This document describes the requirements and wiring instructions for a –48 VDC power cable and safety ground wire for systems equipped with a –48 VDC power supply. CAUTION: A qualified electrician must perform all connections to DC power and safety grounds. The system must be safety grounded at the cabinet frame. All electrical wiring must comply with applicable local or national codes and practices.
Input Requirements Supply voltage: –(48–60) VDC Current consumption: Kit Contents • AMP 794949-1 connector housing, or equivalent • AMP 350218-1 connector contacts, or equivalent • AMP 2-36161-5 ring-tongue terminal, or equivalent • #6-32 nut equipped with lock washer • Heat-shrink tubing Required Tools •...
Page 5
To construct the DC input power cable, perform the following steps: Strip the insulation from the ends of the six DC power wires, exposing approximately 4.5 mm (0.175 inches) of copper wire. Using a hand-crimping tool, crimp a connector contact to each DC power wire. Slide a piece of heat-shrink tubing over the DC power cable.
Page 6
Assembling the Safety Ground Wire Strip the insulation from the end of the green/yellow wire, exposing approximately 4.5 mm (0.175 inches) of copper wire. Using a hand-crimping tool, crimp the ring-tongue terminal to the green/yellow wire. Connecting the –48 VDC Power Cable and Safety Ground Connect the safety ground to the grounding post on the back of the system using a #6-32 nut equipped with a locking washer (see Figure 1-2).
Page 8