EAST Group 9010 User Manual

EAST Group 9010 User Manual

10-120 kva 3/3 series ups

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for EAST Group 9010

  • Page 2: Table Of Contents

    CATALOG   Chapter 1: Introduction ........................1  1.1 Brief Introduction of Performance Features ..............1  1.2 System Structure ........................1  1.3 Operating Mode ........................3  1.4 Functions and Characteristics....................5  Chapter 2: Installation Instruction ..................... 7  2.1 Unloading and Unpacking ..................... 7  2.2 Site Selection ..........................
  • Page 3 PREFACE     Thank you for using our products.  Our company is engaged in developing and manufacturing products of uninterrupted power system  which is a kind of power product with high quality and can meet various performance requirements.      Note: This  manual  contains  instruction  of  mounting,  application,  and  operation  of  UPS.  It  shall  read  this  manual  carefully before  mounting the  system  and  it is  not  allowed to  take  any  operations on  UPS  before  finishing  reading  all  safety  instruction  and  operation  instruction.  This  manual  contains  significant ...
  • Page 4 Change History Changes between document issues are cumulative. The latest document issue  contains all the changes made in earlier issues.  Issue V_02 (2014‐04‐10)    Compared with V01 version, the modified contents are as follows: Delete the contents of unpacking module package.  Increase the descriptions of 80‐120KVA based on Issue V_01.  Increase the way of setting +15 pieces of battery.  Increase the function of input dry contact.  Change the number of dial switch of module ID, 4 pin to5 pin.  Update some pictures based on Issue V_01.    Issue V_01 (2012‐11‐30)        This is the first release.             ...
  • Page 5: Chapter 1: Introduction

    10-120KVA (3/3) UPS user manual   Chapter 1: Introduction 1.1 Brief Introduction of Performance Features 10‐120KVA (3/3) series is a kind of high‐frequency UPS with three‐inlet and three‐outlet designed by  full digital control technology. The design of unit breaks conventional design thought of tower‐type  machine,  replaced  by  advanced  modular  design  idea  which  can  ensure  compactness  of  layout  and  improve reliability of the unit. Electrical performance of 10‐120KVA (3/3) series is advantageous and  protection of software and hardware of it is perfect. It is applicable for different power grid and can  supply safe and reliable power for different loads.    1.2 System Structure Components of the system mainly include: LCD display screen, communication port, power module,  charger, battery (optional), input breaker, output breaker, maintenance bypass breaker, ground row,  N row, and so on. Its system structure chart is shown in figure 1.1, figure 1.2 and figure 1.3. ...
  • Page 6 10-120KVA (3/3) UPS user manual 1.Communication port 2. LCD display screen 3.Power module 4. Charger SPD breaker(optional) 6. SPD (optional) 7. Input breaker 8.Output breaker Maintenance bypass breaker 10. Bypass breaker Terminal block of input,bypass and output Terminal block of battery Terminal block of ground Terminal block of N Front(without baffle)
  • Page 7: Operating Mode

    10-120KVA (3/3) UPS user manual   1.3 Operating Mode 10‐120KVA (3/3) is a kind of online double‐conversion UPS, its operating modes are as follows:  Main power supply mode  Battery mode  Bypass mode  Maintenance mode (manual bypass)  Frequency converter mode  1.3.1 Main power mode The  working  mode  that  alternating  current  power  of  rectifier  circuit  for  UPS  is  supplied  by  main  power,  direct  current  power  for  inverter  is  supplied  after  corrected  by  PFC  power  factor,  and  continuous ...
  • Page 8 10-120KVA (3/3) UPS user manual   Maintenance bypass    bypass AC/DC  Main powe  DC/DC boost    DC/AC inverter    Out put rectification    input Charger  BATTERY   Figure 1.5 Working Process Chart under Battery Mode  1.3.3 Bypass mode If  fault,  such  as  inverter  circuit  fault  and  inverter  circuit  overload,  or  switching  to  bypass  mode  by  hand occurs, the UPS will switch the load from side of inverter to side of bypass and power supply for  the load is not interrupted. ...
  • Page 9: Functions And Characteristics

    10-120KVA (3/3) UPS user manual     Figure 1.7 Working Process Chart under Maintenance Bypass Mode  1.3.5 Frequency converter mode UPS can be set to frequency converter mode which can provide stable output frequency of    50Hz or  60Hz.  Input  frequency  range  of  main  power  is  40  Hz  ~  70  Hz.  UPS  will  output  the  set  output  frequency and the bypass mode is ineffective under frequency transformer mode. When main power  is abnormal, the system will switch to battery mode automatically and still output with the set output  frequency.  1.4 Functions and Characteristics DSP full digital control technology; ...
  • Page 10 10-120KVA (3/3) UPS user manual   Easily damaged components can be changed in module level, field replacement is fast and  convenient and module cost is low;  Perfect hardware and software protection function (breaker, Fuse, hardware protection, and  software protection), super self diagnosis, and rich historic record enquiry;  5.7 inch LCD touch wide screen display, friendly human‐machine interface;    Many communication ports, including RS232, RS485, USB, dry contact card and SNMP smart  card trough.    - 6 -...
  • Page 11: Chapter 2: Installation Instruction

