Hot water energy management control for raytherm & hi delta hot water supply boilers & water heaters (24 pages)
Summary of Contents for Raypak LONMARK Y-200
Page 2
is a registered trademark of Underwriters Laboratories Inc. ®...
Page 5
Model No. Description Y-241 4-Stage Controller - Includes main controller assembly, air temperature sen- sor assembly (P/N 068634), water temperature assembly (P/N 068635) and one (1) stage contact board. Main controller includes one (1) mounted auxiliary contacts board. Y-281 8-Stage Controller - Includes main controller assembly, air temperature sen- sor assembly (P/N 068634), water temperature assembly (P/N 068635) and two (2) stage contact boards.
Page 6
BLACK CIRCUIT VOLT-OHM BREAKER METER WHITE GREEN GROUND A B C...
Page 10
4 OR MORE STAGES OR 4:1 TURN DOWN OR HIGHER 5’ MAX 5’ MAX 12”...
70 °F (21.1°C); or in domestic hot water applications, the desired Setpoint Temperature at which the boiler turns off and on. NOTE: The Band is adjusted during PID operation, it disables the PID Control Band...
Page 14
Alarm Call Events PID Settings sets time interval between stages turning off. Displays the boiler inlet and outlet temperature in °F or °C and the difference (delta) between them. sensor installation, option Y-306.) The lead change time in hours, the lead and last boiler numbers and the mode (either Auto or Manual).
Page 15
Reset Switch Main Circuit Board Manual Override Switch Manual Override Switch a i l...
Page 16
Not active except in special modes To access programming mode: Press and hold "MODE" button for 4 seconds. If no button is pressed while in PROGRAM mode for 30 seconds, screen returns to normal mode Move to previous programmable parameter When in PROGRAM mode, cursor is blinking on first settable parameter.
c i f This is the initial screen displayed after system start-up, provided that there are no faults. Calendar: Month-Day-Year Fahrenheit or Celsius Current time: System water temperature desired at 24 hour clock outdoor temperature of 70°F (21.1°C) Range: 40°F to 220°F(4.4°C to 104.4°C) Default Value: 140°F (60°C) Screen number Screen number...
*C Band is a range of temperature above and below the target temperature. Range: 1°F to 10°F (.5°C to 5.5°C) Default value is 3°F ° Fahrenheit or Celsius Screen number...
"OFFSET" screen Default "OFF" screen Press "MODE" to select "OFF" or "ALL" or "FULL WEEK" "ALL" means every day has the same parameters. — — — There are six offset adjustments allowed for each calendar day. "FULL WEEK" screen There are eight days of selectable offsets: +, blank or –...
Page 20
Thirty two holidays are selectable (01-32) Ratio of outdoor temperature to water system temperature. Range: . 01:1 to 8:1 or "None" for constant water temperature (then TARGET=SETPOINT). Default value is 1.00:1. Default: System temperature at 70°F (21.1°C) 140°F @ 70°F (60°C @ 21.1°C) —...
Typical Temp@ Radiation Design Cond. Standing Convection or Baseboard Fan coil Heating Fan Coil Heat and Cool Radiant Floor Radiant Ceiling Reset Ratio Setpoint at Design Temp: Temp@ 70°F 40°F 20°F 0.3:1 0.6:1 0.3:1 0.5:1 0.3:1 0.6:1 0.9:1 1.4:1 2.0:1 3.3:1 2.0:1 3.3:1...
Page 22
If more than one ERROR, all errors will be displayed in sequence. ERROR Indications: Message NO SAFETY SIGNAL NO CFH SIGNAL WATER TEMP>MAX ILS>OLS SYS IS OPEN SYS IS SHORT OLS IS OPEN OLS IS SHORT ILS IS OPEN ILS IS SHORT OSS IS OPEN OSS IS SHORT Meaning...
Page 23
If the outdoor temperature increases beyond the outdoor cut-off setting, there is no call for heat and the pump turn off delay becomes active. If the outdoor temperature falls below the outdoor cut-off minus the outdoor cut-off Deadband the boiler bank will again be enabled.
Total # of stages available is set on screen 24. SYSTEM PUMP MODULE Rule: Always on before boiler. Always off after last boiler off + programmed delay, or outdoor sensor reading is above cut off temperature setting. P is relay #1 as supplied.
Page 26
Screen number Screen number Screen number...
Page 27
This screen is only a display. Current boiler inlet or system temperature* Auto or Manual — If manual lead Run time change hours (Displayed in manual) Current boiler outlet or system temperature* — Lead boiler Screen number Boiler or System delta.* Screen number —...
P is relay #1 as supplied. INDICATES BOILER Rule: Always B before S INDICATES BOILER STAGE Rule: Must have "B" for that boiler ON and prior stages ON for that boiler. See example above. AUXILIARY RELAY MODULE Optional: A1 - User defined function. (i.e. powered louvers, boiler pump, draft fan) A2 - User defined function.
In display mode shows AAA or current password. To change the default password AAA to a new password: 1. Push the mode key. The cursor under the first A should start flashing. 2. Change the first letter by using the up or down key to the desired letter. 3.
Page 30
0, 1, 2 or 4 Number of temp. sensors. Master unit Total no. Relay sensors of stages boards 01 - 04 05 - 08 1 & 2 09 - 12 1 & 2 13 - 16 1 & 2 17 - 20 1 &...
Number of slaves connected: 01 thru 04 Press MODE button to get into program mode. Press UP arrow key to select YES. Press MODE button to load Factory Defaults and to exit program mode. NOTE: If unit times out the factory defaults will not be set. Screen number Screen number Screen number...
Press MODE button to get into program mode. Press UP or DOWN key to select “Setup Defaults”. If parameters have been changed and original user defaults are required: Press UP or DOWN key to select "Invoke Defaults". Press MODE button to exit program mode. Press MODE button to get into program mode.
Used to enter telephone number to be called when a fault occurs. Used to identify person or place to be called when a fault occurs. Used to set the number of times (00 to 20) you want the unit to keep calling out when a fault occurs. Enable or disable system error indications.
Page 34
Press MODE button to get into program mode. Go to screen number 25 and select the number of slaves you wish to use, 01 thru 04. Go to screen number 24 and select the number of sensors, relays and auxiliaries. Go to screen number 20 and set up your Network master and slave operations.
Page 35
Go to screen number 11 and it should cycle thru your complete setup. Press MODE button to get into program mode. Go to screen number 25 and display should read. Go to screen number 20 and set up your unit operations. Ignore screen number 11 on the slave units.
Page 38
Item No. Description PC Board Assy, Y-200 Expansion Board Assy, 4-Stage Auxiliary Board Assy Transformer Assy LCD Display Assy Control Keypad Modem Module Lon Works Module 4-20 MA/2-10 VDC Module Wire Bonding Connector Air Temp Sensor Assy Water Temp Sensor Assy Air/Water Temp Sensor l l e Retainer and Screw...
Page 39
In accordance with the terms of this Limited Warranty, RAYPAK will furnish a replacement or repair, at our option, any defective part which fails in normal use and service during the applicable warranty period.