Summary of Contents for ABB Relion 615 Series

  • Page 1 ® Relion 615 series Voltage Protection and Control REU615 IEC 60870-5-103 Point List Manual...
  • Page 3 Document ID: 1MRS757055 Issued: 2013-02-21 Revision: C Product version: 4.0 FP1 © Copyright 2013 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............5 This manual..................5 Intended audience................5 Product documentation...............5 Product documentation set............5 Document revision history.............6 Related documentation..............6 Symbols and conventions..............7 Symbols..................7 Document conventions..............7 Functions, codes and symbols............8 Section 2 IEC 60870-5-103 data mappings........11 Overview...................11 Supported functions................11 Indications and controls..............13 General Data(FUN=0) IEC 60870-5-103 standard......13...
  • Page 8 Table of contents LD0.MAPGAPC3 Multipurpose analog protection function (3)....................21 LD0.MAPGAPC4 Multipurpose analog protection function (4)....................21 LD0.MAPGAPC5 Multipurpose analog protection function (5)....................21 LD0.MAPGAPC6 Multipurpose analog protection function (6)....................22 LD0.XRGGIO130 Alarm and warning..........22 LD0.PHPTOV3 Phase overvoltage protection - stage 3....22 LD0.PHPTOV2 Phase overvoltage protection - stage 2....22 LD0.PHPTOV1 Phase overvoltage protection - stage 1....23 LD0.PHPTUV3 Phase undervoltage protection - stage 3....23 LD0.PHPTUV2 Phase undervoltage protection - stage 2....23...
  • Page 9 Table of contents LD0.T2PTTR1 Thermal overload protection (2)......31 LD0.CMMXU1 Phase currents (1) limit supervision....31 LD0.VMMXU1 Phase voltage (1) limit supervision......32 LD0.RESVMMXU1 Residual voltage (1) limit supervision...32 CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection..................32 CTRL.DCXSWI1 Disconnector (1) - controllable object....33 CTRL.DCXSWI2 Disconnector (2) - controllable object....33 CTRL.ESXSWI1 Earth switch - controllable object.....33 CTRL.DCSXSWI1 Disconnector (1) - non-controllable...
  • Page 10 Table of contents Selection of standard information numbers in control direction..................43 System functions in control direction........43 Generic functions in monitor direction........43 Basic application functions............44 Miscellaneous................44 Section 4 Glossary.................45 REU615 Point List Manual...
  • Page 11: Section 1 Introduction

    Section 1 1MRS757055 C Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
  • Page 12: Document Revision History

    Content updated to correspond to the product version C/2013-02-21 4.0 FP1 Content updated to correspond to the product series version Download the latest documents from the ABB Website http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID IEC 60870-5-103 Communication Protocol Manual...
  • Page 13: Symbols And Conventions

    Section 1 1MRS757055 C Introduction Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
  • Page 14: Functions, Codes And Symbols

    Section 1 1MRS757055 C Introduction 1.4.3 Functions, codes and symbols Table 1: REU615 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent PHLPTOC1 3I> (1) 51P-1 (1) protection, low stage Three-phase non-directional overcurrent PHHPTOC1 3I>> (1) 51P-2 (1) protection, high stage Three-phase non-directional overcurrent...
  • Page 15 Section 1 1MRS757055 C Introduction Function IEC 61850 IEC 60617 IEC-ANSI Multi-purpose protection MAPGAPC1 MAP (1) MAP (1) MAPGAPC2 MAP (2) MAP (2) MAPGAPC3 MAP (3) MAP (3) MAPGAPC4 MAP (4) MAP (4) MAPGAPC5 MAP (5) MAP (5) MAPGAPC6 MAP (6) MAP (6) Load shedding and restoration LSHDPFRQ1...
  • Page 17: Section 2 Iec 60870-5-103 Data Mappings

