TECHNICAL DATA & SERVICE MANUAL Indoor Unit Outdoor Unit 4-Way Air Discharge Semi-Concealed Wall-Mounted SPW-C256VH SPW-C256VH8 SPW-C366VH8 Ceiling-Mounted Concealed-Duct SPW-C486VH SPW-C366VH SPW-C486VH8 SPW-C606VH8 Outdoor Unit ( Class Heat Pump Unit SPW-C256VH SPW-C366VH SPW-C486VH (Single-phase) Heat Pump Unit SPW-C256VH8 SPW-C366VH8 SPW-C486VH8...
IMPORTANT! When Installing… Please Read Before Starting …In a Room Properly insulate any tubing run inside a room to prevent This air conditioning system meets strict safety and “sweating” that can cause dripping and water damage to operating standards. As the installer or service person, it is walls and fl oors.
2. The standards for minimum room volume are as follows. Check of Density Limit (1) No partition (shaded portion) The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit.
1. SPECIFICATIONS 1-1. Unit Specifications....................1-2 4-Way Air Discharge Semi-Concealed Type ................. 1-2, 1-97 Wall-Mounted Type ........................1-25, 1-127 Ceiling-Mounted Type ....................... 1-32, 1-136 Concealed-Duct Type ........................ 1-50, 1-160 1-2. Major Component Specifications ................1-226 (A) Indoor Units ............................. 1-226 (B) Outdoor Units ..........................
Page 8
Simultaneous(Twin)-Type 1-1. Unit Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-XDR124GH56 (A/B) x2 / SPW-C256VH Indoor Unit SPW-XDR124GH56 (A/B) x2 MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0]...
Page 9
Simultaneous(Twin)-Type 1-1. Unit Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-X125H x2 / SPW-C256VH Indoor Unit SPW-X125H x2 MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0]...
Page 10
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 11
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 12
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 13
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 14
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 15
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 16
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 17
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 18
Single-Type 1-1. Unit Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-XDR254GH56 (A/B) / SPW-C256VH Indoor Unit SPW-XDR254GH56 (A/B) MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0]...
Page 19
Single-Type 1-1. Unit Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-X255H / SPW-C256VH Indoor Unit SPW-X255H MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0]...
Page 20
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 21
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 22
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 39 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 23
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 39 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 24
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 42 / 38 / 34 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 25
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 42 / 38 / 34 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 26
Simultaneous(Twin)-Type 1-1. Unit Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-XM125H x2 / SPW-C256VH Indoor Unit SPW-XM125H x2 MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0]...
Page 27
Wired: RCS-TM80BG Wireless: RCS-XM18BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 32 / 29 / 26 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 28
Wired: RCS-TM80BG Wireless: RCS-XM18BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 32 / 29 / 26 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 29
Wired: RCS-TM80BG Wireless: RCS-XM18BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 36 / 32 / 28 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 30
Wired: RCS-TM80BG Wireless: RCS-XM18BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 37 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 31
Simultaneous(Twin)-Type 1-1. Unit Specifi cations Wall-Mounted Type SPW-KR124GH56 (A/B) x2 / SPW-C256VH Indoor Unit SPW-KR124GH56 (A/B) x2 MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0]...
Page 32
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 31 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 33
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 31 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 34
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 31 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 35
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 34 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 36
Single-Type 1-1. Unit Specifi cations Wall-Mounted Type SPW-KR254GH56 (A/B) / SPW-C256VH Indoor Unit SPW-KR254GH56 (A/B) MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max]...
Page 37
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 37 / 34 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 38
Simultaneous(Twin)-Type 1-1. Unit Specifi cations Ceiling-Mounted Type SPW-TDR124GH56 (A/B) x2 / SPW-C256VH Indoor Unit SPW-TDR124GH56 (A/B) x2 MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0]...
Page 39
Simultaneous(Twin)-Type 1-1. Unit Specifi cations Ceiling-Mounted Type SPW-T125H x2 / SPW-C256VH Indoor Unit SPW-T125H x2 MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max]...
Page 40
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 41
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 42
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 43
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 44
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 45
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 46
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 36 / 33 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 47
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 36 / 33 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 48
Single-Type 1-1. Unit Specifi cations Ceiling-Mounted Type SPW-TDR254GH56 (A/B) / SPW-C256VH Indoor Unit SPW-TDR254GH56 (A/B) MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max]...
Page 49
Single-Type 1-1. Unit Specifi cations Ceiling-Mounted Type SPW-T255H / SPW-C256VH Indoor Unit SPW-T255H MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max] BTU / h...
Page 50
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 51
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 52
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 38 / 35 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 53
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 38 / 35 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 54
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 43 / 40 / 37 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 55
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 43 / 40 / 37 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 56
Simultaneous(Twin)-Type 1-1. Unit Specifi cations Concealed-Duct Type SPW-UR124GH56 (A/B) x2 / SPW-C256VH Indoor Unit SPW-UR124GH56 (A/B) x2 MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0]...
Page 57
Simultaneous(Twin)-Type 1-1. Unit Specifi cations Concealed-Duct Type SPW-U125H x2 / SPW-C256VH Indoor Unit SPW-U125H x2 MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max]...
Page 58
Simultaneous(Twin)-Type 1-1. Unit Specifi cations Concealed-Duct Type SPW-U125HN x2 / SPW-C256VH Indoor Unit SPW-U125HN x2 MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max]...
Page 59
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 60
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 61
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 62
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 63
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 64
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 65
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 66
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 67
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 68
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 69
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 70
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 71
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 72
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 73
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 74
Single-Type 1-1. Unit Specifi cations Concealed-Duct Type SPW-UR254GH56 (A/B) / SPW-C256VH Indoor Unit SPW-UR254GH56 (A/B) MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max]...
Page 75
Single-Type 1-1. Unit Specifi cations Concealed-Duct Type SPW-UR254SH56B / SPW-C256VH Indoor Unit SPW-UR254SH56B MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max] BTU / h...
Page 76
Single-Type 1-1. Unit Specifi cations Concealed-Duct Type SPW-U255H / SPW-C256VH Indoor Unit SPW-U255H MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max] BTU / h...
Page 77
Single-Type 1-1. Unit Specifi cations Concealed-Duct Type SPW-U255HN / SPW-C256VH Indoor Unit SPW-U255HN MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max] BTU / h...
Page 78
Single-Type 1-1. Unit Specifi cations Concealed-Duct Type SPW-U255SH / SPW-C256VH Indoor Unit SPW-U255SH MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max] BTU / h...
Page 79
Single-Type 1-1. Unit Specifi cations Concealed-Duct Type SPW-U255SHT / SPW-C256VH Indoor Unit SPW-U255SHT MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max] BTU / h...
Page 80
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 81
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 82
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 83
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 84
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 85
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 86
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 87
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 88
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 89
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 90
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 91
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 92
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 93
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 94
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 95
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 96
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 97
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 98
Simultaneous(Twin)-Type 1-1. Unit Specifi cations Concealed-Duct Type SPW-US125H x2 / SPW-C256VH Indoor Unit SPW-US125H x2 MODEL No. Outdoor Unit SPW-C256VH POWER SOURCE 220 - 230 - 240 V, 1 phase, 50/60 Hz PERFORMANCE Cooling Heating 7.1 [2.2~8.0] 8.0 [2.2~9.0] Capacity [min~max]...
Page 99
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 32 / 30 / 28, (34 / 32 / 30: Using short circuit connection) Operation sound...
Page 100
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 32 / 30 / 28, (34 / 32 / 30: Using short circuit connection) Operation sound...
Page 101
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 32 / 30, (36 / 34 / 32: Using short circuit connection) Operation sound...
Page 102
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 33 / 31, (37 / 35 / 33: Using short circuit connection) Operation sound...
Page 103
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 104
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 105
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 106
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 107
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 108
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 109
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 110
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 111
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 112
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 113
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 114
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 31 / 29 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 115
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 116
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 117
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 118
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 119
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 120
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 31 / 28 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 121
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 39 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 122
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 39 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 123
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 42 / 38 / 34 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 124
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 42 / 38 / 34 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 125
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 44 / 40 / 36 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 126
Wired: RCS-TM80BG Wireless: RCS-SH80BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 44 / 40 / 36 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 127
Wired: RCS-TM80BG Wireless: RCS-XM18BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 32 / 29 / 26 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 128
Wired: RCS-TM80BG Wireless: RCS-XM18BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 32 / 29 / 26 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 129
Wired: RCS-TM80BG Wireless: RCS-XM18BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 32 / 29 / 26 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 130
Wired: RCS-TM80BG Wireless: RCS-XM18BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 36 / 32 / 28 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 131
Wired: RCS-TM80BG Wireless: RCS-XM18BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 37 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 132
Wired: RCS-TM80BG / Wireless: RCS-XM18BG.WL Refrigerant control – Drain pump (Drain connection) Max.head 64cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 37 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 2.5GY 9.0 / 0.5...
