hit counter script

Operation Details - LG LT-D5480HL Service Manual

Ceiling cassette air conditioner
Table of Contents

Advertisement

Operation Details

(1) The function of main control
1. Time Delay Safety Control
• 3min
The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 5sec
Vertical louvers are delayed for 5 secs to be opened to prevent the frictional sound between louver and air flow.
• 30sec
The 4-way valve is ceased for 30sec. to prevent abnormal noise when the Heating operation is OFF or
switched to the other operation mode while compress is off.
While compressor is running, it takes 3~5 seconds to switch.
2. Auto Swing Control
• This function is to swing the louver up and down automatically.
3. Air-Filter Checking Control
• 'Filter' sign will appear on the remote controller display and main body display when an air-filter is polluted. Then
clean the air-filter referring to Owners Manual.
4. Soft-Dry Operation
• The indoor fan speed is automatically set to the low, and fan speed control is not available because of already
being set to the best speed for Dry Operation by Micom Control.
5. Cooling Mode Operation
• When selecting the Cooling(
troller and the operation diagram is as follows.
Intake Air temp.
SET TEMP.+0.5°C
(COMP. ON)
SET TEMP
SET TEMP. -0.5°C
(COMP. OFF)
INDOOR FAN
COMPRESSOR
) Mode Operation, the unit will operate according to the setting by the remote con-
More than
3 minutes
Selected
Low
fan speed
ON
OFF
Selected
fan speed
ON
–11–
More than
3 minutes
Selected
Low
fan speed
OFF
ON

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lt-d5480haLt-d5480clLt-d5480ca

Table of Contents