's physical connections section. Table 17: Default connections for analog inputs Analog input Description Connector pins Phase A current...
Section 3 1MRS758127 C RED615 standard configurations Table 19: Default connections for binary outputs Binary output Description Connector pins X100-PO1 Close circuit breaker X100:6-7 X100-PO2 Circuit breaker failure protection trip to upstream X100:8-9 breaker X100-SO1 Line differential protection operate alarm...
Page 71
Section 3 1MRS758127 C RED615 standard configurations Channel Description Table 22: Default disturbance recorder binary channels Channel ID text Level trigger mode LNPLDF1 - start Positive or Rising LNPLDF1 - operate Positive or Rising PHIPTOC1 - start Positive or Rising...
Page 72
Section 3 1MRS758127 C RED615 standard configurations Channel ID text Level trigger mode CCBRBRF1 - trbu Level trigger off LDPLDF1 - blkd2h Level trigger off LNPLDF1 - prot not active Level trigger off PHIPTOC1 - operate Level trigger off DPHHPDOC1 - operate...
Section 3 1MRS758127 C RED615 standard configurations 3.4.3.1 Functional diagrams for protection The functional diagrams describe the protection relay's protection functionality in detail and according to the factory set default connections. Line differential protection with in-zone power transformer LNPLDF1 is intended to be the main protection offering exclusive unit protection for the power distribution lines or cables.
Page 78
Section 3 1MRS758127 C RED615 standard configurations Non-directional (cross-country) earth-fault protection, using calculated Io, EFHPTOC protects against double earth-fault situations in isolated or compensated networks. This protection function uses the calculated residual current originating from the phase currents. EFHPTOC1 BLOCK...
Page 79
Section 3 1MRS758127 C RED615 standard configurations Two thermal overload protection functions are incorporated, one with one time constant T1PTTR1 and other with two time constants T2PTTR1 for detecting overloads under varying load conditions. The BLK_CLOSE output of the function is used to block the closing operation of circuit breaker.
Page 80
Section 3 1MRS758127 C RED615 standard configurations PHPTUV1 BLOCK OPERATE SEQSPVC1_FUSEF_U PHPTUV1_OPERATE START PHPTUV1_START PHPTUV2 BLOCK OPERATE SEQSPVC1_FUSEF_U PHPTUV2_OPERATE START PHPTUV2_START PHPTUV1_OPERATE PHPTUV_OPERATE PHPTUV2_OPERATE GUID-57AFB769-5CB0-41B2-9360-F705B44B2B2B V3 EN Figure 71: Undervoltage protection function The residual overvoltage protection ROVPTOV provides earth-fault protection by detecting an abnormal level of residual voltage.
Page 81
Section 3 1MRS758127 C RED615 standard configurations The overcurrent protection, negative-sequence overcurrent protection, phase discontinuity, earth-fault protection, residual overvoltage protection, phase overvoltage and undervoltage protection are all used as backup protection against line differential protection. The backup protection operated information is available at binary output X110:SO2 which can be used for external alarm purpose.
Page 82
Section 3 1MRS758127 C RED615 standard configurations feeding upstream. For this purpose, the TRBU operate output signal is connected to the binary output X100:PO2. CCBRBRF1 BLOCK CB_FAULT_AL START TRBU PHIPTOC1_OPERATE CCBRBRF1_TRBU POSCLOSE TRRET DPHHPDOC1_OPERATE CCBRBRF1_TRRET CB_FAULT DPHLPDOC1_OPERATE DEFHPDEF1_OPERATE DEFLPDEF2_OPERATE WPWDE2_OPERATE...
Page 86
Section 3 1MRS758127 C RED615 standard configurations SEQSPVC1 BLOCK FUSEF_3PH SEQSPVC1_FUSEF_3PH CB_CLOSED FUSEF_U X120_BI2_CB_CLOSED SEQSPVC1_FUSEF_U DISCON_OPEN X110_BI6_CB_TRUCK_IN_TEST MINCB_OPEN GUID-4A101AD2-2735-4154-9872-04E4AF5611C6 V2 EN Figure 81: Fuse failure supervision function The circuit breaker condition monitoring function SSCBR1 supervises the switch status based on the connected binary input information and the measured current levels.
Page 87
Section 3 1MRS758127 C RED615 standard configurations It is assumed that there is no external resistor in the circuit breaker tripping coil circuit connected in parallel with the circuit breaker normally open auxiliary contact. Set the parameters for TCSSCBR1 properly.
Section 3 1MRS758127 C RED615 standard configurations The binary signal transfer function BSTGGIO is used for changing any binary information which can be used for example, in protection schemes, interlocking and alarms. There are eight separate inputs and corresponding outputs available.
Page 89
Section 3 1MRS758127 C RED615 standard configurations The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or circuit breaker truck and earth-switch position status, status of the trip logics and remote feeder position indication.