Page 133
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 31 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 134
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 31 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 135
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 31 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 136
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 31 / 27 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 137
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 34 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 138
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 34 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 139
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 37 / 34 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 140
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 37 / 34 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 141
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-SH1BG Refrigerant control – Drain pump (Drain connection) (13A, OD18mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 37 / 34 Operation sound Outdoor - Hi dB-A Indoor Munsell 3.0Y 8.6 / 0.8...
Page 142
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 143
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 144
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 145
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 146
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 147
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 148
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 149
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 32 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 150
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 36 / 33 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 151
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 36 / 33 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 152
Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 36 / 33 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 153
Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 36 / 33 / 30 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 154
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 155
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 156
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 157
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 158
Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 159
Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 36 / 33 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 160
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 38 / 35 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 161
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 41 / 38 / 35 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 162
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 43 / 40 / 37 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 163
Remote controller (Option) Wired: RCS-TM80BG Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 43 / 40 / 37 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 164
Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 43 / 40 / 37 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 165
Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL Refrigerant control – Drain pump (Drain connection) (20A, OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 43 / 40 / 37 Operation sound Outdoor - Hi dB-A Indoor Munsell 10Y 9.3 / 0.4...
Page 166
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 167
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 168
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 169
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 170
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 171
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 172
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 173
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 174
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 29 / 26 / 22, (32 / 29 / 26: using the booster cable) Operation sound...
Page 175
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 176
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 177
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 178
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 179
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 180
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 181
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 182
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 183
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 184
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 185
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 186
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 187
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 188
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 189
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable) Operation sound...
Page 190
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 191
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 192
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 193
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 194
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 195
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 196
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 197
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 198
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 199
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 200
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 201
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 202
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 203
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 204
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 205
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 206
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 207
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 30 / 27, (38 / 34 / 30: using the booster cable) Operation sound...
Page 208
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 209
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 210
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 211
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 212
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 213
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 38 / 33 / 31, (42 / 38 / 33: using the booster cable) Operation sound...
Page 214
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 215
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 216
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 217
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 218
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 219
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 220
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 221
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 222
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 223
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 224
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 225
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 40 / 37 / 33, (44 / 40 / 37: using the booster cable) Operation sound...
Page 226
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 32 / 30 / 28, (34 / 32 / 30: Using short circuit connection) Operation sound...
Page 227
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 32 / 30 / 28, (34 / 32 / 30: Using short circuit connection) Operation sound...
Page 228
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 32 / 30 / 28, (34 / 32 / 30: Using short circuit connection) Operation sound...
Page 229
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 34 / 32 / 30, (36 / 34 / 32: Using short circuit connection) Operation sound...
Page 230
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 33 / 31, (37 / 35 / 33: Using short circuit connection) Operation sound...
Page 231
Refrigerant control – Drain pump (Drain connection) Max.head 50cm above drain connection (OD26mm) Compressor Rotary (SANYO) Indoor - Hi / Me / Lo dB-A 35 / 33 / 31, (37 / 35 / 33: Using short circuit connection) Operation sound...
1-3. Other Component Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-XDR124-604GH56 (A/B), X125-605H SPW-XDR124-604GH56 (A/B) MODEL No. Indoor Unit SPW-X125-605H Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C –...
Page 269
1-3. Other Component Specifi cations 4-Way Air Discharge Semi-Concealed Type SPW-XM125 / 165 / 185H MODEL No. Indoor Unit SPW-XM125 / 165 / 185H Power Transformer – Rated – Source VAC, Hz – – Secondary – Ω Coil resistance – Thermal cut off temperature °C –...
1-3. Other Component Specifi cations Wall-Mounted Type SPW-KR124 – 254GH56 (A/B) MODEL No. Indoor Unit SPW-KR124 – 254GH56 (A/B) Power Transformer ATR-IIK245 Rated Source VAC, Hz AC 230 V , 50/60 Hz S1: 11 V, 1.25 A S2: 14 V, 0.45 A Secondary S3: 20 V, 0.2 A Ω...
1-4. Dimensional Data (A) Indoor Units: 4-Way Air Discharge Semi-Concealed Type 12, 16, 18, 25 Types 860 – 910 Ceiling opening dimensions Suspension bolt pitch Unit : mm 1-275...
Page 282
1-4. Dimensional Data (A) Indoor Units: 4-Way Air Discharge Semi-Concealed Type 36, 48, 60 Types Unit : mm 1-276...
Page 283
1-4. Dimensional Data (A) Indoor Units: 4-Way Air Discharge Semi-Concealed XM Type 12, 16, 18 Types Unit : mm 1-277...
Page 284
1-4. Dimensional Data (A) Indoor Units: Wall-Mounted Type 12, 16, 18 Types Gas tube ø12.7 (length: Approx. 400 mm) Drain and wiring port (ø9.52) Liquid tube ø6.35 (length: Approx. 470 mm) Drain hose VP13 (length: Approx. 450 mm) 25 Type 1,140 Drain hose VP13 (length: Approx.
Page 285
1-4. Dimensional Data (A) Indoor Units: Ceiling-Mounted Type Length Type 12, 16, 18 Air intake 1125 1180 36, 48 1540 1595 Ceiling side 27.5 27.5 Air outlet Unit: mm (Suspension bolt pitch) Rear (Figure shows view from front) Left side Right side (Liquid tubing •...
Page 286
1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct Type 12, 16, 18 Types SPW-UR124GH56 (A/B), U125H, U125HN SPW-UR164GH56 (A/B), U165H, U165HN SPW-UR184GH56 (A/B), U185H, U185HN (Air outlet duct fl ange) (Suspension bolt pitch) Refrigerant liquid line ø6.35 (liquid tube) Refrigerant gas line ø12.7 Upper drain port (O.D.
Page 287
1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct Type SPW-UR254GH56 (A/B), U255H, U255HN (Air outlet duct fl ange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (liquid tube) (Use the tube connector) Refrigerant gas line ø15.88 (gas tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D.
Page 288
1-4. Dimensional Data (A) Indoor Unit: Concealed-Duct Type SPW-UR364GH56 (A/B), U365H, U365HN SPW-UR484GH56 (A/B), U485H, U485HN SPW-UR604GH56 (A/B), U605H, U605HN (Air outlet duct fl ange) (Suspension bolt pitch) Refrigerant liquid line ø9.52 (liquid tube) Refrigerant gas line ø15.88 Upper drain port (O.D. 32 mm) Bottom drain port (O.D.
1-4. Dimensional Data (A) Indoor Unit: Flange for Air Intake Duct (Field Supply) For Concealed-Duct Type Thickness more than T1.2 mm Unit : mm (mm) 7, 9, 12, 16, 18 types 12-ø3.3 3 × 200P = 60 1 × 340P = 340 8-ø6 25 type 16-ø3.3 3 ×...
Page 294
1-4. Dimensional Data (B) Outdoor Unit: SPW-C256VH (97) ø18 Drain port Air intake Air intake ø19 Drain port Air discharge (161) Refrigerant tubing joint (liquid tube) Unit: mm (157) Flare connection ø9.52 mm Refrigerant tubing joint (gas tube) Flare connection ø15.88 mm...
Page 295
1-4. Dimensional Data (B) Outdoor Unit: SPW-C366VH 2 - ø32 holes (holes for drain) Of the 4 - ø32 holes, use 1 of the 2 holes specified for drain use to install the port. Use rubber plugs to seal the remaining 3 holes. Air intak Air intake e Air intake...
Page 296
1-4. Dimensional Data (B) Outdoor Unit: SPW-C486VH, C486VH8, C606VH8 2 - ø32 holes (holes for drain) Of the 4 - ø32 holes, use 1 of the 2 holes specified for drain use to install the port. Use rubber plugs to seal the remaining 3 holes. Air intak Air intake e Air intake...
1-5. Refrigerant Flow Diagram Outdoor Unit : SPW-C256VH Indoor Unit: Accumulator Compressor Gas line service valve ø15.88 Flare connection Muffl er Muffl er Heat exchanger 4-way valve Heat exchanger Distributor Strainer Electronic ref. Liquid line control valve service valve ø9.52...
1-7. Capacity Correction Graph According to Temperature Condition SPW-C256VH (For 50 Hz and 60 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 16 °C 20 °C...
Page 300
1-7. Capacity Correction Graph According to Temperature Condition SPW-C366VH (For 50 Hz and 60 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 16 °C 20 °C 22WB 24 °C...
Page 301
1-7. Capacity Correction Graph According to Temperature Condition SPW-C486/606VH8 (For 50 Hz and 60 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp ( °C WB) Indoor air intake temp ( °C DB) 16 °C 20 °C 24 °C 22WB...
Page 308
1-8. Noise Criterion Curves 1-8. Noise Criterion Curves Concealed-Duct Type Concealed-Duct Type Both 50Hz / 60Hz Strong Weak MODEL MODEL : SPW-US125H : SPW-US165H SOUND LEVEL : STRONG 34 dB(A) SOUND LEVEL : STRONG 32 dB(A) WEAK 30 dB(A) WEAK 28 dB(A) CONDITION : 1.5 m directly below unit CONDITION...