    10-120KVA (3/3) UPS user manual   Chapter 2: Installation Instruction 2.1 Unloading and Unpacking User shall check the package to confirm it is undamaged after receiving the product; then open the  package to check whether the equipment is undamaged, and please contact the carrier at once if it is  damaged.    2.1.1 Open of cabinet package 1) Put the packing box vertically;    Figure 2.1 Packing Box Placements  2) Open the top plate of packing box and then take out the foam;    Figure 2.2 Unseal the Packing Box  - 7 -...
  • Page 12: Site Selection

    10-120KVA (3/3) UPS user manual   3) Unseal side plates of packing box and then take out the foams.      Figure 2.3 Unsealed Cabinet  Tips: It shall be careful when unsealing to prevent scratch for the machine body.    Check whether the qualified certificate, instruction book, CD disk, and keys for front and back doors  are complete or not after opening the packing box.    2.2 Site Selection   Placed location must be stable;      Enough ventilation space must be left between all surfaces of UPS and walls;    Be far away from hot source and corrosive materials, avoid the sunshine;    Keep normal working temperature and elevation height (working temperature: 0℃  ~  40℃,            it needs to be applied by derating if elevation height exceeds 1500m);      Keep  clean  working  environment,  avoid  environment  with  moisture,  flammable  gas,    flammable liquid, or corrosive material; ...
  • Page 13: Cable Selection And Connection

    10-120KVA (3/3) UPS user manual     Figure 2.4 Cabinet Placement Chart    2.4 Cable Selection and Connection 2.4.1 Selection of cable When selecting connecting cable for the system, it is suggested to select the wire diameter of cable  according  to  maximum  power  configuration  of  10‐120KVA  system  and  complying  local  connection  rules  and  environmental  condition  (temperature  and  physical  support  media).  The  cable  shall  be  selected ...
  • Page 14 10-120KVA (3/3) UPS user manual 2.4.2 Connection of cable Battery  input  (long‐term  machine),  main  power  input,  bypass  and  output  cable  shall  be  connected  with UPS according to the paths shown in Figure 2.5 and figure 2.6.      Figure 2.5 Inlet and Outlet Wiring Channel of 10‐60K    Figure 2.6 Inlet and Outlet Wiring Channel of 80‐120K    Connection of cable is:  1) Open the distribution board to expose the copper rows.      Figure 2.7 Front View of    10‐30KVA  - 10 -...
  • Page 15 10-120KVA (3/3) UPS user manual   Figure 2.8 Front View of    40‐60KVA                                        Figure 2.9 Front View of    80‐120KVA    - 11 -...
  • Page 16 10-120KVA (3/3) UPS user manual   2)  Phases  shown  in  following  figure  are  line  terminals  of  main  power  input,  bypass  input,  battery  input and output cable after passing the inlet and outlet wiring channels.        Figure 2.10 Distribution Wiring Diagram of 10‐30KVA series          Figure 2.11 Distribution Wiring Diagram of 40‐60KVA series  - 12 -...
  • Page 17: Battery Connection

    10-120KVA (3/3) UPS user manual   Figure 2.12 Distribution Wiring Diagram of 80‐120KVA series    Tip: please tighten the input and output cables and wiring row.              3) Recover the distribution panel  2.5 Battery Connection 2.5.1 Battery connection of long-term machine Battery  group  for  this  machine  is  positive  and  negative  battery  group  framework,  total  number  of  battery ...
  • Page 18 10-120KVA (3/3) UPS user manual   As  shown  in  figure  2.13,  connect  all  batteries  in  series,  and  lead  a  N  line  from  middle  connection  point of battery groups, so it shall be three lines together with positive and negative ends of battery  group to connect with battery connecting terminals of UPS. Batteries between positive end of battery  group and N line are called positive batteries, and batteries between negative end of battery group  and  N  line  are  called  negative  batteries.  User  can  select  the  capability  and  number  of  battery  according to its demand. It must add a direct current breaker between battery group and UPS to play ...
  • Page 19 10-120KVA (3/3) UPS user manual     Figure 2.15 Right View of Battery Pack    4) Put the battery pack with batteries to corresponding location and lock the set screws.    5) Measure whether the voltage of every battery pack is normal(192~208V), then measure whether  the side lead terminal is short‐circuit ,if all of them is normal, connect the battery pack with UPS  according to the connecting method shown in following figure 2.15, if the voltage of battery pack is  0V, check whether the battery fuse is disconnect.    Figure 2.16 Connecting Diagram of Battery Pack    6) Recover the battery pack panel.    Maintenance of battery pack:  1)  Switch the UPS to maintenance bypass mode.  2)  Remove the battery pack panel to expose the battery pack.  3)  Cut off the connecting line of battery pack (as shown in Figure 2.16).  4)  Take away the set screw of battery pack and then take away the battery pack.  5)  Replace the battery according to the demand.  6)  Recover the battery pack.  - 15 -...
  • Page 20 10-120KVA (3/3) UPS user manual   The following safety notes shall be noted all the time when mounting and maintaining the batteries:  1). Electric shock may occur when mounting the batteries, high short‐circuit current may cause fire;    2). Voltage of battery groups can be 480Vdc which may cause death, so please obey safety attentions  for voltage operation;    3). Only qualified personal can mount and maintain the batteries;    4). Wear protective eyewear to prevent accident caused by electric arc;    5). Take off ring, watch, necklace, bracelet, and other aglets;    6). Use tools with insulated hands;  7).  It  shall  break  down  the  breaker  of  battery  when  connecting  lines  between  UPS  and  battery.  It  must ensure that the sequence and polarity of connection are correct after finished connection;    8). Please contact customer service department of our company if the user needs to change the  number of used batteries during normal application. Please do not operate it solely.   ...
  • Page 21: Chapter 3:Operation

