hit counter script

Parameter Selection - ABB ACH 500 Series Programming Manual

Adjustable frequency ac drives 2 to 400 hp
Table of Contents

Advertisement

Chapter 3 – Start-up Data

Parameter Selection

A LANGUAGE
B APPLICATIONS
C APPLIC. RESTORE
D SUPPLY VOLTAGE
E USER DISPLAY
SCALE
3-2
Table 3-1 Start-up Data Parameters
Parameter
A LANGUAGE
B APPLICATIONS
C APPLIC. RESTORE
D SUPPLY VOLTAGE
E USER DISPLAY
SCALE
F MOTOR CURRENT
-FLA
G MOTOR POWER
hp (kW)
H MOTOR POWER
FACTOR
I MOTOR BASE FREQ.
J MOTOR BASE R.P.M.
K MOTOR NOM.
VOLTAGE
The following is a list of the Start-up Data parameters with a description of
each parameter.
The ACH 500 displays all information in the language you select. The
available languages are: English, German, Italian, Spanish, Dutch, French,
Danish, Finnish, and Swedish.
This parameter is used to select the Application macro which will configure
the ACH 500 for a particular application. Refer to Chapter 6 – Parameters for
a list of available Application macros.
This parameter restores all parameters of the current application to the
original parameter values for that macro.
This parameter is used to set the supply voltage to the ACH 500. The choices
are 440, 460, 480, and 500 VAC for 480-volt units or 208, 220, 230, and 240
VAC for 230-volt units.
This parameter is used to set the scaling factor for Operating Data Parameter 2
(Speed). When set to 0, the speed display will show RPM. When set to 100,
the speed display will show %. When set to any other value from 0 – 10000,
the display will show this value (minus slip unless slip compensation is ON)
when the output frequency is at the frequency set by Start-up Data Parameter I
(Motor Base Frequency).
Range/Unit
Available languages
Language selection.
Application macros
Application macro selection.
No, Yes
Restores parameters to original values.
Supply voltage
Sets the supply voltage.
selections
0 – 10000
Scaling factor for speed.
0 A – 1000 A
Matches the ACH 500 to the rated
motor current.
0.7 HP – 1340 HP
Matches the motor rated power.
(0.5 kW – 1000 kW)
0.1 – 1.0
Matches the motor power factor.
30 Hz – 500 Hz
Sets the motor frequency.
200 rpm – sync.
Sets the nameplate speed.
speed
110 V – 575 V
Sets the motor nameplate voltage.
ACH 500 Programming Manual
Description

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach 501Ach 502B seriesAch 500

Table of Contents

Save PDF