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings Section 2 IEC 60870-5-103 data mappings Overview This document describes the IEC 60870-5-103 data points and structures available in the IED. The point lists describe a superset of all data available through the standard configuration/s.
  • Page 18 Section 2 1MRS757055 C IEC 60870-5-103 data mappings Function block UE01 UE02 T2PTTR1 ● TRPPTRC1 ● ● TRPPTRC2 ● ● ARCSARC1 ARCSARC2 ARCSARC3 MAPGAPC1 MAPGAPC2 MAPGAPC3 MAPGAPC4 MAPGAPC5 MAPGAPC6 LSHDPFRQ1 ● LSHDPFRQ2 ● LSHDPFRQ3 ● LSHDPFRQ4 ● LSHDPFRQ5 ● CBXCBR1 ●...
  • Page 19: Indications And Controls

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings Function block UE01 UE02 PEMMXU1 ● XRGGIO130 FMMXU1 ● ● = available in the device variant, o = optionally available in the device variant Indications and controls Table 3: Explanations of the indications and controls table columns Column name Description IEC 61850...
  • Page 20: General Data(Fun=10) - 615-Specific

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .ActSG.ctlVal/stVal Param setting group 5 10=SG 5 1,20 .ActSG.ctlVal/stVal Param setting group 6 10=SG 6 1,20 LD0.TCSSCBR1 .CirAlm.stVal ALARM Trip circuit 1 alarm 10=Alarm LD0.LEDPTRC1 .Op.general...
  • Page 21: Ld0.Mvgapc1 Multipurpose Binary Inputs (1)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.3 LD0.MVGAPC1 Multipurpose binary inputs (1) Table 6: LD0.MVGAPC1 Multipurpose binary inputs (1) IEC 61850 name SA name Description DPI value ASDU LD0.MVGAPC1 .Q1.stVal Input 1 signal 10=On .Q2.stVal Input 2 signal 10=On .Q3.stVal Input 3 signal...
  • Page 22: Ld0.Srgapc2 Multipurpose Binary Outputs - Flip-Flop Resets (2)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .Rs6.ctlVal Reset flip-flop 6 10=Reset .Rs7.ctlVal Reset flip-flop 7 10=Reset .Rs8.ctlVal Reset flip-flop 8 10=Reset 2.3.6 LD0.SRGAPC2 Multipurpose binary outputs - flip-flop resets (2) Table 9: LD0.SRGAPC2 Multipurpose binary outputs - flip-flop resets (2) IEC 61850 name...
  • Page 23: Ld0.Spcggio2 Multipurpose Binary Outputs (2)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .SPCS12.ctlVal Output control 12 10/01=On/Off .SPCS13.ctlVal Output control 13 10/01=On/Off .SPCS14.ctlVal Output control 14 10/01=On/Off .SPCS15.ctlVal Output control 15 10/01=On/Off .SPCS16.ctlVal Output control 16 10/01=On/Off 2.3.8 LD0.SPCGGIO2 Multipurpose binary outputs (2)
  • Page 24: Ctrl.ccrdif1 Current Circuit Failure Protection

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.10 CTRL.CCRDIF1 Current circuit failure protection Table 13: CTRL.CCRDIF1 Current circuit failure protection IEC 61850 name SA name Description DPI value ASDU CTRL.CCRDIF1 .Alm.stVal ALARM Fail Alarm 10=Alarm .Op.general FAIL Fail Operate 10=Operate 2.3.11 LD0.TPOSSLTC1 Tap position...
  • Page 25: Ld0.Frpfrq2 Frequency Protection (2)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.14 LD0.FRPFRQ2 Frequency protection (2) Table 17: LD0.FRPFRQ2 Frequency protection (2) IEC 61850 name SA name Description DPI value ASDU LD0.FRPTRC2 .Str.general START Stage start 10=Start LD0.FRPTOF2 Overfrequency .Op.general OPR_OFRQ -Operate 10=Operate LD0.FRPTUF2 Underfrequency .Op.general...
  • Page 26: Ld0.Frpfrq5 Frequency Protection (5)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.17 LD0.FRPFRQ5 Frequency protection (5) Table 20: LD0.FRPFRQ5 Frequency protection (5) IEC 61850 name SA name Description DPI value ASDU LD0.FRPTRC5 .Str.general START Stage start 10=Start LD0.FRPTOF5 Overfrequency .Op.general OPR_OFRQ -Operate 10=Operate LD0.FRPTUF5 Underfrequency .Op.general...
  • Page 27: Ld0.Mapgapc2 Multipurpose Analog Protection Function (2)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.20 LD0.MAPGAPC2 Multipurpose analog protection function Table 23: LD0.MAPGAPC2 Multipurpose analog protection function (2) IEC 61850 name SA name Description DPI value ASDU LD0.MAPGAPC2 .Str.general START Stage Start 10=Start .Op.general OPERATE Stage Operate 10=Operate 2.3.21 LD0.MAPGAPC3 Multipurpose analog protection function...
  • Page 28: Ld0.Mapgapc6 Multipurpose Analog Protection Function (6)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.24 LD0.MAPGAPC6 Multipurpose analog protection function Table 27: LD0.MAPGAPC6 Multipurpose analog protection function (6) IEC 61850 name SA name Description DPI value ASDU LD0.MAPGAPC6 .Str.general START Stage Start 10=Start .Op.general OPERATE Stage Operate 10=Operate 2.3.25 LD0.XRGGIO130 Alarm and warning...
  • Page 29: Ld0.Phptov1 Phase Overvoltage Protection - Stage 1

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.28 LD0.PHPTOV1 Phase overvoltage protection - stage 1 Table 31: LD0.PHPTOV1 Phase overvoltage protection - stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.PHPTOV1 Stage 1 .Str.phsA -phsA start 10=Start .Str.phsB -phsB start...
  • Page 30: Ld0.Phptuv1 Phase Undervoltage Protection - Stage 1

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.31 LD0.PHPTUV1 Phase undervoltage protection - stage 1 Table 34: LD0.PHPTUV1 Phase undervoltage protection - stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.PHPTUV1 Stage 1 .Str.phsA -phsA start 10=Start .Str.phsB -phsB start...
  • Page 31: Ld0.Nsptov1 Negative-Sequence Overvoltage Protection - Stage 1

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.35 LD0.NSPTOV1 Negative-sequence overvoltage protection - stage 1 Table 38: LD0.NSPTOV1 Negative-sequence overvoltage protection - stage 1 IEC 61850 name SA name Description DPI value ASDU LD0.NSPTOV1 Stage 1 .Str.general START -general start 10=Start .Op.general OPERATE...
  • Page 32: Ld0.Xggio130 Physical Binary I/O Signals (Status Only)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.39 LD0.XGGIO130 Physical binary I/O signals (status only) Table 42: LD0.XGGIO130 Physical binary I/O signals (status only) IEC 61850 name SA name Description DPI value ASDU LD0.XGGIO130 .Ind1.stVal X130-Input 1 10/01=On/Off .Ind2.stVal X130-Input 2 10/01=On/Off .Ind3.stVal...
  • Page 33: Ld0.Xggio100 Physical Binary I/O Signals (Status Only)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .SPCSO2.stVal X110-Output 2 10/01=On/Off .SPCSO3.stVal X110-Output 3 10/01=On/Off .SPCSO4.stVal X110-Output 4 10/01=On/Off 2.3.42 LD0.XGGIO100 Physical binary I/O signals (status only) Table 45: LD0.XGGIO100 Physical binary I/O signals (status only) IEC 61850 name SA name Description...
  • Page 34: Ld0.Lshdpfrq1 Load Shedding - Instance 1

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.44 LD0.LSHDPFRQ1 Load shedding - instance 1 Table 47: LD0.LSHDPFRQ1 Load shedding - instance 1 IEC 61850 name SA name Description DPI value ASDU LD0.LSHDPTRC1 .Str.general START Stage start 10=Start .Op.general OPERATE Stage operate 10=Operate .RestLodStr.general...
  • Page 35: Ld0.Lshdpfrq4 Load Shedding - Instance 4

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.47 LD0.LSHDPFRQ4 Load shedding - instance 4 Table 50: LD0.LSHDPFRQ4 Load shedding - instance 4 IEC 61850 name SA name Description DPI value ASDU LD0.LSHDPTRC4 .Str.general START Stage start 10=Start .Op.general OPERATE Stage operate 10=Operate .RestLodStr.general...
  • Page 36: Ld0.Arcsarc2 Fault Arc Protection - Stage 2

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.50 LD0.ARCSARC2 Fault arc protection - stage 2 Table 53: LD0.ARCSARC2 Fault arc protection - stage 2 IEC 61850 name SA name Description DPI value ASDU LD0.ARCSARC21 .FADet.stVal ARC_FLT_DE T Arc detected 10=Detect LD0.ARCPTRC21 .Op.general...
  • Page 37: Ld0.Phlptoc1 Phase Overcurrent Protection - Low Stage 1

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .Str.phsC -phsC start 10=Start .Op.general OPERATE -general operate 10=Operate .Str.general START -general start 10=Start 2.3.54 LD0.PHLPTOC1 Phase overcurrent protection - low stage 1 Table 57: LD0.PHLPTOC1 Phase overcurrent protection - low stage 1 IEC 61850 name...
  • Page 38: Ld0.Vmmxu1 Phase Voltage (1) Limit Supervision

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.57 LD0.VMMXU1 Phase voltage (1) limit supervision Table 60: LD0.VMMXU1 Phase voltage (1) limit supervision IEC 61850 name SA name Description DPI value ASDU LD0.VMMXU1 .HiAlm.stVal HIGH_ALARM High alarm 10=Alarm .HiWrn.stVal HIGH_WARN High warning 10=Warning .LoWrn.stVal...
  • Page 39: Ctrl.dcxswi1 Disconnector (1) - Controllable Object

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.60 CTRL.DCXSWI1 Disconnector (1) - controllable object Table 63: CTRL.DCXSWI1 Disconnector (1) - controllable object IEC 61850 name SA name Description DPI value ASDU CTRL.DCCILO1 .EnaOpn.stVal ENA_OPEN Open enabled 10=Enabled .EnaCls.stVal ENA_CLOSE Close enabled 10=Enabled .ItlByPss.stVal...
  • Page 40: Ctrl.dcsxswi1 Disconnector (1) - Non-Controllable Object

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings IEC 61850 name SA name Description DPI value ASDU .BlkCls.stVal BLK_CLOSE Close blocked 10=Blocked CTRL.ESCSWI1 .stSeld.stVal SELECTED ES selected 10=Selected .Pos.stVal/ctlVal POSITION ES pos/control 10/01=Close/Open 1,20 2.3.63 CTRL.DCSXSWI1 Disconnector (1) - non-controllable object Table 66: CTRL.DCSXSWI1 Disconnector (1) - non-controllable object IEC 61850 name...
  • Page 41: Ld0.Ledggio1 Lhmi Led Indications Type 1 (2 States)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.3.68 LD0.LEDGGIO1 LHMI LED indications Type 1 (2 states) Table 71: LD0.LEDGGIO1 LHMI LED indications Type 1 (2 states) IEC 61850 name SA name Description DPI value ASDU LD0.LEDGGIO1 .ISCSO1.stVal LED 1 state 10=On .ISCSO2.stVal LED 2 state...
  • Page 42 Section 2 1MRS757055 C IEC 60870-5-103 data mappings Start Length Length Start Cntrl Addr Link user data Csum ASDU Addr Measurand data Meas value ix1 Meas value ix2 Meas value ix3 Meas value ix4 Meas value ixN GUID-7FE191AF-F805-4C25-ACA1-7296D59448D7 V1 EN Figure 1: Class 2 frame response in the predefined private Class 2 frames, numbers 6 or 7...
  • Page 43: Class 2 Private Measurand Data (6 And 7)