    10-120KVA (3/3) UPS user manual Chapter 3:Operation This  chapter  describes  all  enquiries  and  setting  operations  of  UPS  taken  by  operator,  including  starting of UPS, power off of UPS, all enquiry operations, and parameter setting, etc.  Tips:  instruction  manual  must  be  read  carefully  before  implementing  the  following  operations  to  avoid personal injury or equipment damage caused by misoperation.    3.1 Introduction of Operation Interface As ...
  • Page 22: Operation For Power On Of Single Machine (10-60Kva For Example

    10-120KVA (3/3) UPS user manual   Output parameter   Return to main interface   Return to previous menu   Page down    Page up   History   Self‐test and mute off   Record enquiry     TAB  Switch of touch/button‐control    UP  Cursor up   DOWN  Cursor down  Operation buttons  ENTER  Confirm    CANCEL  Return to touch‐control from button‐control  COLD START  Cold start  EPO  Emergency power off ...
  • Page 23 10-120KVA (3/3) UPS user manual   3.2.1 Start under main power mode 1. Start main power mode directly  1) Connect the main power  Close  the  input  and  bypass  breaker  and  UPS  connect  to  the  main  power  and  bypass.  The  UPS  screen starts to work and then LOGO interface occurs.        Figure 3.2 Logo Interface    It will be refreshed to main interface after 1s,and the bypass will start automatically.      Figure 3.3 Main Interface ...
  • Page 24 10-120KVA (3/3) UPS user manual     Figure 3.4 UPS ON password  Click icon of “TO INV” and then UPS starts to power on under main power.        Figure 3.5 On/Off Interface    Process of starting UPS under main power mode will be finished after a time.  The charger starts to power on automatically after the power module is started, and the starting of  charger module is finished after a time.      3) Close battery and output breakers    Close the battery break (long‐term machine) and output breaker after starting of UPS under main  power is finished, and then the UPS start normal operation.    Energy flow after it is started under main power mode is shown in Figure 3.6:          - 20 -...
  • Page 25 10-120KVA (3/3) UPS user manual     Figure 3.6 Operations under Main Power    2. Switch from bypass mode to main power mode    If the UPS is working under bypass mode, click the On/Off icon in main interface to pop the On/Off  interface.      Figure 3.7 On/Off Interface      Click icon of “TO INV”, the UPS will begin to start the main power mode, and starting under main  power mode will be finished after a time.      3.2.2 Starting under battery mode If main power is fault, UPS can be turned on by battery mode directly.  1. Close battery breaker, input breaker and bypass breaker and connect the battery.    2. Press button of “COLD START” in control panel to turn on the LCD screen. LCD screen displays main  interface.  - 21 -...
  • Page 26 10-120KVA (3/3) UPS user manual   3. Press “ENTER” for 2s to build working power for power module, and then the fan of module starts  to rotate. Click the battery icon to check whether the battery set is the same with actual battery  configuration (Detailed operation is shown in 3.6.3 and 3.6.4).      Figure 3.8 Main Interface    4. Click On/Off icon in main interface to pop the On/Off interface. Click icon of “INV ON”, and the  starting under battery mode will be finished after a time.      Figure 3.9 On/Off Interface    5. Close output breaker, and then the UPS output is normal and starting by battery is finished.    Its energy flow is shown in figure 3.10:          - 22 -...
  • Page 27 10-120KVA (3/3) UPS user manual     Figure 3.10 Battery Mode  3.2.3 Starting under bypass mode It can switch to bypass mode directly under main power mode or under the case that main power is  available but the UPS has not been started yet.    1.  Start  the  bypass  mode  from  standby  mode  (main  power  is  available  but  the  UPS  has  not  been  started yet).  The UPS has not been started currently, and display of its main interface is shown in Figure 3.11:  Click  the  battery  icon  to  check  whether  the  battery  set  is  the  same  with  actual  battery  configuration. ...
  • Page 28 10-120KVA (3/3) UPS user manual   1) Click On/Off icon in main interface to pop the On/Off interface.      Figure 3.12 On/Off Interface    2)  Click  icon  of  “BYP  ON”,  UPS  will  enter  the  bypass  mode,  and  the  bypass  mode  is  started.  The  charger will start automatically after a time.  3)  Close  battery  breaker  (long‐term  machine)  and  output  breaker,  and  the  bypass  starts  to  output  normally. ...
  • Page 29 10-120KVA (3/3) UPS user manual     Figure 3.14 On/Off Interface    Click icon of “TO BYP”, and then the system will enter into bypass mode.  3.2.4 Start charger 1. Charger will start automatically to charge the battery when UPS is started under main power mode  or bypass mode.  2.  If  the  charger  is  off  and  needs  to  be  restarted,  when  the  UPS  is  in  main  power  mode  or  bypass  mode, it can click the On/Off icon in main interface to pop the On/Off interface, click icon of “CHG  ON” below the “CHG ON/OFF”, and then the charger will be started.    3. Click the icon of charger in main interface to check the working state of charger.     ...
  • Page 30: Operation For Power Off

