Maximum number of ZONE time channel...20 Maximum number of I-Bus-modules ...21 Limits of 5V supply ...21 Control terminal limits (FC/FT)...21 Limitation of visible texts on a FC700A...21 Limitation of visible texts on a FT700A ...21 Gateway limits (FG) ...22 Specify hardware required...23 Control unit FC700A ...24...
Page 4
Control modules...40 Application of control modules ...40 Overview of the available modules with control outputs ...40 Means of linking ...40 Control outputs station type FC700A ...41 Control outputs remote station type FT700A ...41 Modules...41 CPU-overlapping controls ...42 Mimic Display panel outputs ...43 Modules...43...
Page 5
Determine the alarm organization...57 Organization of system operation ...57 Commissioning ...58 Parameterization, Flash programming ...59 Functions...59 Modules...59 FC700A modules in alphabetical order ...60 Spare parts ...62 Configuration sheets ...63 List of configuration sheets ...63 Control unit FC700A ...64 Auxiliary power supply...65 Control terminal FT700A ...66...
About this document Purpose This document describes the project planning of the hardware modules of the con- trol unit FC700A. The consistent adherence to these instructions is a prerequisite for a safe application. Scope This document contains information of all FC700A components, including part numbers for ordering.
Page 7
-> Document identification Place Title page Last page Modification index Version 007836_a_en_-- Siemens Building Technologies Fire & Security Products Additional information Notes Definitions of designations Details see page ..., chapter or document ... Configuration sheets to fill out Signification –...
The symbols listed below indicate the nature and origin of the danger. Signal word Signal word Example for a danger warning DANGER External voltage Siemens Building Technologies Fire & Security Products General danger Electrical voltage Disconnect the module from power supply. 007836_a_en_--.doc...
In the case of extinguishing systems, always use the ”General installation in- structions” as a guideline. This guideline is available on request. Siemens Building Technologies Fire & Security Products Any work on electrical installations may only be carried out by qualified electri- cians or instructed persons working under the guidance and supervision of a qualified electrician, in accordance with the electro technical regulations.
Page 10
Batteries require environmentally safe disposal. They must be handed in at the local collecting points. Please take into account that the extinguishing agent cylinders are pressurized and must be exchanged in compliance with the local safety regulations. Siemens Building Technologies Fire & Security Products 007836_a_en_--.doc 03.2004...
Main features Fire detection system for modular configuration Up to 1000 detectors per FC700A possible For the processing of addressable and conventional detectors Logical and physical structure totally separated Control console as main CPU Interfaces for VdS peripheral equipment, printer, host systems...
Technical data FC700A Technical data FC700A Operating voltage Power consumption Battery operation in the event of mains failure - Standard operating period - Optional Environmental conditions Temperature during Humidity IP protection category (EN 60529 / IEC 529) - Control unit...
Logical and physical structure In the FC700A fire detection system, the logical structure is completely separated from the physical structure. This enables the greatest possible flexibility. Display and control terminal are based on the geographical and organizational aspects and are independent of the actual hardware installation of the detector network.
Bus systems Bus systems In the FC700A fire detection system there are 5 communication levels: I-Bus Internal data bus between individual modules in the control unit (line modules, control modules etc.) C-Bus Local data bus between control unit(s), control terminal(s) and Gateway(s) SynoLOOP and SynoLINE600 Local detector bus;...
The driver resistors specify the current on the C-Bus. In order that the signal on the C-Bus always has the same amplitude (1.35Vpp), the following correlation is valid: Rd = Ri x 3,65 Siemens Building Technologies Fire & Security Products I-Bus...
(default 110Ω). In the choice of other cables the above rules apply (the Ri are in this case the external end-of-line resistors). For further information, see document 007831 Siemens Building Technologies Fire & Security Products Standard Lifeline...
Type of station Module FC700A B3Q700 FT700A B3Q700 FG700A E3H020 Siemens Building Technologies Fire & Security Products FT700A (max.15) C-Bus Network - max. 16 Stations - 3 different types of stations - loop line max. 1400m with G51 ø 0.8mm...
Operating platform requirements in detail see document 007895 – For details see document ……. (not available yet) – FC/FT C-BUS FC/FT Siemens Building Technologies Fire & Security Products max. length of line dependent on type of modem E3I020 Modem Dedicated line...
Control terminals (FT) can be freely allocated to AREAS as required – Visibilities on gateways (FG) shall be set per station only, not per AREA! – Siemens Building Technologies Fire & Security Products All AREAS control terminal C-Bus stations 007836_a_en_--.doc AREA 03.2004...
Limitations of C-Bus participants Limitations of C-Bus participants This chapter describes the quantitative limits of the FC700A station. The selection of the station type depends on the requirements. The following vari- ants are available: Station type Modules FC700A B3Q700 FT700A...
