Honeywell GENT S4-34410 Data And Installation

Honeywell GENT S4-34410 Data And Installation

Interface modules for vigilon, low voltage (lv) input/output
Hide thumbs Also See for GENT S4-34410:

Advertisement

Data and Installation

Low voltage (LV) Input/Output

S4-34410
S4 1-Input Interface
Module
(low voltage)
1- End-of-line
Capacitor unit
2- 10K Resistors
These instructions cover the above interface
modules and accessories. The S4 interface
modules are designed for use with Vigilon and
34000 fire alarm control panel. Each module
includes a loop isolator for device isolation.
Each interface module use one of 207 available
device addresses on a loop and responds to
regular polls from the control panel reporting the
type of device and the status (open/normal/short) of
its supervised input circuit(s).

Features

¨
Analogue addressable communications
¨
Built-in type identification automatically identifies
these devices to the control panel
¨
Reliable communication technique with high
noise immunity
¨
Soft or SAFE addressing
¨
Common mounting options including surface
mount, panel mount and DIN rail mount
¨
Dual-colour LEDs
¨
Plug-in terminal connections for ease of field
wiring
¨
EN54-17:2005 and EN54-18:2005
Cables
The cables recommended for wiring the input /
output lines are the same as those used for loop
wiring, see instructions supplied with the fire control
panel.
4188-873_issue 4_Pt.1_02/09_S4 LV Interfaces
S4-34420
S4-34450
S4 1-Output &
# S4 4-Input / Output
1-Input Interface
Interface Module
Module (low voltage)
(low voltage)
Output
2- 10K Resistors
# Now supplied fully assembled
S4-34490
Plastic box
1- End-of-line
Capacitor unit
8- 10K Resistors

Installation

The S4 interface modules can be mounted in other
equipment housings using the DIN rail mount
brackets (S4-34491). A module can also be fitted
into a plastic box (S4-34490) or metal box
(S4-34492). The boxes have cable termination
points on the enclosure for incoming cables.
Module
Slide &
lock
Allen
key
Module
Door
M4 Screws
Metal
backbox
Lid
by Honeywell
1- Allen key
2 - M4 Screws
2 - M4 Posi Pan Screws
7 - Hole plugs
S4-34492
Metal box
S4-34491
DIN rail mount
bracket
Connect to loop
cable screen
DIN rail
Hook and push
to lock
DIN rail mount bracket
7 - top cable
62.5 62.5
entry points
Box
3 - box fixing points
(Includes 1-keyhole)
140
Module
M4 Screws
7 usable cable entry points
1

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell GENT S4-34410

  • Page 1 Data and Installation Interface Modules for Vigilon by Honeywell Low voltage (LV) Input/Output S4-34410 S4-34420 S4-34450 S4-34490 S4 1-Input Interface S4 1-Output & # S4 4-Input / Output Plastic box Module 1-Input Interface Interface Module (low voltage) Module (low voltage)
  • Page 2 Data and Installation Interfaces (Low voltage) to minimise false alarms by suppressing a fire input Maximum cable usage per circuit for a period of time defined during commissioning. & The zone reset period can be extended to allow for different types of fire detectors. Cable usage per circuit of: £Zone circuit - 100 metres maximum.
  • Page 3 Interfaces (Low voltage) Data and Installation Wiring diagrams & The loop cable screen must be continued through each interface module. The loop, switch input, zone input and LED output cable screens where used must connect to an earth terminal. S4 1-Input module S4 4-Input/Output module connection details connection details...
  • Page 4 Do not burn. Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes. Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK Website: www.gent.co.uk...
  • Page 5 MCC/MCB - version 3.94 / 4.37 ¨ LPC - version 3.93 / 4.35 For further information on upgrade requirements contact Gent by Honeywell. Click Configuration on the menu bar and Links on S4-34450 select LV Interface or alternatively click the LV icon on the tool bar.
  • Page 6 Commissioning information Interfaces (Low voltage) Channel modes Unused This option sets the channel as not used. Output This option sets the channel for either relay or LED output. As a relay output it provides a set of normally open or normally closed contacts. As an LED output it can be set to normally On (lit) or normally Off (not lit) drive for an LED load.
  • Page 7 Interfaces (Low voltage) Commissioning information Zone I/P " The Zone I/P is only applicable for Channel 1. This option sets the channel to accept the connection of conventional fire detectors and manual call points. A duration after which the input is accepted. Extendable reset duration with a default value of 2s plus this value.
  • Page 8 Keyswitch mode This feature is a future option. Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes.