hit counter script

Setting Feed-In At Limited Current - Huawei SUN2000-20KTL-M3 User Manual

Hide thumbs Also See for SUN2000-20KTL-M3:
Table of Contents

Advertisement

SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual
Parameter
Shutdo
Shutdown at high feed-in
wn at
power
high
feed-in
a
power
Upper feed-in power
threshold for inverter
shutdown (kW)
High feed-in power duration
threshold for triggering
inverter shutdown (s)
Note a: This parameter is supported only for the AS4777 or G99-TYPEA-LV grid code.
----End

7.3.2 Setting Feed-in at Limited Current

Function
The output current of the PV power system can be limited or reduced to ensure
that the output current is within the specified range.
This function applies only to the commercial and industrial (C&I) scenarios in the
UK where the grid code is G99-TYPEA-LV, G99-TYPEB-LV, G99-TYPEB-HV, G99-
TYPEB-HV-MV480, or G99-TYPEA-HV. The SUN2000 app version must be later
than 6.24.00.563.
Issue 18 (2024-03-10)
Description
Communication
In the inverter export limitation scenario, if this
disconnection
parameter is set to Enable, the inverter will derate
fail-safe
according to the active power derating percentage when
the communication between the inverter and the Smart
Dongle is disconnected for a period longer than
Communication disconnection detection time.
Communication
Specifies the fail-safe detection time in case of
disconnection
disconnection between the inverter and the Smart
detection time
Dongle.
This parameter is displayed when Communication
disconnection fail-safe is set to Enable.
● The default value is Disable.
● If this parameter is set to Enable, the inverter shuts
The default value is 0. This parameter specifies the
power threshold of the grid-tied point for triggering
inverter shutdown.
The default value is 20. This parameter specifies the
duration threshold of high feed-in power for triggering
inverter shutdown.
● When High feed-in power duration threshold for
● When High feed-in power duration threshold for
Copyright © Huawei Technologies Co., Ltd.
down for protection when the power at the grid-tied
point exceeds the threshold and remains in this
condition for the specified time threshold.
triggering inverter shutdown is set to 5, Shutdown
at high feed-in power takes precedence.
triggering inverter shutdown is set to 20, Grid
connection with limited power takes precedence
(when Active power control is set to Grid
connection with limited power).
7 Human-Machine Interaction
75

Advertisement

Table of Contents
loading

Table of Contents