Page 309
1-8. Noise Criterion Curves (B) Outdoor Unit MODEL : SPW-C256VH MODEL : SPW-C256VH SOUND : 65.7 dB(A) SOUND LEVEL : Cooling 49 dB(A), Heating 51 dB(A) POWER LEVEL : Cooling CONDITION : 1 m in front at height of 1.5 m...
Page 310
1-8. Noise Criterion Curves (B) Outdoor Unit MODEL : SPW-C486VH MODEL : SPW-C486VH SOUND : 67.8 dB(A) SOUND LEVEL : Cooling 51 dB(A), Heating 54 dB(A) POWER LEVEL : Cooling CONDITION : 1 m in front at height of 1.5 m SOURCE : 220 - 230 - 240 V, 1 Phase, 50 Hz Heating...
Page 311
1-8. Noise Criterion Curves (B) Outdoor Unit MODEL : SPW-C486VH8 MODEL : SPW-C486VH8 SOUND : 67.8 dB(A) SOUND LEVEL : Cooling 51 dB(A), Heating 54 dB(A) POWER LEVEL : Cooling CONDITION : 1 m in front at height of 1.5 m SOURCE : 380 - 400 - 415 V, 3 Phase, 50 Hz Cooling...
1-9. Indoor Fan Performance Electrical component box Booster Cable for Concealed-Duct Type If external static pressure is too great (due to long Booster cable extension of ducts, for example), the airfl ow volume Booster cable motor may drop too low at each air outlet. This problem may be solved by increasing the fan speed using Fan motor socket the following procedure:...
Page 313
For Short Circuit Connection • The standard (before shipment) external static pressure is shown in the table below. • When using with a higher static pressure, it is necessary to change to the high static pressure mode. White Yellow Red External static pressure 125 / 165 / 185 Standard...
1-10. Air Flow Distance Chart 4-Way Air Discharge Semi-Concealed Type • If an ultra long-life fi lter or high performance fi lter (65% by colorimetric method) is installed, the vertical air fl ow distance for heating and cooling will be approximately 0.2 m less than the values shown in the graph below. •...
Page 315
SPW-XDR254GH56(A/B), X255H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.65°) (Room temperature approx.20°C) 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air fl ow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.65°) (Room temperature approx.20°C) Horizontal air fl ow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30°)
Page 316
SPW-XDR364GH56(A/B), X365H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.65°) (Room temperature approx.20°C) 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air fl ow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.65°) (Room temperature approx.20°C) Horizontal air fl ow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30°)
Page 317
SPW-XDR484/604GH56(A/B), X485/605H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.65°) (Room temperature approx.20°C) 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air fl ow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.65°) (Room temperature approx.20°C) Horizontal air fl ow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30°)
Page 318
SPW-XM125H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.60°) (Room temperature approx.20°C) 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air fl ow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.60°) (Room temperature approx.20°C) Horizontal air fl ow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30°)
Page 319
SPW-XM165 / 185H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.60°) (Room temperature approx.20°C) 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air fl ow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.60°) (Room temperature approx.20°C) Horizontal air fl ow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.30°)
Page 320
Wall-Mounted Type Wall-Mounted Type SPW-KR124/164GH56(A/B) Heating : Distribution of temperature Heating : Distribution of wind velocity (Strong wind : (Strong wind : Discharge angle app.60°) (Rm. temp. app.20°C) Discharge angle app.60°) (Rm. temp. app.20°C) 1.5m/s 1.2m/s 0.9m/s 0.3m/s 0.6m/s 0.3m/s Horizontal air fl ow distance (m) Horizontal air fl ow distance (m) Cooling : Distribution of wind velocity...
Page 321
SPW-KR254GH56(A/B) Heating : Distribution of temperature Heating : Distribution of wind velocity (Strong wind : (Strong wind : Discharge angle app.60°) (Rm. temp. app.20°C) Discharge angle app.60°) (Rm. temp. app.20°C) 1.5m/s 0.9m/s 0.3m/s 1.2m/s 0.6m/s 0.3m/s Horizontal air fl ow distance (m) Horizontal air fl ow distance (m) Cooling : Distribution of wind velocity Cooling : Distribution of temperature...
Page 322
Ceiling-Mounted Type Ceiling-Mounted Type SPW-TDR124/164/184GH56(A/B), T125/165/185H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54°) (Room temperature approx.20°C) 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air fl ow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54°) (Room temperature approx.20°C) Horizontal air fl ow distance (m) Cooling : Distribution of wind velocity...
Page 323
SPW-TDR254/364GH56(A/B), T255/365H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54°) (Room temperature approx.20°C) 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air fl ow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54°) (Room temperature approx.20°C) Horizontal air fl ow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.-7°)
Page 324
SPW-TDR484/604GH56(A/B), T485/605H Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54°) (Room temperature approx.20°C) 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air fl ow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54°) (Room temperature approx.20°C) Horizontal air fl ow distance (m) Cooling : Distribution of wind velocity (Strong wind : Discharge angle approx.-7°)
1-11. Intaking Fresh Air of Semi-Concealed Type and Concealed-Duct Type • Precautions Regarding External Air Intake (1) Ventilation Load Ensure that the design of the air-conditioner takes air-conditioning loads into consideration when external air intake is involved. (2) Restrictions on External Air Intake Ensure that the design conforms to the restrictions on air intake volume stipulated in accordance with the model of the indoor unit and the intake method.
Page 326
• X, XM Type When an External Air Intake Flange (ø100) is in Use External Air Intake Volume and Resistance and With the External Air Intake Flange Attached Operation Noise Characteristics within the Unit X Type XM Type Duct (ø100) for Connecting the External Air Intake Flange Operation Noise (External Air Intake Only)
1-12. Installation Instructions Tubing Length Table 1-1 (A) Single type Outdoor unit type 25 type Maximum allowable tubing length 50 m Keep refrigerant tubing between the indoor and outdoor Charge-less tubing length units as short as possible. 3 - 20 (30 : VH8) m (actual length) The length of the refrigerant tubes between the indoor Additional charge per 1 m...
Page 328
Table 1-2 Tubing Data for Models (Single) SPW-C256VH SPW-C366VH SPW-C486VH Models SPW-C606VH8 Tubing Data SPW-C256VH8 SPW-C366VH8 SPW-C486VH8 Liquid tube mm (in.) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) Tubing size outer diameter 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) Gas tube mm (in.)
Page 329
This unit requires no additional refrigerant CAUTION charge up to tubing length 30 m. In case of more than 30 m, additional refrigerant charge is required. Refer to Tables 1-2 and 1-3. In case of multi type installation, indoor units should be installed within the same room.
Optional Distribution Joint Kits APR-P160BG:Cooling capacity after distribution is 16.0 kW (54,600 BTU/h) or less APR-RTP280AGB: Cooling capacity after distribution is 28.0 kW (95,500 BTU/h) or less Table 1-4 Distribution Branch Size(ℓ1, ℓ2, ℓ3, ℓ4, ) Unit : mm (in) Indoor Unit 12 type 16 type...
Installing Distribution Joint Kit (for Twin & If the distribution joint will be cut before use, cut on the line marked “cutting point” in the fi gure below. Double-Twin) (APR-P160BG) • Use a tube cutter and cut at the size position that Stopper (boss) Cutting point corresponds to the fi eld-supply tube size selected...
Installing Distribution Joint Kit (for Triple) (APR-RTP280AGB) Only the distribution joints are horizontal with • Check the system combination before installing the respect to the ground. The collective tubes are distribution joints. vertical with respect to the ground. • Three indoor units must be installed within the same The collective tube and distribution room.
Selecting the Installation Site Ceiling-Mounted Type Indoor Unit Ceiling CAUTION Wall • When moving the unit during or after unpacking, make sure to lift it by holding its lifting lugs. Do not exert any pressure on other parts, especially min. 25 cm min.
Page 334
Outdoor Unit Exhaust fan Hot air AVOID: Heat source • heat sources, exhaust fans, etc. (Fig. 1-4) • damp, humid or uneven locations Outdoor unit • choose a place as cool as possible. • choose a place that is well ventilated and outside Fig.
Page 335
Air Discharge Chamber for Top Discharge Be sure to install the air discharge chamber in the fi eld when: Air discharge Air discharge • it is diffi cult to keep a space of min. 1 m between the air discharge outlet and an obstacle, also in case of the obstacle is higher than 2 m.
Dimensions of Air-Discharge Chamber In snowy regions, if there is concern that snow may enter the air discharge chamber, remove the base of the chamber before using. Reference diagram for SPW-C256VH Unit: mm Air discharge support (STK-FV140B) 4-ø12 hole Left side installation fi xture (STK-UFE56E) T1.0...
Page 337
Reference diagram for left side installation fi xture (fi eld supply) : STK-UFE56E Unit: mm 2-ø3.3 protrusion hole (reverse side) 552.7 438.7 11.3 Reference diagram for right side installation fi xture (fi eld supply) : STK-UFE56E Unit: mm 2-ø3.3 protrusion hole (reverse side) 552.7 11.3...
Page 338
Reference diagram for center side installation fi xture (fi eld supply) : STK-UFE56E Unit: mm (200) A View Cyclic bending Same on reverse side 32.5 (495) 32.5 1-332...
Page 339
Dimensions of Outdoor Unit with air-discharge chamber (fi eld supply) In snowy regions, if there is concern that snow may enter the air discharge chamber, remove the base of the chamber (10 screws) before using. Unit: mm Reference diagram for SPW-C256 / 366VH8 Air Intake Air discharge Air Intake...
Page 340
Dimensions of Air-Discharge Chamber (continued) Reference diagram for SPW-C366VH Unit: mm Air Intake Air discharge support (STK-FV140B) Left side installation fi xture (STK-UFV80E) T1.0 Right side installation fi xture (STK-UFV80E) T1.0 Air Intake Center side installation fi xture (STK-UFV80E ) T1.0 Installation anchoring hole (4-R6.5) / Anchor bolt : M10 (110)
Page 341
Reference diagram for air-discharge support (fi eld supply) : STK-FV140B Unit: mm Reference diagram for left side installation fi xture (fi eld supply) : STK-UFV80E Unit: mm 2-ø3.3 protrusion hole (reverse side) 1-335...
Page 342
Reference diagram for right side installation fi xture (fi eld supply) : STK-UFV80E Unit: mm 2-ø3.3 protrusion hole (reverse side) Cyclic bending Reference diagram for center side installation fi xture (fi eld supply) : STK-UFV80E Unit: mm Cyclic bending 32.5 (495) 32.5 Same on reverse side...
Page 343
Reference diagram for air-discharge chamber (fi eld supply) The models of SPW-C256VH with STK-FV140B and STK-UFE56E, SPW-C256 / 366VH8 with STK-DRV80U, SPW-C366 / 486VH with STK-FV140B and STK-UFV80E, SPW-C486 / 606VH8 with STK-FV140B and STK-UFV80E Required space around outdoor unit If the air discharge chamber is used, the space shown below must be secured around the outdoor unit.
Dimensions of Wind-proof Duct In snowy regions, if there is concern that snow may enter the wind-proof duct, remove the base of the chamber before using. Reference diagram for SPW-C256VH Unit: mm Drain port 2- 19 Drain port Electrical wiring inlet Refrigerant tubing joint (liquid tube) Flare connection ø9.52 mm...
Page 345
Dimensions of wind-proof Duct (continued) Reference diagram for SPW-C366VH Air Intake Unit: mm Hole for anchor bolt (4–R6.5) / Anchor bolt: M10 Air Intake Air discharge discharge (110) (319) Air discharge discharge Air Intake discharge discharge Air discharge Air discharge Reference diagram for wind-proof duct (fi eld supply) : STK-DGV160E Unit: mm (50)
Page 346
Dimensions of Wind-proof Duct (continued) Reference diagram for SPW-C486VH (8) / 606VH8 Air Intake Unit: mm Air Intake Hole for anchor bolt (4–R6.5) / Anchor bolt: M10 discharge discharge (110) (319) Air discharge discharge discharge discharge Air discharge discharge Reference diagram for wind-proof duct (fi eld supply) : STK-DGV160E Unit: mm (50) (126.5)
Dimensions of Snow-proof Duct Reference diagram for SPW-C256VH Unit: mm Drain port Drain port 2- 19 Electrical wiring inlet (161) Refrigerant tubing joint (liquid tube) (157) Flare connection ø9.52 mm Refrigerant tubing joint (gas tube) Flare connection ø15.88 mm Reference diagram for snow-proof duct (fi eld supply) : STK-BDE56E Unit: mm 250 (O.D.)
Page 348
Dimensions of Snow-proof Duct (continued) Reference diagram for snow-proof duct (fi eld supply) : STK-BDE56E (54) Unit: mm 688 (O.D.) 250 (O.D.) 11.7 10.5 Reference diagram for snow-proof duct (fi eld supply) : STK-BDE56E Unit: mm (126.5) 20.5 26 (I.D.) 16.6 791(I.D.) 11.5...
Page 349
Dimensions of Snow-proof Duct (continued) Reference diagram for SPW-C256 / 366VH8 : STK-BDRE80A Unit: mm Air Intake Air Intake Air discharge Air discharge Air discharge Air Intake Reference diagram for snow-proof duct (fi eld supply) : STK-BDRE80A Unit: mm Unit top, snow-proof vent Unit left side Unit right side Unit reverse side...
Page 350
Dimensions of Snow-proof Duct (continued) Reference diagram for SPW-C366/486VH and SPW-C486 / 606VH8 Unit: mm (295) Hole for anchor bolt (4–R6.5) / Anchor bolt: M10 Air Intake SPW-C366VH (48) Air discharge SPW-C486VH (8) 913 (178) (227) SPW-C606VH8 (178) (303) discharge Air Intake Reference diagram for snow-proof duct (fi eld supply) : STK-BDV80E Unit: mm...
Page 351
Reference diagram for snow-proof duct - 1 Space requirements for setting - (1) (1) The models of SPW-C256VH with STK-BDE56E [Obstacle to the rear of unit] [Obstacle to the rear of unit] Top is open: Top is open: (1) Single-unit installation (1) Single-unit installation (2) Obstacles on both sides Min.
Page 352
Reference diagram for snow-proof duct - 2 Space requirements for setting - (2) The models of SPW-C256VH with STK-BDE56E [Obstacle to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
Page 353
Reference diagram for snow-proof vents – 1 Space requirements for setting – (1) The models of SPW-C256 / 366VH8 with STK-BDRE80A [Obstacle to the rear of unit] [Obstacle to the rear of unit] Top is open: Top is open: (1) Single-unit installation (2) Obstacles on both sides (1) Single-unit installation Min.
Page 354
Reference diagram for snow-proof vents – 2 Space requirements for setting – (2) The models of SPW-C256 / 366VH8 with STK-BDRE80A [Obstacle to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
Page 355
Reference diagram for snow-proof duct - 3 Space requirements for setting - (3) (1) The models of SPW-C366/486VH and SPW-C486 / 606VH8 with STK-BDV80E [Obstacle to the rear of unit] [Obstacle to the rear of unit] Top is open: Top is open: (1) Single-unit installation (2) Obstacles on both sides (1) Single-unit installation Min.
Page 356
Reference diagram for snow-proof duct - 4 Space requirements for setting - (4) The models of SPW-C366/486VH and SPW-C486 / 606VH8 with STK-BDV80E [Obstacle to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
Be sure to anchor the feet with anchor bolts (M10). In addition, use anchoring washers on the top side. (Use large square 32 x 32 SUS washers with JIS nominal diameter of 10.) (Field supply) For SPW-C256VH 4- ø12 Anchor bolt hole (97) (Anchor bolt M8)
Page 358
• When using a drain pipe, install the drain socket (optional parts SPW-C256VH : STK-DS13U, all models excluding SPW-C256VH : STK-DS25T ) onto the drain port. Seal the other drain port with the rubber cap supplied with the drain socket.
Time delay (A) Power supply Time delay fuse or circuit fuse or circuit Wire size Max. length Wire size Max. length capacity capacity SPW-C256VH 4.0 mm 20 m 25 A SPW-C256VH8 2.5 mm 58 m 16 A SPW-C366VH 4.0 mm...
Page 360
Wiring System Diagrams (For single-phase outdoor unit) Indoor unit (No. 1) Outdoor unit Power supply INV unit 220 – 240 V ~ 50/60 Hz Power supply 220 – 240 V ~ 50/60 Hz Ground Remote controller Ground Ground Ground Ground Ground Indoor unit (No.
Page 361
Wiring System Diagrams (For 3-phase outdoor unit) Indoor unit (No. 1) Power supply Outdoor unit 220 – 240 V ~ 50/60 Hz INV unit Power supply Ground Remote 380– 415 V 3N ~ 50 Hz controller Ground Ground Ground Ground Ground Indoor unit (No.
Page 362
CAUTION (1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) Otherwise the communication of S-net link system is not performed.
Page 363
(5) Use shielded wires for inter-unit control wiring (C) and ground the shield on both sides, otherwise malfunction from noise may occur. Connect wiring as shown in the section “Wiring System Diagrams”. Shielded wire Loose wiring may cause the Ground Ground terminal to overheat or result WARNING...
2. TEST RUN 2-1. Preparing for Test Run ...........................2-2 X, XM, T, U, US Types 2-2. Caution ................................2-2 2-3. Test Run Procedure ............................2-2 2-4.Items to Check Before the Test Run .......................2-3 2-5.Test Run Using the Remote Controller ......................2-3 2-6.Precautions ..............................2-3 2-7.Table of Self-Diagnostic Function and Corrections (X, XM, T, U, US Types) ..........2-4 2-8.System Control ..............................2-5 K Type...
2-1. Preparing for Test Run X, XM, T, U, US Types Before attempting to start the air conditioner, 2-2. Caution check the following: This unit may be used in a single-type (1) All loose matter is removed from the cabinet refrigerant system where 1 outdoor unit is connected to 1 indoor unit, and also in a system especially steel filings, bits of wire, and clips.
2-4. Items to Check Before the Test Run Indoor unit control PCB (1) Turn the remote power switch ON at least 12 CHK (2P plug) hours in advance in order to energize the crank 2P connector (brown) case heater. 2P connector (blue) (2) Fully open the closed valves on the liquid-tube and gas-tube sides.
2-8. System Control System control refers to the link wiring connection for control of simultaneous operation multi systems, group control, and main-sub remote controller control. 2-8-1.Basic wiring diagram 1 Single type and simultaneous operation multi system Simultaneous operation multi system Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation.
Page 370
2-8-2. Basic wiring diagram 2 Group control (when a central control device is not used) Simultaneous operation multi system Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.) A maximum of 8 indoor units can be connected to 1 remote controller.
(Wiring procedure) (1) Connect the remote controller to the indoor unit remote controller wiring terminal plate (1, 2). (Remote controller wiring) (2) Connect the indoor units (U1, U2) and the outdoor units (1, 2). Connect the other outdoor units and indoor units (with different refrigerant systems) in the same way.
Page 372
2-8-4. Automatic address setting using the remote controller When the outdoor unit shown in “2-8-2. Basic wiring diagram 2” is used for group control of multiple units, use the remote controller to perform automatic address setting. (During automatic address setting, “SETTING” blinks on the remote controller display.) Press the remote controller timer time button and...
Page 373
2-8-6. Main-sub remote controller control K Type Control using 2 remote controller switches Main-sub 2-9. Caution remote controller control refers to the use of 2 remote This unit may be used in a single-type controllers to control 1 or multiple indoor units. refrigerant system where 1 outdoor unit is (A maximum of 2 remote controllers can be connected.) connected to 1 indoor unit, and also in a system...
Page 374
2-10. Test Run Procedure (See 2-11) Recheck the items to check befor the test run. (See 2-16) Check the combination (wiring) of indoor and outdoor units. Is system “single-type”? (1 indoor unit is connected to 1 outdoor unit) Turn ON the indoor and Are multiple outdoor units used? outdoor power (See 2-16-2) In case of group control...
Page 375
2-13. Test Run Indoor unit control PCB 2 HP Using the control unit Varistor (black) (1) Change the indoor control unit switch from VA002 “ON” “TEST”. Fuse (0.5A) (The outdoor unit will not operate for 3 minutes after the power is turned ON and after operation is CHK (2P plug) stopped.) (2) All the indicator lamps blink while the test run is in...
Page 376
2-15. Table of Self-Diagnostic Functions and Corrections (K Type) Cause Wired remote controller Indoor unit Group connection Correction display receiver lamp 1:1 connection (Single type) (Simultaneous (Field supply) multi system) Nothing is Nothing is • Indoor operation switch is OFF. •...
Page 377
2-16. System Control System control refers to the link wiring connection for control of simultaneous operation multi systems, group control, and main/sub remote controller control. 2-16-1. Basic wiring diagram 1 Single type and simultaneous operation multi system • Simultaneous operation multi system Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation.
Page 378
2-16-2. Basic wiring diagram 2 Group control (when a central control device is not used) • A maximum of 8 indoor units can be connected to a single remote controller. Example: In a refrigerant system where 2 or 3 indoor units are connected to 1 outdoor unit, set the new system address (refrigerant system address) before turning ON the remote power switch.
Page 379
2-16-3. Setting the outdoor unit system addresses For basic wiring diagram 2 (Set the system addresses: 1, 2,...) Outdoor unit control PCB System address System address System address System address System address rotary switch System System 1s place 10s digit 10s digit 1s place (Set to “0”...
2-16-6. Indoor unit address setting • If multiple single-type units are installed in the same room the addresses can be set to prevent signal interference. By coordinating the numbers of the indoor unit (wireless PCB) and remote controller addresses, up to 6 indoor units can be controlled independently by their respective remote controllers.
Page 381
2-18. Test Run Procedure (See 2-19) Recheck the items to check befor the test run. Check the combination (wiring) of (See 2-22-1) indoor and outdoor units. Is system “single-type”? Is outdoor unit multiple? (See 2-22-2) How to Set the Outdoor Unit System Address Set the outdoor unit system address.
2-21. Table of Self-Diagnostic Functions and Corrections (X, T, U Types) Cause Wired remote Indoor unit controller Correction Group connection and simultaneous operation multi receiver lamp display system • Remote controller is not connected with indoor unit Connect the remote controller correctly. Turn ON Nothing is Nothing is correctly.
Page 383
Automatic address setting from the outdoor unit (X, T, U Types) Case 1 • If the power can be turned ON separately for the indoor and outdoor units in each system, the indoor unit addresses can be set without running the compressor. (1) Turn on the indoor and outdoor unit power for refrigerant system 1.
Page 384
Case 4 • If the power cannot be turned ON separately for the indoor and outdoor units in each system: (The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work.) All-systems automatic address setting: Display item code “AA”...
2-22-3.Checking indoor unit addresses Use the remote controller to check the addresses of the indoor units. Press and hold button and button for 4 seconds or longer (simple settings mode, “ALL” appears on the remote controller). Then press the button and select the indoor address. (For the system addresses of the No.
Page 386
2-24. Test Run Procedure Recheck the items to check (See 2-11) before the test run. Check the combination (wiring) (See 2-16-1) of indoor and outdoor units. Is system “single-type”? (1 indoor unit is connected to 1 outdoor unit) Turn ON the indoor Are multiple outdoor units used? and outdoor power.
Page 387
2-25. Table of Self-Diagnostic Functions and Corrections (K Type) Cause Wired remote Indoor unit controller Correction Group connection and simultaneous operation multi receiver lamp display system • Remote controller is not connected with indoor unit Connect the remote controller correctly. Turn ON Nothing is Nothing is correctly.
Page 388
2-26. Automatic Address Setting 2-26-1. Basic wiring diagram Link wiring NOTE A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only 1 outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes” to “No”).
Page 389
2-26-2. Setting the outdoor unit system addresses For basic wiring diagram (Set the system addresses: 1, 2, 3...) Outdoor unit control PCB System address rotary switch (Set to “0” at time of shipment) System address System address System address System address System address rotary switch System System...
Page 390
Case 2 If the power cannot be turned ON separately for the indoor and outdoor units in each system: The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work. (1) Turn ON the power to the indoor and outdoor units in all refrigerant systems.
XM Type (for Link Wiring) 2-27. Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 4 <...
Page 392
2-28. Test Run Procedure (See 2-29) Recheck the items to check befor the test run. Check the combination (wiring) of (See 2-32-1) indoor and outdoor units. Is system “single-type”? Is group control with multiple outdoor units used? Turn ON the indoor and (See 2-32-2) How to Set the Outdoor Unit System Address outdoor power.
2-31. Table of Self-Diagnostic Functions and Corrections (XM Type) Cause Wired remote Indoor unit Correction Group connection and simultaneous-operation controller display receiver lamp multi system • Remote controller is not connected with indoor Connect the remote controller correctly. Nothing is displayed Nothing is displayed. unit correctly.
Page 394
2-32. Automatic Address Setting 2-32-1. Basic wiring diagram Link wiring NOTE A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only one outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side. At all the other outdoor units, change the socket (from “Yes” to “No”). A maximum of 8 indoor units can be connected to 1 remote controller for group control.
Page 395
Automatic address setting using the remote controller Case 3 If the power can be turned ON separately for the indoor and outdoor units in each system (indoor unit addresses can be set without running the compressor): Individual system automatic address setting: Display item code “A1”. (1) Press the remote controller timer time button and button simultaneously.
Page 396
2-32-3. Checking indoor unit addresses Use the remote controller to check the addresses of Installing the batteries the indoor units. Press and hold the button and (1) Press on both sides of the remote controller cover button for 4 seconds or longer (simple settings mode, and slide it downward to remove it.
Page 397
Important Information Concerning Pump Down Observe the following items when using pump down 3 – 4 HP (Single-phase)) operation to recover the refrigerant. (1) If the length of inter-unit tubing exceeds 30 m, pump down cannot be used to recover the refrigerant.
3. ELECTRICAL DATA 3-1. Indoor Units (Electric Wiring Diagram, Schematic Diagram) ......... 3-2 4-Way Air Discharge Semi-Concealed Type ................... 3-2 Wall-Mounted Type ..........................3-5 Ceiling-Mounted Type ..........................3-9 Concealed-Duct Type ..........................3-11 3-2. Outdoor Units (Electric Wiring Diagram, Schematic Diagram) ......3-19...
Page 400
3-1. Indoor Units 4-Way Air Discharge Semi-Concealed Type SPW-XDR124 / 164 / 184 / 254 / 364 / 484 / 604GH56 (A/B) SPW-X125 / 165 / 185 / 255 / 365 / 485 / 605H Electric Wiring Diagram...
4. PROCESS AND FUNCTIONS 4-1. Control Functions ...................... 4-2 4-2. Outdoor Unit Control PCB ..................4-8 4-3. Indoor Unit Control PCB Switches and Functions ..........4-18...
4-1. Control Functions 1. Indoor Air Temprature Control The thermostat is switched on and off in accordance with T shown below. T= (Indoor air temperature) - (Temperature set with the remote controller) In the body thermostat mode Indoor air temperature = (Body sensor) - (Shift temperature *) (setting at factory shipment) In the remote controller thermostat mode Indoor air temperature = (Remote controller sensor) * Shift Temperature...
Page 429
2) Maximum and Minimum Frequency Control The compressor's inverter frequency is controlled in accordance with the model and operation mode. The maximum and minimum frequencies for each model are shown in the table below. * There are cases in which frequency is limited with other control functions depending on operational conditions, so operations are not always carried out in accordance with the maximum frequencies listed below.
Page 430
5) Heating High-Load Prevention Control This system controls the inverter frequency when the high pressure's abnormal increase and high-load operating prevention occur in the heating mode. In accordance with the temperature of the indoor heat exchanger temperatures sensor (E1, E2), such controls are performed as to limiting the increase of inverter frequency, decreasing it or halting operation of the compressor.
Page 431
7) Discharge Temperature Control The following control is performed to prevent the discharge temperature from rising abnormally in order to protect the inverter compressor. In accordance with the temperature of the discharge sensor TD, such controls are performed as to limiting the increase of inverter frequency, decreasing it or halting operation of the compressor.
Page 432
Heating Mask Time This refers to the shortest time that heating operations must be performed without defrosting operations being executed. The mask time for this model is 25 minutes. Defrosting operations will not be commenced until the defrosting mask time has elapsed, even if frost adherence has been detected.
Page 433
11) Demand Control There are two styles of demand operations available as methods of restraining power consumption. (1) Demand via External Input Demand input from an external source is carried out from the outdoor unit EXCT (CN030) PCB or the outdoor unit's serial/parallel I/O (optional).
4-2. Outdoor Unit Control PCB (1-1) Layout Diagram (CR-C256VH:Up side) TERMINAL R.C.ADD TERMINAL A.ADD pin (S003) A.ADD pin (S010) RC-P JP007 (CN041) (CN032) R.C.ADD (S002) PUMP DOWN pin PUMP DOWN pin (CN042) LED1 LED2 MODE pin MODE pin (CN031) TEST pin TEST pin (CN036) EEPROM...
Page 435
4-2. Outdoor Unit Control PCB (1-2) Layout Diagram (CR-C256VH:Bottom side) Fuse Fuse (F003) SILENT SILENT (CN028) EXCT EXCT (CN026) Suction temp. Suction temp. (TS) Comp.discharge (TD) Outdoor air temp. (TO) Sensor at lower side Sensor at lower side of heat exchanger of heat exchanger (C1) Sensor at upper side Sensor at upper side...
Page 436
4-2. Outdoor Unit Control PCB (2-1) Layout Diagram (CR-C366VH:Up side) TERMINAL R.C.ADD TERMINAL (S003) A.ADD pin (S010) RC-P JP007 (CN041) (CN032) R.C.ADD (S002) PUMP DOWN pin PUMP DOWN pin (CN042) LED1 LED2 MODE pin MODE pin (CN031) TEST pin TEST pin (CN036) EEPROM EEPROM...
Page 437
4-2. Outdoor Unit Control PCB (2-2) Layout Diagram (CR-C366VH:Bottom side) Fuse Fuse (F003) SILENT SILENT (CN028) EXCT EXCT (CN026) Suction temp. Suction temp. (TS) Comp.discharge Comp.discharge (TD) Outdoor air temp. Outdoor air temp. (TO) Sensor at lower side Sensor at lower side of heat exchanger of heat exchanger (C1) Sensor at upper side...
Page 438
4-2. Outdoor Unit Control PCB (3) Layout Diagram (CR-C486VH) EXCT EXCT (CN026) QUIET MODE QUIET MODE (CN028) Fuse Fuse (F101) PUMP DOWN PUMP DOWN MODE MODE (S005) (CN031) RC-P TEST TEST (CN032) (CN036) LED2 LED1 RC ADD (S003) Terminal Terminal (CN015) RC ADD (S002)
Page 439
4-2. Outdoor Unit Control PCB (4) Layout Diagram (CR-C256VH8) Fuse Fuse (F101) Terminal Terminal (CN015) LED1 LED2 Fuse Fuse (F002) TEST TEST (CN036) MODE MODE (CN031) RC ADD (S003) RC ADD (S002) EEPROM EEPROM AUTO ADD AUTO ADD (IC007) (S001) EXCT EXCT (CN026)
Page 440
4-2. Outdoor Unit Control PCB (5) Layout Diagram (CR-C606VH8) LED2 LED1 Fuse Fuse (F101) MODE MODE (CN031) TEST TEST (CN036) RC ADD (S002) RC ADD (S003) Fuse Fuse EXCT EXCT Fuse Fuse (CN026) (F201) (F200) Sensor at upper SILENT Sensor at upper Suction Suction Outdoor air...
Page 441
4-2. Outdoor Unit Control PCB (CR-C256VH, CR-C366VH) (4-1) Explanation of Functions Auto Address 2P plug (white): Automatic address setting Pin (CN041) • If the system address switch (S002: set to 0 at time of shipment) setting is other than “0”(central control), short circuit this pin once to automatically set the addresses at all indoor units which are in the same system, and are connected to that outdoor unit.
Page 442
4-2. Outdoor Unit Control PCB (CR-C486VH, CR-C256VH8, CR-C606VH8) (4-2) Explanation of Functions AUT ADD Push-button switch (black): Automatic address setting switch (S001) • If the system address switch (S002: set to 0 at time of shipment) setting is other than “0”, press this switch once to automatically set the addresses at all indoor units which are in the same system, and are connected to that outdoor unit.
4-2. Outdoor Unit Control PCB (4-3) Explanation of Functions SILENT 2P plug (white): Enables operation in quiet mode. • The outdoor unit fan and compressor frequencies are subject to limits during operation. QUIET MODE • Low-noise operation is enabled when the relay is turned ON. (Non-voltage contact "a" ) •Example of wiring Relay (fi eld supply) Power...
4-3. Indoor Unit Control PCB Switches and Functions [Indoor unit control PCB] T10 (CN061): 6P plug (YEL) / Used for remote control operation. (Refer to the Remote Control Section.) Control items: (1) Start/stop input (2) Remote controller prohibit input (3) Start signal output (4) Alarm signal output EXCT (CN073): 2P plug (RED) / Can be used for demand control.
Page 445
4-3. Indoor Unit Control PCB Switches and Functions For AC Fan Motor (CR-UXRP71B-B (or CB-UXRP71B-B)) EEPROM (IC010) OC (CN040) VARISTOR EMG (CN044) (VA100) JP001 OPTION (CN060) EXCT (CN073) GRL (CN020) DISP (CN072) POWER LED (D002) CHK (CN071) FAN DRIVE (CN032) T10 (CN061) FILTER (CN070) For DC Fan Motor (CR-SXRP56B-B)
Page 446
For DC Fan Motor (CR-KRP50A) OPTION (CN014) FAN DRIVE (CN017) T10 (CN015) DISP (CN010) CHK (CN011) VARISTOR (VA002) JP001 EMG (CN018) EEPROM (IC002) EXCT (CN009) OC (CN019) FILTER (CN012) For DC Fan Motor (CR-KRP80A) OC (CN019) EEPROM (IC002) JP001 EMG (CN018) VARISTOR (VA002) CHK (CN011) DISP (CN010)
5. SERVICE PROCEDURES 5-1. Meaning of Alarm Messages ..................5-2 5-2. Contents of LED Display on the Outdoor Unit Control PCB ........5-4 5-3. Symptoms and Parts to Inspect ................5-5 5-4. Details of Alarm Messages ..................5-8 5-5. Table of Thermistor Characteristics ................ 5-16...
5-1. Meaning of Alarm Messages 1. Contents of the alarm display on the remote controller Blinking: OFF: Wireless remote controller Lamp display Possible cause of malfunction Display Serial commu- Remote controller is • Error in receiving serial communication signal nication errors detecting error signal from (Signal from main indoor unit in case of group control) Mis-setting...
Page 449
Blinking: OFF: Wireless remote controller Lamp display Possible cause of malfunction Display Ceiling panel connection failure Activation of Indoor protection Fan protective thermostat protective Float switch Alter. device DC fan error Outdoor protection Discharge temperature trouble AC power trouble No gas 4-way valve locked High cooling load Alternately...
5-2. Contents of LED Display on the Outdoor Unit Control PCB LED 1 LED 2 Remarks Power ON sequence 1. No communication from indoor units in system If it is not possible to advance to 3, 2. Communication received from 1 or more indoor units in system repeats 1 3.
5-3. Symptoms and Parts to Inspect Remote Alarm Eliminating controller Judgement conditions Judgement and correction contents condition of alarm alarm display Abnormal discharge Stops when temp. exceeds Recovery at restart 1. Check refrigerant cycle (gas temperature error leak). • Discharge temp. Alarm output on 4 pre-trips 2.Trouble with electronic detected at or...