    Section 2 1MRS757055 C IEC 60870-5-103 data mappings 2.4.1 Class 2 private measurand data (6 and 7) Table 74: Class 2 private measurand data (6 and 7) IEC 61850 name Description Scale ix (U-a) LD0.CMMXU1 Phase currents (1) LD0.CMMXU1 Phase-to-ground current .A.phsA.cVal.mag -phsA magnitude .A.phsB.cVal.mag...
  • Page 44 Section 2 1MRS757055 C IEC 60870-5-103 data mappings IEC 61850 name Description Scale ix (U-a) LD0.PEMMXU1 Power measurands (1) LD0.PEMMXU1 .TotW.instMag Active power P value 1000 .TotVAr.instMag Reactive power Q value 1000 .TotVA.instMag Apparent power S value 1000 .TotPF.instMag Power factor value LD0.FMMXU1 Frequency measurement (1) LD0.FMMXU1 .Hz.Mag...
  • Page 45: Section 3 Interoperability Profile For 615 Series Iec 60870-5-103

    Section 3 1MRS757055 C Interoperability profile for 615 series IEC 60870-5-103 Section 3 Interoperability profile for 615 series IEC 60870-5-103 Physical layer 3.1.1 Electrical interface ⊠ EIA RS-485 ⃞ Number of loads ......for one protection equipment NOTE - EIA RS-485 standard defines unit loads so that 32 of them can be operated on one line. For detailed information refer to clause 3 of EIA RS-485 standard.
  • Page 46: Application Layer

    Section 3 1MRS757055 C Interoperability profile for 615 series IEC 60870-5-103 Application layer 3.3.1 Transmission mode for application data Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion standard. 3.3.2 COMMON ADDRESS of ASDU ⊠...
  • Page 47: Supervision Indications In Monitor Direction

    Section 3 1MRS757055 C Interoperability profile for 615 series IEC 60870-5-103 ⃞ <27> Auxiliary input 1 ⃞ <28> Auxiliary input 2 ⃞ <29> Auxiliary input 3 ⃞ <30> Auxiliary input 4 Note <27>...<30>: Depending on Binary I/O options and application usage there may be additional auxiliary inputs available in the IED.
  • Page 48: Auto-Reclosure Indications In Monitor Direction

    Section 3 1MRS757055 C Interoperability profile for 615 series IEC 60870-5-103 ⃞ <66> Start /pick-up L ⃞ <67> Start /pick-up N ⊠ <68> General trip ⃞ <69> Trip L ⃞ <70> Trip L ⃞ <71> Trip L ⃞ <72> Trip I>> (back-up operation) ⃞...
  • Page 49: Measurands In Monitor Direction

    Section 3 1MRS757055 C Interoperability profile for 615 series IEC 60870-5-103 3.3.3.7 Measurands in monitor direction Semantics ⊠ <144> Measurand I ⊠ <145> Measurands I, V ⊠ <146> Measurands I, V, P, Q ⊠ <147> Measurands I ⊠ <148> Measurands I , P, Q, f L1,2,3 L1,2,3...
  • Page 50: Basic Application Functions

    Section 3 1MRS757055 C Interoperability profile for 615 series IEC 60870-5-103 3.3.5 Basic application functions ⊠ Test mode ⃞ Blocking of monitor direction ⊠ Disturbance data ⃞ Generic services ⊠ Private data 3.3.6 Miscellaneous Measurands are transmitted as Class2 data using ASDU 3 or ASDU 9. The default MVAL scalings in this IED series is 2.4.
  • Page 51: Section 4 Glossary

    Section 4 1MRS757055 C Glossary Section 4 Glossary Autoreclosing Electromagnetic compatibility Human-machine interface International Electrotechnical Commission IEC 60870-5-103 1. Communication standard for protective equipment 2. A serial master/slave protocol for point-to-point communication IEC 61850 International standard for substation communication and modeling Intelligent electronic device IET600...