Rotation Function for PAR-21MAA-J
User Guide
Change Temperature
Clock On/Off
Menu
Mode
Timer Up/Down
1.
Press "TEST" button for 3 seconds so that the
Maintenance Mode appears.
2.
After 3 seconds 00 will appear in a small square in the
middle of the remote this is the refrigerant address.
3.
Press "CHECK" button for 3 seconds to switch to
Maintenance Monitor
---- appears on the screen when Maintenance Monitor
4.
is activated
5.
Press the "TEMP UP / TEMP DOWN" to select the
desired refrigerant address i.e 00-01------ 015.
Press the "CLOCK UP/ CLOCK DOWN" to set the
6.
desired request code no. From 311~318 & 321~324
see list on opposite.
7.
Press "FILTER" button to perform the function settings.
If the above setting is entered correctly the request
code i.e 311will appear in the large square at the top
of the remote.
8.
You can check the current request code setting by
setting the request code i.e 311 and pressing the
"FILTER" button.
To return to the normal mode/screen press
9.
the "POWER ON/OFF" button.
>
Request Code List - Rotation Setting
Setting No
Setting Contents
(Request Code)
No 1 (310)
Monitoring the request code of current setting
No 2 (311)
Rotation and backup off (Normal group operation)
No 3 (312)
Back up function only
No 4 (313)
Rotation on(Alternating interval =1 day) and back up function
No 5 (314)
Rotation on(Alternating interval =3 day) and back up function
No 6 (315)
Rotation on(Alternating interval =5 day) and back up function
No 7 (316)
Rotation on(Alternating interval =7 day) and back up function
No 8 (317)
Rotation on(Alternating interval =14 day) and back up function
No 9 (318)
Rotation on(Alternating interval =28 day) and back up function
2nd unit Cut-in Setting
Setting No
Setting Contents
(Request Code)
No 1 (320)
Monitoring the request code of current setting
No 2 (321)
Cut function off
No 3 (322)
Cut-in function on(Set point = Set temp +4ºC)
No 4 (323)
Cut-in function on(Set point = Set temp +6ºC)
No 5 (324)
Cut-in function on(Set point = Set temp +8ºC)
www.mitsubishielectric.co.uk/aircon
On/Off
Fan Speed
Vane
Filter
Test
Check
Ventilation
Louvre Swing
Initial
Setting
O
Initial
Setting
O

Advertisement

loading

Summary of Contents for Mitsubishi Electric PAR-21MAA-J

  • Page 1 Technical Information > Rotation Function for PAR-21MAA-J User Guide Change Temperature On/Off Clock On/Off Fan Speed Menu Vane Mode Filter Test Timer Up/Down Check Ventilation Louvre Swing Request Code List - Rotation Setting Press “TEST” button for 3 seconds so that the Maintenance Mode appears.
  • Page 2 Related Links Model Number: PAR-21MAA M Series and Mr Slim Optional Parts PAR-21MAA Declaration of Conformity PAR-21MAA Instruction Book (WT05000X01) PAR-21MAA Installation Manual (WT05598X01) PAR-21MA_Instruction_Book_(WT05000X01) PAR-21MAA_User_Guide PAR-21MAA_Rotation_Guide PAR-21MA_Declaration_of_Conformity_(EU09005B) PAR-21MA_Installation_Manual_(WT05598X01) PAR-21MA_Parts_Catalog_(BWE0642A) PAR-21MA_Service_Manual_(MP0254A)