Page 90
Section 3 1MRS758127 C RED615 standard configurations REMOTE_FEEDER_READY CBXCBR1_ENA_CLOSE LOCAL_FEEDER_READY AND6 DCSXSWI1_OKPOS LOCAL_FEEDER_READY ESSXSWI1_OPENPOS X110_BI4_CB_SPRING_CHARGED TRPPTRC1_TRIP TRPPTRC2_TRIP X110_BI3_GAS_PRESSURE_ALARM GUID-7A1BC865-FEEC-483B-902A-FA63B943377F V1 EN Figure 94: Circuit breaker 1 close enable logic Connect higher-priority conditions before enabling the circuit breaker. These conditions cannot be bypassed with bypass feature of the function.
Section 3 1MRS758127 C RED615 standard configurations CONTROL_LOCAL FALSE CBXBCR1_AU_OPEN CONTROL_REMOTE FALSE GUID-234BEA35-18B0-41CA-9B82-F7F4F098DBA7 V1 EN Figure 97: External opening command for circuit breaker 1 3.4.3.5 Functional diagrams for measurement functions The phase current inputs to the protection relay are measured by the three-phase current measurement function CMMXU1.
Page 92
Section 3 1MRS758127 C RED615 standard configurations RESCMMXU1 BLOCK HIGH_ALARM HIGH_WARN GUID-5F19BB51-E128-4264-92CE-80919279D13C V1 EN Figure 100: Current measurement: Residual current measurement VMMXU1 BLOCK HIGH_ALARM HIGH_WARN LOW_WARN LOW_ALARM GUID-185F1398-111B-4110-A7EF-A3DA5C402034 V1 EN Figure 101: Voltage measurement: Three-phase voltage measurement VMMXU2 BLOCK HIGH_ALARM...
Section 3 1MRS758127 C RED615 standard configurations FLTRFRC1 BLOCK CB_CLRD GUID-2FC37793-AF71-4854-A84A-70CCEEA56E32 V2 EN Figure 107: Other measurement: Data monitoring LDPRLRC1 RSTMEM MEM_WARN MEM_ALARM GUID-668FDBE4-A071-4F49-9142-2BCA9129622B V2 EN Figure 108: Other measurement: Load profile record 3.4.3.6 Functional diagrams for I/O and alarm LEDs X110_BI1_RST_LOCKOUT X110 (BIO).X110-Input 1...
(current metering, power metering, and so on) of the protection relay. The CT accuracy primary limit current describes the highest fault current magnitude at which the CT fulfils the specified accuracy. Beyond this level, the secondary current RED615 Application Manual...
Current start value < 0.7 × (I kmin is the nominal primary current of the CT. The factor 0.7 takes into account the protection relay inaccuracy, current transformer errors, and imperfections of the short circuit calculations. RED615 Application Manual...
The Current start value is the primary start current setting of the protection relay. 4.1.1.3 Example for non-directional overcurrent protection The following figure describes a typical medium voltage feeder. The protection is implemented as three-stage definite time non-directional overcurrent protection. RED615 Application Manual...
Page 102
F . In this application, the CT rated burden could have been selected much lower than 10 VA for economical reasons. RED615 Application Manual...
Residual current input Terminal Description X120:13-14 5.1.1.3 Phase voltages Table 26: Phase voltage inputs included in configuration D Terminal Description X130:11-12 X130:13-14 X130:15-16 5.1.1.4 Residual voltage Table 27: Additional residual voltage input included in configuration D Terminal Description X130:17-18 RED615 Application Manual...
X100:16 PO3, NO X100:17 PO3, NO X100:18 PO3 (TCS1 input), NO X100:19 PO3 (TCS1 input), NO X100:20 PO4, NO (TCS resistor) X100:21 PO4, NO X100:22 PO4, NO X100:23 PO4 (TCS2 input), NO X100:24 PO4 (TCS2 input), NO RED615 Application Manual...
In addition, a diagnostic kit is available as an ordering option for more advanced diagnostic and logging of diagnostic RED615 Application Manual...
Page 109
Diagnostic Tool software with a built-in help, required drivers and a special serial diagnostic cable to be connected to the console port of the modem. Fibre optic link MM or SM fiber optic RED615 RED615 Galvanic pilot wire link SM fibre optic SM fibre optic ≥...
A standard for connecting a family of frame-based computer networking technologies into a LAN FIFO First in, first out File transfer protocol FTPS FTP Secure GOOSE Generic Object-Oriented Substation Event Global Positioning System Human-machine interface High-availability seamless redundancy HTTPS Hypertext Transfer Protocol Secure RED615 Application Manual...
Page 112
A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices. Modbus TCP/IP Modbus RTU protocol which uses TCP/IP and Ethernet to carry data between devices Normally closed RED615 Application Manual...
Page 113
Instead of representing each of three phases with a separate line or terminal, only one conductor is represented. Single-line diagram Sampled measured values SNTP Simple Network Time Protocol Signal output Trip-circuit supervision Voltage transformer Wide area network WHMI Web human-machine interface RED615 Application Manual...