Page 452
Remote Alarm Eliminating controller Judgement conditions Judgement and correction contents condition of alarm alarm display Error in current • Inverter halted after alarm Recovery at restart 1.Stops immediately even detection circuit. detected. when operations restarted. • AC current value • Alarm output on 4 consecutive •...
Page 453
Remote Alarm Eliminating controller Judgement conditions Judgement and correction contents condition of alarm alarm display Settings failure Main unit in simultaneous Power reset recovery 1.Check inter-unit control operation multi control duplicated wiring. (Outdoor unit detected) 2.Check indoor unit combination. Automatic address Insuffi cient indoor unit capacity Power reset recovery 1.Check inter-unit control setting failure...
5-4. Details of Alarm Messages SPW-C256/366VH Alarm Details (1-1) [Alarm “P29”] Start-up failure of the compressor (will not start up) Related parts • Outdoor unit control PCB (Model 256 : CR-C256VH) (Model 366 : CR-C366VH) Start of defect diagnosis Is the power voltage correct? Improve the power voltage line.
Page 455
SPW-C486VH for single-phase and C256 / 366 / 486 / 606VH8 for 3-phase Alarm Details (1-2) [Alarm “P29”] Start-up failure of the compressor (will not start up) Related parts • HIC PCB (CR-HIC160B-E, HIC-CR364GVH8, HIC-CR604GVH8) Start of defect diagnosis • Outdoor unit control PCB (CR-C486VH, CR256VH8, CR606VH8) Improve the power voltage line.
Page 456
SPW-C256/366VH (2-1) [Alarm "P26"] Excessive current alarm of HIC Control Mounted on Outdoor Unit Control PCB Related parts Start of defect diagnosis • Outdoor unit control PCB (Model 256 : CR-C256VH) Is the power voltage correct? Improve the power voltage line. Check the following: Check to ascertain that the power voltage is within the permissible range of 198 to 264V for indoor and outdoor units regardless of whether the compressor is operating or not.
Page 457
SPW-C486VH for single-phase and C256 / 366 / 486 / 606VH8 for 3-phase (2-2) [Alarm “P26”] Excessive current alarm of HIC PCB Related parts Start of defect diagnosis • HIC PCB (CR-HIC160B-E, HIC-CR364GVH8, HIC-CR604GVH8) • Outdoor unit control PCB (CR-C486VH, CR-C256VH8, CR-C606VH8) Improve the power voltage line.
Page 458
HIC Control Mounted on Outdoor Unit Control PCB CR-C256VH (outdoor unit) for SPW-C256VH, CR-C366VH (outdoor unit) for SPW-C366VH U V W HIC + HIC PCB CR-HIC160B-E HIC-CR364GVH8 HIC + HIC + U HIC-CR604GVH8 HIC + Resistance (Common use in PAC-i series)
Page 459
(4) [Alarm "P22"] Outdoor unit fan motor drive circuit trouble Start of defect diagnosis Connectors Type 256, 366 "A" = CN030(FAN) Type 486, 606 "A" = CN003(FM1), CN005(FM2) Are the connectors "A" connected correctly to the outdoor Correct the connections unit control PCB? Connectors...
Page 460
(5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12,”] Sensor trouble Start of defect diagnosis Connectors Type 256, 366 "A" = CN020(C2) "A" = CN021(C1) "A" = CN022(TO) "A" = CN023(TD, TS) Type 486 "A" = CN020(C2) ...
Page 461
Sensor Temperature Display Function (Displayed regardless of operation and stop) The below check procedure can be used to display all remote controller, indoor unit, and outdoor unit sensor temperatures. <Check procedure> (1) Press and hold the button and button simultaneously for 4 seconds or longer.
6. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL 6-1. Overview ........................6-2 6-2. Functions ........................6-2 6-3. Normal Display Operations and Functions ............. 6-3 6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures ....................6-6 6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History ......................
6-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this way, the setting switches that were located on earlier PCBs have been converted to EEPROM data. This remote controller is an out- door unit maintenance tool that is used to make and change the EEPROM settings.
Temperature monitor • Displays the indoor/outdoor unit sensor temperatures. Outdoor unit alarm history monitor • Displays the outdoor unit alarm history. Setting modes • Setting mode 1 and setting mode 2 are used to make the outdoor EEPROM setting. 6-3. Normal Display Operations and Functions Normal display functions •...
Page 466
Display (functions) • Use the temperature setting buttons to change the item code. Item code Display contents Remarks 00(1) Outdoor unit alarm contents (code) : OFF when normal At initial status Blinking 8 - alarm code display at pre-trip, LED (2) No.
Page 467
*2: 7-segment, 4-digit display for remote controller timer display The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit ( ) display and the colon. ● Display for unit Nos. 1 – 20 Not lit Not lit Not lit Not lit Meaning of display colon...
6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures <Operating procedure> (1) Press and hold the button and button simultaneously for 4 seconds or longer to switch to temperature monitor mode. During temperature monitoring, “Service Monitor” is lit. (The display and operations are the same as when monitor mode is started from the unit remote controller.) (2) Press the...
6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History Displays outdoor unit alarms only. Does not display indoor unit alarms. Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device. <Operating procedure>...
Page 470
List of Item Codes (Some item codes cannot be set due to the type of models.) Item code Parameter Control system schedule Do not set Control system schedule Do not set Control system schedule Do not set Snowfall sensor operation 0 = No sensor, control performed 1 = No sensor, control not performed 2 = Sensor present, control performed...
Page 471
• Setting mode 2 <Operating procedure> (1) Press and hold the button, button, and button simultaneously for 4 seconds or longer. (2) Use the temperature setting buttons to change the item code. The item codes and setting data are shown in the table below. (3) Use the timer time buttons to change the setting data.
7-1. Simple Settings Function • This allows the filter lifetime, operating mode priority change, central control address, and other settings to be made for an individual or group- control indoor unit to which the remote controller used for simple settings is connected. When simple settings mode is engaged, operation stops at the individual or group-control indoor unit to which the remote controller for simple settings is...
7-2. List of Simple Setting Items Setting data Item code Item Description 0000 Not displayed 0001 150 hours 0002 2,500 hours Filter sign ON time (filter life time) 0003 5,000 hours 0004 10,000 hours 0005 Use the filter clogging sensor. 0000 Standard (setting at time of shipping) Degree of filter fouling Highly fouled...
7-3. Detailed Settings Function • This allows the system address, indoor unit address, and other settings to be made for the individual or group-control indoor unit to which the remote controller used for detailed settings is connected. When detailed settings mode is engaged, operation stops at the individual or group-control indoor unit where the remote controller used for detailed settings is connected.
7-4. List of Detailed Setting Items Setting data Item Item code Description Description Description 4-Way Air Discharge 1-Way Air Discharge 2-Way Air Discharge Semi-Concealed 0000 0001 0002 Semi-Concealed (A) Semi-Concealed (S) (X, XM) Concealed-Duct 1-Way Air Discharge Concealed-Duct High Type 0003 0005 0006...
Page 478
Setting data Item code Item Description Forced thermostat ON 0000 5 minutes (1B) time 0001 4 minutes –10°C –010 –9°C –009 Cooling discharge –8°C –008 temperature shift 0010 10°C –10°C –010 –9°C –009 Heating discharge –8°C –008 temperature shift 0010 10°C 0001 ±...
Page 479
Setting data Item code Item Description 0000 No forced operation 0001 Forced operation for 1 minute Automatic drain pump operation Continuous operation 0060 None 0000 Ventilation fan operation 0001 Ventilation fan operated by remote controller. 0000 Not used. (Body sensor is used.) Wired remote controller Remote control sensor is used.
Page 480
Setting data Item code Item Description DC fan tap Purpose operating mode 0000 Standard Standard (setting at shipment) High ceiling use High ceiling setting 1 (with standard panel) Ultra long-life filter, oil guard panel, ammonia For low static- 0001 deodorizing filter, optical regenerative pressure filter Fan tap setting deodorizing filter...
7-5. Simple Setting Items Item code Item Description Filter sign ON time setting Changes the indoor unit filter lifetime when a high-performance filter or (filter lifetime) other optional product is installed. Reduces the filter sign ON time to 1/2 of the standard time (setting at the Degree of filter fouling time of shipping) for cases when filter fouling is more severe than normal.
Page 482
Item code Item Description Set when using a central control device. Central control address Used when setting the central control address manually from the remote controller. Operating mode priority change Note (1) NOTE (1) Explanation of operation mode priority change Enabled only in 2WAY MULTI heat-pump models.
Page 483
When the operating mode at the priority remote controller is changed, the operating modes of other remote controllers change as shown below. Mode change at priority remote controller Operating modes at other remote controllers Current mode New mode Current mode New mode Cooling or dry Heating...
7-6. Detaild Setting Items Item code Item Description Unit type Set when the indoor unit EEPROM memory is replaced during servicing. Indoor unit capacity System (outdoor unit) These are not set at the time of shipping from the factory. address These must be set after installation if automatic address setting is not Indoor unit address performed.