    10-120KVA (3/3) UPS user manual normally when main power fails suddenly.    Click icon of self‐test and mute off in main screen, the popped interfaces include “TEST 10S”, “TEST  10M”, “TEST LOW”, “CLR TEST”, and “MUTE”. Click one of the first three options to select the self‐test  time. Select different self‐test times according to the time of actual test period.      Figure 3.16 Self‐test and Mute off Interface    3.2.6 Starting under ECO mode If the main power is normal and battery is connected, when the bypass voltage qualified the  need of ECO mode, click icon of “TO ECO”, after a while, system operating under ECO mode.  3.3 Operation for Power off 3.3.1 Power off under line mode The UPS is working under main power mode currently.  Click icon of On/Off in main interface to pop the On/Off interface. Click icon of “SHUT” to shut down  the UPS, and the charger will be off automatically at the same time.    Figure 3.17 Interface of Power off under Main Power  - 26 -...
  • Page 31: Operation For Emergency Power Off

    10-120KVA (3/3) UPS user manual   3.3.2 Power off under battery mode The UPS is working under battery mode currently.  Click icon of On/Off in main interface to pop the On/Off interface. Click icon of “SHUT” to shut down  the UPS.    3.3.3 Power off under bypass mode The UPS is working under bypass mode currently.  Click  icon  of  On/Off  in  main  interface  to  pop  the  On/Off  interface.  Click  icon  of  “BYP  OFF”  to  shut  down the UPS, and the charger will be off automatically at the same time. ...
  • Page 32: Operation For Maintenance Bypass

    10-120KVA (3/3) UPS user manual   3.5 Operation for Maintenance Bypass 3.5.1 Start of maintenance bypass 1. Select option of On/Off in LCD main interface, select icon of “TO BYP” in On/Off interface, and  confirm the UPS is working under bypass mode in LCD screen.      Figure 3.19 Bypass Mode    2. Open the cover of maintenance bypass breaker, close the maintenance bypass breaker, cut off the  output and battery breakers, and then the UPS enters into maintenance bypass mode. Its energy  flow is shown in figure 3.20, and then cut off the input breakers and bypass breaker.        Figure 3.20 Maintenance Bypass Mode    - 28 -...
  • Page 33: Enquiry Operation

    10-120KVA (3/3) UPS user manual 3.5.2 Exit of maintenance bypass mode 1. Close the input breaker and bypass breaker, the power module builds working power and switches  to bypass mode by hand operation, charger starts automatically.  2. Close the output breaker and battery breaker, cut off maintenance bypass breaker, put back the  baffle of maintenance bypass breaker back, and then the warning “Maint CB Cover Open” in LCD  screen disappears.    3.  Select  option  of  On/Off  in  LCD  main  interface,  select  “TO  INV”  in  On/Off  interface,  the  power  module will start the inverter after 30s, and then UPS will be working under main power mode.    3.6 Enquiry Operation Enquiry operation is a parameter to inquiry the working condition and setting of UPS.  3.6.1 Enquiry of input information Click “I/P” in main interface to pop the input parameter interface. The input parameter interface will ...
  • Page 34 10-120KVA (3/3) UPS user manual     Figure 3.22 Output Parameter Display  3.6.3 Enquiry of information of charger Click icon of charger in main interface to inquiry information of charger.  Information  of  charger  includes:  state  of  charger  and  parameter  of  charger  (can  be  switched  by  button of page up or page down).  The  interface  of  charger  state  will  display:  working  mode  of  charger,  charger  temperature,  positive/negative charger voltage, and positive/negative charger current. ...
  • Page 35 10-120KVA (3/3) UPS user manual     Figure 3.24 Interface of Charger Parameter  3.6.4 Enquiry of battery information Click icon of battery in main interface to enter into interface of battery parameter. It will display:  pieces and groups of battery, connection state, battery voltage, battery temperature, battery remain  time, battery remain capability and time of next self‐test.        Figure 3.25 Display of Interface of Battery parameter    3.6.5 Enquiry of current warn Click icon of “WARN” in main interface to pop current warning information. It can switch the warn  interface between UPS and charger by button of page up and page down.          - 31 -...
  • Page 36 10-120KVA (3/3) UPS user manual     Figure 3.26 Warn Interface  3.6.6 Enquiry of history Click icon of “HISTORY” in main interface to pop the interface of UPS history. It contains: “FAULT”,  “WARNING”, “STATUS”, and “OPERATE”.        Figure 3.27 Interface of History      1. FAULT:  “FAULT” records all faults occurred during operation of UPS.                  - 32 -...
  • Page 37 10-120KVA (3/3) UPS user manual     Figure 3.28 Interface of Fault    2. WARNING  “WARNING” records reasons of all warns when warns occurred for UPS.      Figure 3.29 Interface of Warning    FAULT and WARNING can record 2100 pieces at most and the earliest records will be replaced by new  record if number of all records exceeds 2100. All records are listed by inverted order of time.      3. OPERATE  “OPERATE” records all operations of UPS taken by user.            - 33 -...
  • Page 38 10-120KVA (3/3) UPS user manual     Figure 3.30 Display Chart of Interface of Operate    4. STATUS  “STATUS” records all working mode of UPS under different periods.      Figure 3.31 Display Chart of Interface of Status    OPERATE and STATUS can save 768 pieces at most and the earliest records will be replaced by new  record if number of all records exceeds 768. All records are listed by inverted order of time.      5. Enquiry record  Click icon of enquiry record in four interfaces above to pop the interfaces of record enquiry. Enter the  record time, it can inquiry records before and after the entered time.          - 34 -...
  • Page 39 10-120KVA (3/3) UPS user manual   3.6.7 Enquiry of current information Click icon of setting in main interface to pop the setting interface.        Figure 3.32 Setting Interface    Click icon of “SET INFO” to pop the current setting interface of UPS. Information contained in the  interface includes: cabinet No., status of converter mode, status of charger, status of auto start, test  mode, and contact telephone.        Figure 3.33 Display of Current Setting Interface    Click the page up or page down to pop the warranty interface which can inquire the warranty period  of components such as battery to remind the user to replace.            - 35 -...
  • Page 40: Operations For User Configuration

