Remote CAN Digital I/O Module
Instruction manual
GEK-106465A
Copyright © 2006 GE Multilin
GE Multilin
Avda. Pinoa, 10
48170 Zamudio SPAIN
T +34 94 485 88 00 F +34 94 485 88 45
E gemultilin.euro@ge.com

Advertisement

Table of Contents
loading

Summary of Contents for GE GEK-106465A

  • Page 1 GE Consumer & Industrial Multilin Remote CAN Digital I/O Module Instruction manual GEK-106465A Copyright © 2006 GE Multilin GE Multilin Avda. Pinoa, 10 48170 Zamudio SPAIN T +34 94 485 88 00 F +34 94 485 88 45 E gemultilin.euro@ge.com...
  • Page 2: Table Of Contents

    3.2.2. REAR COVER DESCRIPTION ...16 3.3. WIRING 3.3.1. EXTERNAL CONNECTIONS ...17 3.4. BOARDS 3.4.1. BOARD OPTION 1 ...19 3.4.2. BOARD OPTION 2 ...20 USER INTERFACES 4.1. SOFTWARE 4.2. FRONT INDICATORS GEK-106465A TABLE OF CONTENTS CIO Remote CAN Digital I/O Module...
  • Page 3 CONTROL SETTINGS FOR INPUTS/OUTPUTS 5.2.1. INPUT/OUTPUT BOARDS SETTINGS...32 5.2.2. INPUTS/OUTPUTS STATUS ...36 ACCEPTANCE TESTS 6.1. VISUAL INSPECTION 6.2. GENERAL CONSIDERATIONS ON THE POWER SUPPLY NETWORK 6.3. ISOLATION TESTS 6.4. INDICATORS 6.5. POWER SUPLY TESTING 6.6. COMMUNICATION WITH THE MASTER UNIT 6.7.
  • Page 4: Overview

    MANNER NOT SPECIFIED IN THIS MANUAL, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED FIGURE 1-1 CIO FRONT VIEW Installation must be according to the national electric code of the appropriate country GEK-106465A CIO Remote CAN Digital I/O Module...
  • Page 5: Inspection Checklist

    - Please ensure that you receive the following items with your CIO unit: - Mounting screws for rear terminals and for fixing the relay to a cabinet - Wiring diagram For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin Home Page www.GEMultilin.com. OVERVIEW...
  • Page 6 Note: If there is any physical damage detected on the relay, or any of the contents listed are missing, please contact GE Multilin immediately at: The information provided herein does not intend to cover all details of variations of the equipment nor does it take into account the circumstances that may be present in your installation, operating or maintenance activities.
  • Page 7: Safety Instructions

    This is required not only for personal protection, but also for avoiding a voltage difference between the CIO serial port and the master unit port, which could produce anomalies in communication. GE Multilin will not be responsible for any damage in the relay or connected equipment whenever this elemental safety rule is not followed.
  • Page 8: Overview

    CIO units respond to this need, allowing connection to F650 and F600 IEDs, and increasing the number of available inputs and outputs depending on the connected equipment. 1.2.2. HARDWARE ARCHITECTURE CIO units incorporate a series of interconnected modules to operate. These modules are a power supply and input/output boards. Contact Inputs Contact Outputs...
  • Page 9: Communications Architecture

    CIO unit. For connections including several CIO units, the cable port must be used. If the master unit is a F650, then communication must always be in fiber optic. CIO Remote CAN Digital I/O Module GEK-106465A...
  • Page 10: Product Description

    Possibility to select pulse or level activation. OUTPUTS Outputs programmable from the master unit Possibility to select positive or negative activation logic Selectable pulse mode activation Selectable latched configuration Breaker tripping and Closing circuits supervision GEK-106465A PRODUCT DESCRIPTION CIO Remote CAN Digital I/O Module...
  • Page 11: Ordering Code

    ORDERING CODE CIO units are available in 1/3 19’’ rack, 6 units high, and it includes a power supply module and a communication module, plus a maximum of two I/O modules. Each of these modules can be supplied in different versions, which must be specified when ordering.
  • Page 12: Technical Specifications

    Interruptions: Baudrate: Media: Operation temperature: Storage temperature: Humidity: GEK-106465A PRODUCT DESCRIPTION Programmable from 1 up to 255 Vdc in steps of 1 V > 100 kOhm 2 mA + V/100 kOhm <1 m 1 to 50 ms in steps of 1 ms...
  • Page 13: Packaging And Weight

    0Hz to 150 kHz immunity test. Surge immunity test Noise MHz. Oscillatory immunity test. Electrical fast transient/burst immunity test Immunity to conducted disturbances, induced by radio-frequency fields Conducted and radiated emissions class Insulation 2.4.8. APPROVALS GEK-106465A field waves...
  • Page 14: Hardware