8.2.2 Limitation of visible texts on a FT700A The number of texts of other stations (FC700A) that can be displayed on one con- trol terminal is limited by 14'000 texts. To evaluate how many control panels FC700A can be displayed to one FT700A,...
Gateway limits (FG) Via one gateway a maximum of 8 C-Bus stations (FC700A) can be addressed. If more than 8 C-Bus stations (FC700A) are present, they must be split up on two gateways. Also for special applications, more than two gateways can be configured.
2. Specify number and type of fire control installations 3. Specify number of operating units 4. Specify Accessories required 5. Specify emergency power supply battery capacity 6. Provide configuration sheet/sheets (see chapter 29) Siemens Building Technologies Fire & Security Products Dependent on: Detector series –...
Control unit FC700A Control unit FC700A 10.1 Configuration Pre-assembled compact control unit E3G070 and E3M111 are pre-wired on terminal block 'X1' Place for additional terminal block 'X2', modules, relay and batteries Batteries as required either 2x 12V/15Ah or 2x12V/27Ah Control terminal built into front terminal (also serves as main CPU)
Use flat cable F20A020 12.2.3 Place of the E3I040 LON interface (FT) H28T110 B3Q700 Siemens Building Technologies Fire & Security Products RS232 module E3I020 is mounted at the rear of the control terminal ‘FT’ by means of accessories Z1B020 B3Q700 ->...
Mounting accessory for E3I040 Z3I481 491185 Cable set for control terminal FT700A in H28G200 Cabinets H23/H26/H28 for details referring cabinets -> see chapter 13 Siemens Building Technologies Fire & Security Products Control terminal B3Q700 (FC/FT) Notes Operating unit For control terminal For control unit Incl.
Page 32
Colour Pantone 421 grey Colour Pantone 421 grey Protection category IP40 Protection category IP40 Front can not be pivoted Front can not be pivoted Siemens Building Technologies Fire & Security Products H28G200 Housing with lock (DOM) Dimensions 520x300x70mm Material Steel sheet...
532879 Recess box to B3Q580/590/595 H23Z230 532882 Cover frame to B3Q580/590/595/B3R051 UPR28 430434 Recess box Siemens Building Technologies Fire & Security Products H23U220 H23G230 H23Z230 UPR28 H28G200 Details of the cabinets -> see document 007827 Range of cabinets H23 / H26 / H28...
378198 Hinge 19"/6HE G2A130 475088 Adapter plate 19"/6HE G2A140 484228 Adapter plate 19"/6HE Siemens Building Technologies Fire & Security Products 19” G2A130 Z2G030 Notes Consisting of hinge and spacer profile For control terminal B3Q700 (FT) For parallel indicator panel B3R051 007836_a_en_--.doc...
460268 Line module SynoLINE600/-Ex Z3I1050 A5Q00004717 Connection cable 19 conductors Z1K030 484231 Terminal block with p.c.b. Chassis Siemens Building Technologies Fire & Security Products FC700A E3M111 SynoLOOP 4 x 128 In each device Separate supply output 24V for input/output modules...
Some detectors have different loading factors, to evaluate how many special de- tectors can be connected to one addressable line see chapter 16.3 Control output for 1 external response indicator in each detector base Room 102 Siemens Building Technologies Fire & Security Products AI340 HI32xA...
DM1103 E3M080 HI62xC OP620C Some detectors have different loading factors, to evaluate how many special de- tectors can be connected to one collective line see chapter 16.2. Siemens Building Technologies Fire & Security Products DLO1191 DF1191/92 HI62xC SynoLINE600 DLR11 . .
Input module Output module In-/output module In-/output module Do not install lines longer than 2000m Siemens Building Technologies Fire & Security Products Collective line factor (SynoLINE600) Load factor for collective / conventional elements (SynoLINE600/300) addressable line factor (SynoLOOP) Load factor for addressable elements (SynoLOOP)
E3M111 DC1192 24VDC Max. Resistance 150Ω (max. R) Max. Capacitance 300nF (max. C) -> max. 600nF with max. 50Ω line resistance Siemens Building Technologies Fire & Security Products Connection factors, line resistances and capacitances max. C max. R DC1192...
- switch on/off Visible statuses: - activate/de - active -activate - switched off - executed ('Acknowledgem.') - fault Siemens Building Technologies Fire & Security Products Monitored con- Driver outputs trol lines Programmable For alarm devices 1) 2) Can also be used as control inputs (e.g. 'acknowledgement')
17.3 Control outputs station type FC700A Basic equipment B3Q700 E3G070 Driver 1...7 Z3B171 FÜ 250VAC/10A Fire control installations Up to 2 Z3I1050 (with additional terminal block) can be used other- wise Z1K030 must be used. 17.4 Control outputs remote station type FT700A...
Control modules 17.6 CPU-overlapping controls all-AREA = AREA initiating data point control ZONE/ELEMENT control device Limitation: see chapter 8 Siemens Building Technologies Fire & Security Products single-AREA C-Bus must be within the same Gateway 007836_a_en_--.doc 03.2004...
