− Training program information including the Siemens intranet link − A complete list of all available DMS8000 documents − Instructions for how to obtain a document via the Siemens intranet using the STEP Documentation Repository System − A map of relevant documents for each target audience group −...
Page 5
Liability disclaimer for damage or injuries Before products are delivered, they are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions, or the disregard of danger adviso- ries.
Introduction This is a guide to the software configuration procedures for the NICE and RIVER Digital Video Recorders (DVR) in the MM8000 Management Station. For a complete guide to the configuration process, this manual should be used with the DMS8000 Network, Fire and Intrusion Guide, and with the Installation, Configu- ration and Commissioning manual (ICC) of the specific product.
2.1.3 NICE/RIVER add-on installation The following are the installation procedures for the NICE/RIVER add-on module. 1. Start Add-on Manager; from the Windows Start menu, select the following: Start DMS8000 Tools Add-on Manager The Add-on Manager window appears (Fig. 1). 2. In the list of add-ons Names, select Nice or River depending on which product family you have to use.
Configuration Video integration The DMS8000 systems MM8000 and MK8000 can support the connection to the following NICE video systems (and to the corresponding RIVER products when applicable): Manufacturer Model Device type NICE NiceVision Alto Digital Video Recorder (DVR) NICE NiceVision Pro Digital Video Recorder (DVR) NICE NiceVision NVSat...
Video Drivers The VNM can support the driver required to handle the network communication with NICE/RIVER units. To add the driver to your project, proceed as follows: 1. Select the VNM node. 2. In the toolbar, click the icon corresponding to the NR driver (Fig. 3): Fig.
NICE/RIVER DVR configuration 3.5.1 Configuration checklist Verify that you have satisfied the items needed in the first checklist before proceed- ing to the configuration procedure that follows. ITEMS NEEDED FOR CONFIGURATION The NR Video driver installed and configured under the Video Network Manager in Composer The DVR IP address The camera connections...
Page 11
Connecting the cameras 1. Select and expand the DVR node. 2. Select and expand the DVR Video-in folder. 3. Add the required video inputs: note that input number can be customised. 4. Select and expand the Video Cameras folder. 5. Select the video-out node of the camera. 6.
Limitations Currently, the support of NICE/RIVER DVR units is subject to the following limita- tions (please check latest news with customer support): • Maximum number of connectable DVR units per Server or FEP is 150 (100 rec- ommended for best performance). •...
Operations MM8000 PTZ control panel MM8000 operations are described in the MM8000 Operation Manual (document no. A6V10062409). When operating with NICE/RIVER video systems in event treatment and plant browsing, a specific control panel is provided for the cameras equipped with PTZ control features.
Page 14
Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel +41 41 724 24 24 Fax +41 41 724 35 22 www.sbt.siemens.com Document no. A6V10097205_a_en DMS8000 Technical Material Edition 06.2009 Section 4...