    Optionally, a second I/O module can be added. A relay connected to the low voltage side of the power supply monitors this voltage. The three contact terminals, normally open, common, and normally closed, are available at the external connector terminals. This relay monitors only the power supply integrity.
  • Page 15: Mechanical Description

    The unit is designed for both semi-flush mounting with the terminals on the back, and rear panel mounting, with the terminals towards the front. In both cases the relay should be secured to the panel with the M6 screws provided with the unit. FIGURE 3-2 SEMI-FLUSH MOUNTING CIO Remote CAN Digital I/O Module GEK-106465A...
  • Page 16 O 0 , 3 " 7 , 0 GEK-106465A HARDWARE FIGURE 3-3 REAR PANEL MOUNTING 5, 3 " 134, 0 4 , 5 " 1 1 4, 0 7 ,5 " 1 9 0 , 5 FIGURE 3-4 DRILLING DIMENSIONS CIO Remote CAN Digital I/O Module 10 , 3 "...
  • Page 17: Rear Cover Description

    Unit wiring is performed through the terminal blocks located on the rear. The rest of the terminal blocks for power supply, inputs/outputs, incorporate high quality connectors with the capacity to withstand a rated current of 15 A at 300 V. These terminal blocks admit a cable section of up to 2.5 mm (AWG 12).
  • Page 18: Wiring

    Board with 8 digital inputs, 4 circuit supervision outputs, 6 conventional outputs, and two current sensing outputs Each model has a different wiring diagram, as follows: FIGURE 3-5 WIRING DIAGRAM FOR MODELS CIOH2J1 (226B5113F1) GEK-106465A HARDWARE CIO Remote CAN Digital I/O Module 3.3.1.
  • Page 19 HARDWARE FIGURE 3-6 WIRING DIAGRAM FOR MODEL CIOH1J1 (226B5113F2) CIO Remote CAN Digital I/O Module GEK-106465A...
  • Page 20: Boards

    BOARDS CIO I/O board option 1 includes 16 inputs grouped in two series of 8 inputs with a common, and 8 conventional inputs. FIGURE 3-7 shows the location of terminals for both types of board: GEK-106465A HARDWARE MIXED SUPERVISION TERMINA...
  • Page 21: Board Option 2

    Inputs in both groups are wet contacts, this means they need to receive a positive in the terminal labeled as + coming from a power supply whose negative is connected to the terminal labelled as -. Using voltage detectors and current sensing, it is possible to implement several trip or close circuit supervision schemes, as well as protection of the unit output contact.
  • Page 22 This is a very frequent case, and we must only wire the tripping circuit to terminals 35 and 36, leaving unused terminals 34, 15, 16, 17, 18. FIGURE 3-8 CIRCUIT WITHOUT TRIPPING CIRCUIT SUPERVISION (A6631F1) GEK-106465A CIO Remote CAN Digital I/O Module...
  • Page 23 0.5 A at 125 Vdc. This latching or memory function is only guaranteed while the unit is powered. FIGURE 3-9 CURRENT SUPERVISION OF THE TRIPPING CONTACT (A6631F2) CIO Remote CAN Digital I/O Module GEK-106465A...
  • Page 24 HARDWARE 3.4.2.3. WITH SIMPLE VOLTAGE SUPERVISION FIGURE 3-10 SUPERVISION APPLICATION WITH AUXILIARY CONTACT 52A AND A RESISTOR (A6631F3) GEK-106465A CIO Remote CAN Digital I/O Module...
  • Page 25 ON (if t < 500 ms) OFF (if t > 500 ms) ON (if t < 500 ms) OFF (if t > 500 ms) OFF (500 ms delay) OFF (500 ms delay) OFF (500 ms delay) OFF (500 ms delay) GEK-106465A...
  • Page 26 CONTACT INPUT_00_15 (SUP_COIL2), will be activated showing a failure when the breaker is open, and therefore it will be required to supervise the continuity failure signalling by the breaker status information. GEK-106465A HARDWARE CIO Remote CAN Digital I/O Module...
  • Page 27 HARDWARE FIGURE 3-11 TRIP CIRCUIT AND TRIP COIL SUPERVISION USING AUXILIARY CONTACT 52/A. ONLY WITH CLOSED BREAKER (A6631F5) CIO Remote CAN Digital I/O Module GEK-106465A...
  • Page 28 HARDWARE 3.4.2.4. WITH DOUBLE VOLTAGE SUPERVISION FIGURE 3-12 SUPERVISION APPLICATION WITH AUXILIARY CONTACTS 52A AND 52B (A6631F4) GEK-106465A CIO Remote CAN Digital I/O Module...
  • Page 29 ON (if t < 500 ms) OFF (if t > 500 ms) ON (if t < 500 ms) OFF (if t > 500 ms) OFF (500 ms delay) OFF (500 ms delay) OFF (500 ms delay) OFF (500 ms delay) GEK-106465A...
  • Page 30: User Interfaces