    10-120KVA (3/3) UPS user manual     Figure 3.34 Display of Warranty Interface  3.6.8 Enquiry of system information Click icon of setting in main interface to pop the setting interface. Click icon of “SYS INFO” to pop the  system information of the machine, including: sequence number, model, software version and  telephone.      Figure 3.35 Interface of System Information  3.7 Operations for User Configuration Warn: operation for user configuration is used for setting UPS parameters, and non professional  personal shall not take any setting operations.    Click icon of “USER CONF” in setting interface to pop the password input interface of user set.      - 36 -...
  • Page 41 10-120KVA (3/3) UPS user manual     Figure 3.36 Password Input Interface    Enter correct password (initial password is 666666) to pop the user configuration interface, including:  LANGUAGE, TIME, SELFTEST, PROTOCOL, PASSWORD, CALIB, and PHONE.      Figure 3.37 User Configuration Interface  3.7.1 Language set LCD display screen can provide the language of English.                    - 37 -...
  • Page 42 10-120KVA (3/3) UPS user manual     Figure 3.38 Language Set Interface  3.7.2 Time set Click icon of “TIME SET” in user set interface to enter into time set interface. It can change the  displayed time of UPS by entering current time.      Figure 3.39 Time Set Interface  3.7.3 Auto self-test set Click icon of “SELFTEST” in user set interface to pop the self‐test set interface.    Its display is shown in figure 3.40, auto self‐test interface includes: on and off of self‐test, run cycle of  self‐test, and duration of self‐test for every time.            - 38 -...
  • Page 43 10-120KVA (3/3) UPS user manual     Figure 3.40 Self‐test Set    Select proper self‐test duration and time by demand.  3.7.4 Protocol Set Click icon of “PROTOCOL” in user set interface to pop the protocol set interface.        Figure 3.41 Protocol Set Interface    There are two optional communication ports, “RS232” and “RS485”.  Click icon of “RS232”, and then communication port set interface will be popped.                - 39 -...
  • Page 44 10-120KVA (3/3) UPS user manual     Figure 3.42 Communication Port Set Interface    Port property shall be set by demand.  3.7.5 Password set Click icon of “PASSWORD” in user set interface to pop the password set interface.        Figure 3.43 Password Set Interface    The password is required when entering user configuration interface.    Enter old password and new password according to requirement to change the password of entering  User Configuration Interface (initial password is 666666). If you forgot your password, please contact  customer service.        - 40 -...
  • Page 45 10-120KVA (3/3) UPS user manual   3.7.6 Calibrate If the touch click is not so sensible, it can recover the sensitivity of touch screen through “CALIBRATE”.  Click  icon  of  “CALIBRATE”  in  set  interface  to  pop  the  calibrate  interface  of  touch  screen.  Click  specified site according to order, and then the sensitivity of touch screen will be recovered.        Figure 3.44 Calibrate Interface of Touch Screen    Note: object used to click the touch screen shall not be too sharp when calibrating, otherwise it will  damage the screen.    3.7.7 Telephone set It can change the contact telephone of agency by “TEL SET”.      Figure 3.45 Telephone set interface ...
  • Page 46 10-120KVA (3/3) UPS user manual   3.7.8 Mute off Click icon of battery self‐test and mute off in main interface to pop interface of battery self‐test and  mute off. Click “MUT OFF” in self‐test interface to mute the warning sound.        Figure 3.46 Interface of Self‐test and Mute off  3.7.9 Advanced setting Note: It is forbidden to enter the advanced setting interface without the allowance of the customer  service, otherwise great damage may occur.  Click the icon of “ADVANCED” in setting interface to pop the password input interface.      Figure 3.47 Password input interface    Enter correct password (initial password is 19841219) to pop the advanced setting interface.        - 42 -...
  • Page 47 10-120KVA (3/3) UPS user manual     Figure 3.48 Advanced setting interface    Advanced setting include “MODEL” “CHG CONF” “SYS CONF” “WARRANTY” “OPEN SET” “OTHERSET”  “COM DATA” and “OUT COEF”.  1. MODEL  Click the icon of “MODEL” to pop the model setting interface.                                  Figure 3.49 Advanced setting interface  RUN MODE: to choose the working mode user needed, single or parallel.  CAB NUM: if the user want to build a parallel system, the cabinets should be set the number  from 1 to 6, if the user just want a single UPS, the number should be set as 1.  OUT  TYPE:  we can  set the  output type  as  3/3(  3 phase input  and  3 phase output)  or  3/1  (3  phase input and 1 phase output). ...
  • Page 48 10-120KVA (3/3) UPS user manual We can configure the charger parameter and the battery parameter in this interface.      Figure 3.50 Charger configure interface    CHGSTATE:    if this option is set as open, the charger is allowed to start, otherwise the  charger can not been started.  TEMP CMP: to adjust the charging current by battery temperature.  BAT NUM: for standard machine, the number should be set as 16, for long‐backup machine,  the number is count to the mount of batteries user offered.  BATGROUP: this parameter refer to the number of battery groups.  BAT CAPACITY: it should match the battery capacity user offered.  CHG RATE: charging speed of the charger.  CHG CURR: charger current= charger rate* battery groups* battery capacity.  3. SYS CONF  Click the icon of  “SYS CONF”  to pop the system configure interface.      Figure 3.51 System configure  - 44 -...
  • Page 49 10-120KVA (3/3) UPS user manual   CONVERT: to start the frequency converter mode or not.    AUTO START: when it is open, the UPS will start automatically when the main power resupply  after the UPS shut down in battery mode.  OUT FREQ: to set the output frequency, it can be set as 50Hz or 60Hz.  OUT VOLT: to set the output voltage.  BYP VOLT: to set the range of bypass voltage, if the bypass power  voltage is beyond it, UPS  will be forbidden to start bypass mode.  BYP FREQ: to set the range of bypass frequency, if the bypass power frequency is beyond it,  UPS will be forbidden to start bypass mode.  4. WARRANTY  Click the icon of  “WARRANTY”  to pop the warranty interface.        Figure 3.52 Warranty interface      Then input the time when the battery    is replaced and the life of the battery , the UPS will warn  you if the battery is up to the warranty date.  When starting the UPS first time, update the install time of the battery and capacitance.  5. OPEN SET  Click the icon of “OPEN SET” to pop the open set interface.               ...
  • Page 50 10-120KVA (3/3) UPS user manual     Figure 3.53 Open set interface    OPEN PWD: if it is open, the user need input the password when starting the UPS next time,  after the UPS is started, this set will turn to close automatically.  LOCK PWD: if it is open, no password is needed to interview any interface.  BYP ENA: if it is open, bypass mode cannot be started.  6. OTHERSET  Click the icon of “OTHERSET” to pop the other set interface.      Figure 3.54 Other set interface    1) DEFAULT: restore the factory setting.  2) FIRMWARE: to update the Software.  3) CLR LOG: clear history records.  7. COM DATA  Click the icon of “COM DATA” to pop the com data interface.    - 46 -...
  • Page 51 10-120KVA (3/3) UPS user manual     Figure 3.55 Com data interface    The second row represent the working mode of the UPS, “1” means standby mode,“2” means  bypass mode, “3” means main power mode, “4” means battery mode.  The forth row is the BUS voltage of the BUS line, when the UPS works normally, the BUS line should  be 360V.  The fifth row is the inverter voltage of the UPS.  The sixth row is the software version of the power module  8. OUT CONF  Click the icon of “OUT CONF” to pop the output parameter interface.      Figure3. 56 Parameter set interface    Click the module needed to be adjusted to pop the parameter interface        - 47 -...
  • Page 52 10-120KVA (3/3) UPS user manual                                               Figure3. 57    INV Volt set and OUT Volt set interface    INV VOLT SET: to adjust the output voltage.  OUT VOLT SET: to adjust the digital which is displayed in the output interface(chapter 3.6.2) of  the LCD screen.             ...
  • Page 53: Chapter 4: Installation And Operation Of Paralleled Machine

