hit counter script

Contact S51/P1 - ABB Tmax T7 Operating Instructions Manual

T7-t8-x1 low voltage air circuit breakers protection releases
Hide thumbs Also See for Tmax T7:
Table of Contents

Advertisement

3.8.5.

Contact S51/P1

PR332/P and PR333/P have an external contact, which can be configured by the customer and is useful for monitoring a series
of events, including alarms and protection trips
The configuration options of the contact, available via PR010/T or Ekip Connect, are:
- Monitoring event/s;
- Contact activation delay;
- Idle state (normally open or closed);
- Trigger configuration (Auto or Single).
The parameters are available in the Settings-Modules-SIGNALLING module-Relay.
The contact is available in all supply configurations and possesses the following electrical characteristics:
Type of contact
Maximum switching voltage
Maximum switching current
Maximum switching power
Contact/Circuit insulation
NOTE: contact S51/p1 is not available for release PR332/P MM.
3.8.6.
Function MM
PR332/P MM has a pair of input and output contacts for managing protection MM, described on page <OV>:
- K14/K15: input for activating protection MM;
The voltage applied between K14 (+) and K15 (-) establishes the state of the protection:
- 0..2Vdc protection deactivated.
- 15..24Vdc protection activated.
Consumption @24Vdc= 3mA max.
- 95S/98S: the output supplies the state of protection MM:
- If the protection is active, the contact is closed;
- If the protection is deactivated, the contact is open.
The electrical characteristics of the output contact are the same as those of contact S51/P1, described in the previous chapter.
Operation of the output contact is guaranteed when the release is on, in the Full Power mode or in the presence of auxiliary supply.
WARNING:
-Upon powering, and if there is already energizing voltage on the input contact, the output contact closes within 100 ms.
-Following a trip through protection MM, the output contact can open temporarily for up to 20ms.
3.9. Settings Menu
The Settings menu contains various different settings for protection release operation and for configuring the installation in the
correct way.
9 options are available:
Settings Menu Options
1. Circuit breaker
2. Mains frequency
3. Modules
4. Data Logger
5. Dual setting
6. Measurement interval
7. Harmonic distortion
8. System
9. Display Contrast
3.9.1.
Circuit-breaker
This area allows you to:
- Enable the Neutral protection (ON/OFF) and adjust its control level (50%- 100% - 200%). All the details about the operating
mode are given in the description of the Neutral protection, in par. 1.6.20.
- Enable the presence of a sensor on the earth protection line (SGR or Rc). A further option for selecting the sensor model
(100,250,250,800) will be available if the selected sensor is the SGR type. Functions and case reports on use of the earth pro-
tections are illustrated in the chapters that describe protections Gext (par. 1.6.9) and Rc (par. 1.6.10).
- Perform the installation and uninstalling operations for the protection release in the CB. Instructions for correct installation are
given in par. 1.12.1 and 1.12.2.
B0431
Mod.
400 Vac (Peak) / Vdc
0.1 Aac (Peak) / Adc
40 W
1500 Vac
Description
Enabling and adjustment of the Neutral protection, earth protection and the installation com-
mands
Adjustment of the frequency of the installation
Monitoring and setting of the internal module characteristics
Enabling and adjustment of the Datalogger function
Enabling and setting of the dual set function (available with PR333/P).
Adjustment of the measurement interval for the log file
Activation of the harmonic distortion control (available with PR333/P)
Date, time, language, password settings
Adjustment of the display contrast
B1751
Apparatus
Emax X1-Tmax T7-Tmax T8
1SDH000587R0002
Doc N°
Scale
Page No
52/66

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Emax x1Tmax t8

Table of Contents

Save PDF