18.2 LON-Bus as stub line B3Q700 Z3I1050 Z1K030 E3I040 Details K3R072 see page 43 Details B3R051 see page 29 Siemens Building Technologies Fire & Security Products B3Q580 Text display terminal B3Q590/595 = Text control terminal K3I050 LON/Mimic Display converter K3I110...
Output local buzzer Output LED 'operation' 18.5 LON I/O card K3I110 Input/output card – – Dimensions: 122 x 220 x 14mm Siemens Building Technologies Fire & Security Products I-Bus max. length of LON-Bus 500m 24VDC K3I110 K3I050 Data bus 24VDC...
Per C-Bus network are several gateway possible, see chapter 8 Install preferably in the fire detection system control unit cabinet 19.2 Application Fire detection control unit I-BUS Line- modules Module chassis view modules Siemens Building Technologies Fire & Security Products C-BUS I-BUS module Line- Control- Detector C-Bus 24VDC...
484231 Terminal block with p.c.b. Holder Note: The E3H020 is factory side equipped with 4 RAMs (4x 512Kx8Bit) details see document 007831 Siemens Building Technologies Fire & Security Products Notes Requires 2 module spaces Software for ISO1745 Protocol for E3H020 For direct connection 007836_a_en_--.doc...
Single channel (alarm + fault) or multi channel (several alarm channels) – Disabling/enabling via B3Q700 (FC/FT) – Interfacing Via output contacts and special control in-/outputs of the E3G070 – Siemens Building Technologies Fire & Security Products Interfacing via E3G070 I-Bus B3Q700 (CPU) E3G070 alarm...
Power supply Power supply 22.1 Concept The power supply for the FC700A fire detection system consists of: Converter Battery charging unit (by means of E3C011) Batteries (lead) 22.2 Special functions Automatic battery load test – Battery charging characteristic can be programmed according to make –...
Note: A 2nd supply output is only necessary for operating units, which must com- ply with EN54 (at least 1 operating unit per system) 22.8 Power supply for remote transmission equipment and acces- sories Siemens Building Technologies Fire & Security Products + / - /Earth Output 1 Output 2...
Without remote transmission equipment – Only quiescent current taken into account – Siemens Building Technologies Fire & Security Products Discharge over 12-hour period: Allow a safety factor for ageing (Total quiescent current y 1.25 or battery capacity y 0.8) >...
15mA without external 24V load K3I050 15mA K3I110 24mA max. 184mA all relay activated incl. service LED Siemens Building Technologies Fire & Security Products Additional current with alarm condition + 230mA + 160mA + 167mA + 2mA + 11mA per activated relay + 23mA per activated control line, without external load + 34mA without external load (horns etc.)
The response of the operating personnel is monitored by two independent time circuits (V1 and V2) monitored The CAC is an integrated part of the FC700A control unit. The required parame- ters can be entered via the user functions 24.2 Principle of the Cerberus alarm concept During the "Day"...
24.3 Determine the alarm organization The FC700A fire detection system has up to 64 programmable organization lev- – els (AREAS) A number of "Alarm variants" are possible (can be selected per ZONE) – The time countdown memories "V1" and "V2" must be specified individually –...
Commissioning Commissioning The FC700A fire detection system is designed for rational systems engineering. Connection work at the control unit can be due by non-specialist personnel (e.g. outside electricians). However, co-ordinated supervision is still essential. Specially trained personnel with a maintenance PC are required for commissioning (service engineer).
PC by means of the software tool set 'SWE700A'. Online-Help text Flash programming is only relevant if B3Q700 is used as replacement for FC700A New software is programmed by means of the 'Flash Tool' software. For the modules B3Q700 the application software is now loaded into the Flash ROM via the maintenance PC by means of the 'Flash Tool' software.
– B3Q580/590/595, B3R051 – K3I110, K3I050, K3R072, K3G060 etc. – Siemens Building Technologies Fire & Security Products Configuration with control terminal B3Q700 as main CPU (control unit) Details see page 64 Details see page 65 Configuration for control terminal B3Q700 Details see page 66 Configuration display &...
E3I040 module Terminalblock Details see chapter 10 Siemens Building Technologies Fire & Security Products SynoLOOP for 30V FC700A-1 Control unit FC700A including: E3C011, E3G070, E3M111, 40 Terminals, B2F020 pre-wired SynoLINE600/-Ex for 250V Control unit FC700A-1 A5Q00004734 Inscription sets FCA…...
Auxiliary power supply H38G310 Mains terminals AX1201 AX1210 AX1201 AX1210 View A Details see chapter 11 Siemens Building Technologies Fire & Security Products Auxiliary power supply Housing H38G310 484930 Power supply B2F020 470588 E3C011 505479 Cable set Z3I470 484341 Batteries...