    10-120KVA (3/3) UPS user manual   Chapter 4: Installation and Operation of Paralleled Machine The  machine  supports  paralleled  machine  extended  operation  with  maximum  extended  number  of  machines is 6 and maximum extended power is 360KVA.  4.1 Installation of Paralleled System 1. Connect the main power input, bypass input, output and battery of UPS which is ready for parallel  according to figure 4.1, and then connect to the main power, bypass, battery and load.        Figure 4.1 Connection Chart of Paralleled Machines    2. As shown in figure 4.2, connect the paralleled ports of communication ports for UPS ready for  parallel with parallel wire, and it can parallel 6 machines at most. ...
  • Page 54: On/Off Of Paralleled Machines

    10-120KVA (3/3) UPS user manual   2. It needs to detect whether the wiring is correct or not after parallel of output, bypass, battery  and load is finished.    3. Length difference of all the single machine output lines must be less than 10m.  4. The paralleled UPS is set by sales and checked OK before deliver to customer.  4.2 On/Off of Paralleled Machines 4.2.1 Parallel on/off of paralleled machines Close  all  input  breakers,  bypass  breakers,  battery  breakers  and  output  breakers  of  paralleled  machines, and its main interface is shown as figure 4.3:    Figure 4.3 Main Interface of Paralleled Machines ...
  • Page 55 10-120KVA (3/3) UPS user manual   Click “SYSTEM” in On/Off interface to take on/off operation of paralleled machines (same with on/off  operation of single machine in Chapter 3).        Figure 4.5 On/Off Interface    Note: all breakers, other than maintenance bypass breaker, shall be closed when power on or  power off the paralleled machines.    4.2.2 Single on/off of paralleled machines Click icon of On/Off to pop the On/Off interface, as shown below:    Figure 4.6 On/Off Interface of Paralleled Machines    Select “UPS‐n” (n≤6) for on/off operation to enter into the On/Off interface of UPS.    Take on/off operation (same with on/off operation of single machine in Chapter 3).      - 51 -...
  • Page 56: Enquire Operation Of Paralleled System

    10-120KVA (3/3) UPS user manual   4.3 Enquire Operation of Paralleled System 4.3.1 Information enquire of single machine for paralleled system Click “UPS ‐n” (n≤6) in main interface to enter into the subordinate interface of paralleled system.        Figure 4.7 Information Interface of Single Machine    This interface can enquire the information on input and output battery and charger of this single  machine.    4.3.2 Information enquire of whole unit for paralleled system Click related icon in main interface to take the enquire operation (same with that in Chapter 3).  Note:The warning and fault system of paralleled system can only record warning and fault ...
  • Page 57: Chapter 5: Ups Repairing And Maintenance

    10-120KVA (3/3) UPS user manual   Chapter 5: UPS Repairing and Maintenance   5.1 UPS Repairing and Maintenance 5.1.1 Power and features of load shall be considered when using UPS Rated output power of UPS is the key parameter to express how much power load the product can  drive,  it  changes  along  with  alteration  of  load  power  factor,  for  example,  and  1  KVA  UPS  maybe  cannot drive 1 KVA load. UPS shall not be under full load condition in order to prolong working life of ...
  • Page 58 10-120KVA (3/3) UPS user manual   Discharging  requirement  of battery:  in  general, the UPS  is equipped with  protection  measures  for discharging of battery, but the battery will recover to certain voltage after it is discharged so  that  the  protection  is  powered  off,  and  it  is  not  allowed  to  restart  the  machine,  otherwise,  it  may cause over‐discharging of battery. The battery shall be used normally after it is recharged.    For new bought UPS (or for UPS stored for a long time), it only can be operated after the battery  is charged. Otherwise, the standby time will not be ensured.    For UPS without power off for a long time, its battery shall be discharged for every 3~6 months  and then recharged again. It can prolong the working life of battery by this way.    For UPS stored for a long time, it shall be started and charged for every 3~6 months, otherwise, ...
  • Page 59: Troubleshooting

    10-120KVA (3/3) UPS user manual   5.2 Troubleshooting Faults  of  UPS  can  be  known  by  inquiring  history  records  of  UPS,  and  common  problems  during  operation of UPS can be solved by contrasting table 5.1.    Table 5.1 Fault/Warn Removal  Problem Type  Fault/Warning  Solution  Battery Overcharged  Power  off  the  charger  and  contact  customer  service personal.    Power ...
  • Page 60 10-120KVA (3/3) UPS user manual T phase Out Short    RS phase Out Short      ST phase Out Short    TR phase Out Short      R Reactive Abnormal    S Reactive Abnormal    Contact the customer service personal  T Reactive Abnormal    1. Power off secondary load    2.  Reallocate  the  load  so  that  outputs  of  three  Overload Fail    phases are balance.    3. Cut off UPS input breaker for 30s, then start  again.  Ensure  environmental  temperature  is  within  Overtemp Fault ...
  • Page 61 10-120KVA (3/3) UPS user manual Input CB Open  Check whether the input breaker is closed or not.  Check  whether  the  output  breaker  is  closed  or  Output CB Open  not. Output Overvolt  Please contact the customer service personal.  Unnecessary  for  treatment  under  maintenance  Maint CB Cover Open  bypass mode  1. Unnecessary for treatment under maintenance  bypass mode.    Maint CB Cover Open  2. Check whether the screw of maintenance cover  is fastened or not under other operation mode.  1.  Check  whether  the  battery  and  charger  are  normal or not. ...
  • Page 62: Maintenance Assurance

