No.
Name/Value
80.61
Q value Q2
80.62
Q value Q3
80.63
Q value Q4
80.64
Q value Q5
81
81 Sensor settings
81.01
Actual inlet
pressure
0.00...32767.00 bar
81.02
Actual outlet
pressure
0.00...32767.00 bar
81.10
Inlet pressure
source
Not selected
AI1 scaled
AI2 scaled
Freq in scaled
AI1 percent
AI2 percent
Feedback storage
Other [bit]
81.11
Outlet pressure
source
Not selected
AI1 scaled
AI2 scaled
Freq in scaled
AI1 percent
AI2 percent
Feedback storage
Other [bit]
81.12
Sensors height
difference
0.00...32767.00 m
81.20
Pressure unit
bar
Description
Defines the flow rate at point 2 on the PQ performance curve.
See parameter
80.60 Q value Q1
Defines the flow rate at point 3 on the PQ performance curve.
See parameter
80.60 Q value Q1
Defines the flow rate at point 4 on the PQ performance curve.
See parameter
80.60 Q value Q1
Defines the flow rate at point 5 on the PQ performance curve.
See parameter
80.60 Q value Q1
Defines the sensor settings for inlet and outlet pressure
protection function.
Shows the actual inlet pressure.
Note: By default the parameter unit will be bar. However, the
unit can be changed according to the parameter
Pressure
unit.
Actual inlet pressure.
Shows the actual outlet pressure.
Actual outlet pressure.
Selects the primary source used for pump inlet pressure
measurement.
None
Parameter
12.12 AI1 scaled
Parameter
12.22 AI2 scaled
Parameter
11.39 Freq in 1 scaled
Parameter
12.101 AI1 percent
Parameter
12.102 AI2 percent
Parameter
40.91 Feedback data
Source selection (see
Terms and abbreviations
Selects the primary source used for pump outlet pressure
measurement.
None
Parameter
12.12 AI1 scaled
Parameter
12.22 AI2 scaled
Parameter
11.39 Freq in 1 scaled
Parameter
12.101 AI1 percent
Parameter
12.102 AI2 percent
Parameter
40.91 Feedback data
Source selection (see
Terms and abbreviations
Defines the height difference between inlet and outlet
pressure sensors for flow calculation.
Sensors height difference.
Selects the unit of pressure.
Pressure
(page 272).
(page 272).
(page 272).
(page 272).
81.20
value.
value.
value.
value.
value.
storage.
on page 100). -
value.
value.
value.
value.
value.
storage.
on page 100). -
Parameters 273
Def/FbEq16
0.00
0.00
0.00
0.00
0.00
1 = 1 bar
0.00
1 = 1 bar
AI1 scaled
0
1
2
3
8
9
10
AI2 scaled
0
1
2
3
8
9
10
0.00
1 = 1 m
bar
0