    EnerVista F650Setup program; in case of using an F600 as master unit, the CIO can be programmed using GE-CONF software. In both cases, CIO inputs/outputs will be shown as if they were part of the master unit, with the same programming options as the master unit I/O.
  • Page 31 USER INTERFACES CIO Remote CAN Digital I/O Module GEK-106465A...
  • Page 32: Gek-106465A Cio Remote Can Digital I/O Module

    The circuit and the current threshold of the function are as follows: 100 mA min FIGURE 5-1 CURRENT SUPERVISION GEK-106465A CIO Remote CAN Digital I/O Module...
  • Page 33: Control Settings For Inputs/Outputs

    CONTROL SETTINGS FOR INPUTS/OUTPUTS This section explains the settings related to CIO inputs/outputs. Modification of these values is performed using the master unit communication software, EnerVista F650Setup for F650, or GE-CONF for F600. Settings relative to I/O boards are described in table 5-1:...
  • Page 34 Is the name used for the different outputs in I/O boards, 8 outputs available for any of the two types of board (01,…., 08) Description of I/O board settings is as follows: General Board Settings: I/O Board Type: Selection of the I/O board type. GEK-106465A I/O MODULES DESCRIPTION CIO Remote CAN Digital I/O Module...
  • Page 35 Delay Input Time will not be considered, only the Debounce Time; this edge signals are deactivated automatically after one PLC scan cycle. FIGURE 5-2 shows the types of signals associated to the different input configuration types. FIGURE 5-2. INPUT LOGIC CIO Remote CAN Digital I/O Module GEK-106465A...
  • Page 36 Pulse Output Time: This is the output pulse length, applicable only to signals set as pulse type; the default value is 10000 ms and the setting range is 0 to 60000 ms (1 minute). FIGURE 5-3 shows the types of signals associated to the different output configuration types. FIGURE 5-3 OUTPUT LOGIC. GEK-106465A CIO Remote CAN Digital I/O Module...
  • Page 37: Inputs/Outputs Status

    I/O MODULES DESCRIPTION TABLE 5-2: INPUT STATUS MIXED BOARD (TYPE 1) CC10 CC11 CC12 CC13 CC14 CC15 CC16 CIO Remote CAN Digital I/O Module 5.2.2. INPUTS/OUTPUTS STATUS SUPERVISION BOARD (TYPE 2) Va_COIL1 Vb_COIL1 Va_COIL2 Vb_COIL2 O7_SEAL O8_SEAL SUP_COIL1 SUP_COIL2 GEK-106465A...
  • Page 38 (slot F, G, H or J). These signals can be configured at Setpoint > Relay Configuration > Outputs > Contact Output Operate. GEK-106465A I/O MODULES DESCRIPTION...
  • Page 39 CONT OP RESET_X_04 CONT OP RESET_X_05 CONT OP RESET_X_06 CONT OP RESET_X_07 CONT OP RESET_X_08 TABLE 5-6 I/O BOARD STATUS BOARD STATUS BOARD F STATUS BOARD G STATUS BOARD H STATUS BOARD J STATUS CIO Remote CAN Digital I/O Module GEK-106465A...
  • Page 40: Acceptance Tests

    When the device is tested, a power supply network with no harmonics in its waveform must be used. It is important to point out that the accuracy with which the test is performed depends on the network and on the instruments used.
  • Page 41: Isolation Tests

    Feed the unit to the minimum and maximum voltage. For each voltage value, verify that the alarm relay is activated when there is voltage, and it is deactivated when there is no feed. If the power supply source incorporates AC feed, this test will be performed also for VAC.
  • Page 42: Communication With The Master Unit

    Inputs (or contact converters, CC1 – CC15) must also be set to POSITIVE. I/O Board Type 2 Voltage Threshold A_01 Voltage Threshold B_01 Debounce Time A_01 Debounce Time B_01 Input Type 01 00 (CC1) Input Type 01 07 (CC8) GEK-106465A ACCEPTANCE TESTS 30 V 40 V 15 ms 15 ms POSITIVE POSITIVE...
  • Page 43: Contact Outputs

    Send an opening command and verify that the contact does not open. Interrupt current and check than the contact is released. Repeat the test for the other latched contact ACCEPTANCE TESTS 6.7.3. CIRCUIT CONTINUITY SUPERVISION INPUTS CIO Remote CAN Digital I/O Module 6.7.2. CONTACT OUTPUTS 6.7.4. LATCHING CIRCUITS GEK-106465A...