Page 485
Item code Item Description 1F (Upper limit) Cooling 20 (Lower limit) This setting changes the temperature range (upper limit and lower 21 (Upper limit) Change to the limit) which is set from the remote controller or central control Heating 22 (Lower limit) remote control device.
Page 486
(Continued from previous page) Item code Item Description Heat exchanger The heat exchanger temperature control point for prevention of cold temperature for cold air air discharge during heating operation can be changed. discharge The indoor unit PCB optional output for the fan can be switched Fan output switching according to the purpose of use.
Page 487
DC Fan Tap Change Procedure <Procedure> Be sure to turn the main power OFF before performing the steps below. (1) Check the optional product that will be used from the table below. Setting No. Optional part name Optional part No. Super long-life filter AFT-LS140A Oil guard panel...
7-7. Remote Controller Servicing Functions • The remote controller includes a number of servicing functions. Use these as needed for test runs and inspections. List of Servicing Functions Functions Description Button operation Reset operation Unit status Operation with forced Press and hold the button for 4 Test run thermostat ON...
Page 489
Sensor Temperature Display Function (displayed regardless of whether unit is operating or stopped) The procedure below displays the sensor temperatures from the remote controller, indoor unit, and outdoor unit on the remote controller. <Procedure> 1 Press and hold the buttons simultaneously for 4 seconds or longer.
Warning 8-1. Warning about Installation of Receivers The wireless remote uses a very weak infrared light for its signal, which can result in the signal not being received because of the following influences, so take care in where the unit is installed. ·...
Optional Controller (Remote Controller) Wireless Remote Controller / RCS-SH80BG.WL / RCS-TRP80BG.WL / RCS-SS80BG.WL / RCS-BH80BG.WL / RCS-XM18BG.WL One remote control can control a group of up to eight indoor units. 8-3. Names and Functions REMOTE CONTROLLER 1. Operation Display Displays the operation status. 15.
Page 494
RECEIVER 1. Receiver Receives the signal sent from the RCS-SH80BG.WL RCS-TRP80BG.WL remote control. 2. Emergency Display lamps operation When an error occurs, one of the button lamps fl ashes. When a display lamp is blinking, refer to " Before Requesting Service ". 3.
8-4. Installing Batteries 1.Remove the cover. 2.Insert two AAA alkaline batteries. Put the batteries in with the polarity [+/–] as shown in the fi gure. 3.Gently insert one end of an unfolded paper clip (or a similar object that can fi t) into the Reset hole and press the Reset button inside the hole and then Reset hole put the cover back on.
8-7. Timer Operation • When setting the timer, make sure the current time on the remote control is accurate. • The timer’s clock can only be set when the display of the remote control is ON. • After setting the timer, put the remote control in a place where its signal will reach the receiver of the indoor unit.
8-9. Operating Multiple In/Outdoor Units Simultaneously Indoor Unit (Group Control) Group control works well for providing air conditioning to one, large room with more than one air conditioning units. Receiver Indoor Unit • One remote control can operate up to eight indoor units. Signal Line •...
Page 498
Address Display on the Remote Control RCS-SH80BG.WL For 1, 2 and 3, set the switch on the left and for 4, 5 and Position of The position of the 6, to the right. receiver’s receiver’s address (inside indoor switch does not unit) address matter.
8-13. Emergency Operation Use [Emergency Operation] in the following situations when there is an urgent need. • When the remote control's batteries have failed. • When the remote control is broken. • When the remote control is lost. *1 Figures: RCS-SH80BG.WL and RCS-TRP80BG.WL are of receivers (inside indoor unit), RCS-SS80BG.WL is of the operation panel (inside indoor unit) and Indoor Unit (K type) is of its front panel.
8-14. Miscellaneous Settings A variety of changes can be made to settings, depending on the indoor unit being used. Wind direction (fl ap) indicator, operation mode indicator, time display (24 hour, AM/PM), heat max temp • For information about the fl ap function, refer to the users’ manual of the unit being used. •...
How to Install the Wireless Remote Controller Receiver 8-16. Common to All Models 1. Warning about Installation of Receivers The wireless remote uses a very weak infrared light for its signal, which can result in the signal not being received because of the following infl uences, so take care in where the unit is installed.
Page 502
8-17. RCS-SH80BG.WL 1. Accessories Accessories Quantity Accessories Quantity AAA alkaline batteries Receiver Users Manual Truss self-tapping screws 4 X 16 Remote controller Cable clamp Remote control holder Clamp fi xing screw 4 X 12 2. Installing the Receiver Unit The receiver can only be installed on the corner indicated in Fig. 8-1, so consider how the panel will face when it is installed on the indoor unit.
Page 503
3. Wiring the Receiver Unit • Wiring Diagram Receiver PCB Indoor Unit CN001 Terminal Strip for Wiring Remote White Controls Black • Connections Connect the wires from the receiver to the remote control terminal strip on the indoor unit. (Polarity does not matter.) 4.
Page 504
8-18. RCS-TRP80BG.WL 1. Accessories Accessories Quantity Accessories Quantity AAA alkaline batteries Receiver Users Manual Remote controller Truss self-tapping screws 4 X 16 Remote control holder Cable tie 2. Installing the Receiver Unit • Ceiling Suspended Model (1) Open the air inlet grille on the side panel, remove the 1 screw and then move it toward the front (direction of the arrow) and remove it.
Page 505
• Unidirectional cassette model for high ceilings/Unidirectional ceiling cassette model 1. While spreading the tabs of the cover, pull it out from the panel to the front. (Fig. 8-10) 2. Pass the lead wire through the panel and install the receiver in the hole in the panel. (The projecting parts of the receiver hold it in the hole in the panel) 3.
Page 506
4. Test Operation S003 Implementing a Test Run Bit 1: OFF 1. Turn the #1 DIP switch [S003] on the receiver’s PCB from OFF to ON and operate the wireless remote control with its Start/Stop button. 2. During a test run, all display lamps on the display will light up. 3.
Page 507
8-19. RCS-SS80BG.WL 1. Accessories Accessories Quantity Accessories Quantity Operation panel AAA alkaline batteries Users Manual Display Truss self-tapping screws 4 X 16 Remote control Pan head self-tapping screws 4 X 10 Remote control holder Plastic clamp L150 2. Accessories Installing the Display/Operation Panel Resin Panel Installing the Operation Panel 1.
Page 508
Metal Panel Installing the Operation Panel 1. Remove the 2 screws and remove cover A from the back of the panel. (Fig. 8-19) 2. Fasten the operation panel to the location in the diagram below with the 2 enclosed screws (4 X10). (Fig. 8-20) 3.
Page 509
4. Test Operation DIP Switch Bit 1 Implementing a Test Run 1. Turn the #1 DIP switch of the operation panel from OFF to ON (Down Up) and operate the wireless remote control with its Start/Stop button. 2. During a test run, all display lamps on the display will light up. 3.
Page 510
8-20. RCS-BH80BG.WL 1. Accessories Accessories Quantity Accessories Quantity Receiver Users Manual (Enclosed 200 mm wiring) Truss self-tapping screws 4 X 16 Remote controller Machine screws Remote controller's holder Wood screws AAA alkaline batteries Cable tie 2. Installing the Receiver Unit When using a separately installed receiver as a built-in model, install it to the JIS switch box (fi eld supply) shown in the diagram on the right, which has been built into the wall on site in advance.
Page 511
When using a receiver that has been installed separately into the ceiling, use the enclosed fi ttings for installing to a ceiling. (1) Remove the metal plate of the receiver by slipping a fl athead screwdriver or the like into the cut-out on the bottom.
Page 512
4. Setting Address Switches • When more than one receiver and remote control are installed in the same room, setting up addresses allows them to avoid interfering with each other. • Refer to the Users Manual for information on how to change the addresses of the remote controls. •...
Page 513
8-21. RCS-XM18BG.WL 1.Accessories Accessories Quantity Accessories Quantity Receiver Remote controller's holder AAA alkaline batteries Tapping screw 4x16 Remote controller Clamper 2.Installing the Receiver Unit As the receiver can only be installed in the corner where the panel wire comes out, as shown in Fig. 8-32, consideration should be given to orientation when fi tting the panel to the indoor unit.
Page 514
3. Pass the wire from the wireless receiver through the grille. (Fig. 8-34) 4. Fit the panel to the indoor unit and connect the wire from the receiver to the connector (CN130/WL/WHT/10P) on the indoor control board. (Fig. 8-35) 5. After fi xing the panel in place, fi t the receiver to the panel taking care not to trap the wire from the receiver. 6.
Page 515
8-22. Common to All Models 1. The Self-Diagnosis Function Display and What is Detected Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote control is connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to Test Run or servicing materials.
Page 516
3. Setting Up Remote Control Functions The functions of the wireless remote can be set on site. (These settings are saved in nonvolatile memory in the remote control, so even when its batteries are changed, the settings do not revert to the defaults.) NOTE The operation of the air conditioner can be impacted, depending on the settings made, so only service personnel should make the settings.
Page 517
SANYO Electric Co., Ltd. 201002E DC Printed in Japan...