    Service commitment of our company is: warranted for three years and maintained for all life.    The following cases are not included in warranty range:    1. Artificial fault;  2. Out of warranty period;  3. Product whose production serial number is changed or lost;    4. Damage or loss caused by force majeure and external causes;    5. Dismantle or change the UPS without authority;    6. Breach operation/application stipulations of UPS;  7. The battery is discharged deeply or damaged by manual.  5.4 Technical Specifications Table 5.2 Technical Specifications  Model    9010  9015  9020  9030  9040  9060  9080  90100  90120 Nominal  100K  120K  10KVA  15KVA  20KVA...
  • Page 63 10-120KVA (3/3) UPS user manual Output  Output power  0.9  factor  Rated voltage  380Vac/400Vac/415Vac  Stabilized  voltage  ±1%  precision  Dynamic  voltage  ±5% (0‐100% load fluctuation)  transient range  Total harmonic  ≤1 % (resistive load);  distortion  ≤3% (nonlinear load)  (THDV)  Output voltage  direct current  ≤100mv  component  Output current  3:1  peak factor  Output  Main power mode: synchronous with bypass;    frequency  Battery mode: 50Hz/60Hz  Frequency  ≤1 Hz/s  tracking rate  Phase lock  1° ...
  • Page 64 10-120KVA (3/3) UPS user manual Maximum  paralleled  6  machines    Working  temperature  0~40℃  range  Working  elevation  <1500 m (Shall be reduced using if exceeding this height)  height  Storage  ‐25 ~55℃  temperature  Noise in 1m  <60dB  from ground  Safety    EN62040‐1‐1 Electrostatic  IEC 61000‐4‐2    Level 3  discharge  Sustained  electromagneti IEC 61000‐4‐3    Level 3  c sensitivity  Voltage flash  IEC 61000‐4‐4    Level 3  compatibility ...
  • Page 65: Appendix 1: Lamp Signal Reference List

    10-120KVA (3/3) UPS user manual Appendix 1: Lamp Signal Reference List Mode    Fault/Warning  Status of LED  Status of buzzer    Phase  sequence  is  error,  and  The fault light twinkles  Buzz  once  2s  and  last    main  power  bypass  is  once 2s and lasts for  for 1/4s  Standby mode  abnormal  1/4s  The fault light twinkles  Buzz  once  2s  and  last  Disconnection of battery ...
  • Page 66 10-120KVA (3/3) UPS user manual   Some module is under fault  Fault  light  is  on  all  the  Buzz all the time    mode  time    Battery  light  twinkles  Buzz  once  1s  and  last  Low‐voltage of battery  Battery self‐test  once 1s    for 1/4s  Buzz  once  2s  and  last  Overload    All is off  for 1/4s  Twinkle in turn for every ...
  • Page 67: Appendix 2: Port Of Communication Interface

    10-120KVA (3/3) UPS user manual   Appendix 2: Port of Communication Interface There are several communication ports for 10‐120KVA system, as shown in Figure 1:        Figure 1 Chart of 10‐120KVA Communication Port    1. SNMP Network Card Port (optional fitting)  The LAN port communication needs to be set as:  Connect the computer and system with network cable. It can use twisted pair network cable to  connect the computer directly or use direct network cable to connect the computer through  switchboard.      2. RS232 Port  Its maximum transmission range is 50m when the baud rate is 9600.  RS232 interface definition (others are not connected):    Stitch    2  3  5  Definition  RXD  TXD  GND    3. RS485 Port  Its maximum transmission range is 500m when the baud rate is 9600. ...
  • Page 68 10-120KVA (3/3) UPS user manual   Stitch    1、2  4、5  Definition  B    Double‐pin port:  Stitch    1  2  Definition  A  B    4. USB Port  The USB port is special port for UPSmart2000I monitoring software.        5. Inspection Port of Battery Temperature  The charger module can collect battery temperature at any time to provide temperature  compensation through inspection port of battery temperature.      6. Passive Input Dry Contact    10‐120KVA (3/3) series UPS is equipped 1 groups of signal input which has three PIN. And from left  to right which are Number PIN 1 to Number PIN 3. Number PIN 3 is set for checking the status of the  battery breaker. Number PIN 2 is set for remote emergency power off. Number PIN 1 is ground. PIN  2 is normally closed and connected with PIN1. PIN 3 is normally open.    PIN3,PIN1shut Mains power for generator Generator PIN3,PIN1open...
  • Page 69 10-120KVA (3/3) UPS user manual User  can  select  to  connect  the  normally  open  terminal  or  normally  closed  terminal  according  to  actual demand.        Ntifier    Meaning  Inverter output LINE LOSS  Main power is abnormal OVER LOAD  Overload of output BYPASS  Bypass output FAULT  System fault BAT.LOW  Warning of battery low‐voltage ALARM  System alarm  ...
  • Page 70: Appendix 3: Dial Switch Set Of Module And Charger

    10-120KVA (3/3) UPS user manual   Appendix 3: Dial Switch Set of Module and Charger 1. Dial Set of Address for Module Input Power Connector  Depending on the power segment, the DIP switch in the input power connector can be set as follows:      Dial switch (0 means OFF and 1 means ON)  NO.  1  2  3  4  5  10KVA  1  0  0  0  0  15KVA  1  0  0  0  0  20KVA  1 ...
  • Page 71 10-120KVA (3/3) UPS user manual     Figure 2 Dial Set of Address    2. Dial Set of Hardware Protection for Charger  Set the set dial switch of battery pieces of communication port interface so that it can be the same  with actual battery pieces to protect the battery.  Dial switch is protected by a cover, so it shall take away the cover before adjust the battery piece  of dial switch.  Dial switch sets for all battery pieces are:      Dial switch (0 means OFF and 1 means ON)    1  2  3  4  20 pieces of  0  0  0  0  batteries  19 pieces of  1  0  0  0  batteries  18 pieces of  1  1  0  0 ...