DESIGO™ RXC RXZ95.1/LON Gateway EnOcean/LonWorks For use with: – DESIGO RXC – Devices / systems with L ® communication ORKS Wireless receiver with L ® interface FTT10A ORKS Evaluation of up to 9 EnOcean room units Operating voltage AC / DC 24 V...
Page 2
EnOcean interface (temperature sensor with setpoint adjuster, freely programmable button and 5-stage switch) The RXZ95.1/LON can be used in all systems with L Note communication ORKS 2 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies 23 Sep 2011...
Page 3
Room unit 2 Room unit 3 Total max. Temperature, setpoint Temperature Temperature, setpoint, 9 room units fan speed, presence Integration of EnOcean room units into DESIGO RXC Mechanical design Screw terminals LED "Power" Service pin LED "EnOcean- Service LED communications"...
Page 4
.NXE; .XFB; .XIF; .PDF (if SRC-FTT plug-in is not used) application ORKS Software source / LNS plug-in, device resource files, L application: ORKS Download from the DESIGO RX intranet:https://intranet10.sbt.siemens.com/ documentation https://intra.industry.siemens.com/bt/global/en/business/building_comfort/systems/ desigo/ra/Pages/des-ra-units.aspx?TabcardNo=6 resource files version 13.00: Download from http://www.lonmark.org/technical_resources/resource_files/ Environment for engineering tool Integration of QAX95.x/QAX96.x: The RXT10 tool or a standard LNS tool can be...
Page 5
Installation of L resource files version 13.00 or higher Source: http://www.lonmark.org/technical_resources/resource_files/ Step 2: Installation of device resource files: Source: Download from the DESIGO RX intranet: https://intra.industry.siemens.com/bt/global/en/business/building_comfort/systems/ desigo/ra/Pages/des-ra-units.aspx?TabcardNo=6 Step 3: Installation of SRC04-FTT plug-in Source: Download from the DESIGO RX intranet: https://intra.industry.siemens.com/bt/global/en/business/building_comfort/systems/ desigo/ra/Pages/des-ra-units.aspx?TabcardNo=6...
Page 6
Device > Configure > Thermokon_SRC-FTT > OK Confirm message by selecting YES. Select function “Thermokon SRC-FTT“ > Click OK. Confirm message by selecting YES. 6 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Workflow with RXT10 and LNS plug-in...
Page 7
Recommendation: Same as RXC Default 2700 [s] (45 min) Configure the gateway: select tab Switch settings: Functions not available with the RXT10 7 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Workflow with RXT10 and LNS plug-in 23 Sep 2011...
Page 9
Open Plug-in (Device > Configure > Thermokon SRC-FTT > OK > Click button next to SensorID > Learn-in > Press button on the room unit Function check gateway / room unit: 9 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Workflow with RXT10 and LNS plug-in...
Page 10
Extract and save LON application: srcn_9_1_01 (.apb; .nxe; .xfb; .xif) / optional: srcn_12_1_01 Source: Download from the DESIGO RX intranet:https://intranet10.sbt.siemens.com/ business/building_comfort/systems/desigo/ra/_des_ra_qax/_des_ra_qax95.htm Engineering with Set up the gateway with the RXT10 tool by following the standard procedure for RXT10 and XIF-Import integration of third-party devices (for details, refer to User Manual RXT10, CM110669).
Page 11
> Read XIF File > Select path for srcn_9_1_02.xif > OK > Select Plug-in > Close Device > Configure > OK (depending on plug-in: Configure Device) 11 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Workflow with RXT10 and SBT generic plug-in...
Page 12
Receive time For monitoring the RF link to the room unit (optional) UCPTspMax/MinValue: Setpoint Offset ( 3 K, default) 12 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Workflow with RXT10 and SBT generic plug-in 23 Sep 2011...
Page 13
Setpoint Offnet: nvoSetpoint_x nviSetpointOffset Netwok > Connect (online) Assign devices and install Device > Configure > OK 13 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Workflow with RXT10 and SBT generic plug-in 23 Sep 2011...
Page 14
Additional room units: Repeat procedure set bit [1] = 1 to learn-in Sensor [1] set bit [2] = 1 to learn-in Sensor [2] etc. 14 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Workflow with RXT10 and SBT generic plug-in...
Page 15
Function check gateway / room unit: nvoHVACTemp_1: Receive room temperature from room unit nvoSetpoint_1: Receive setpoint offset from room unit 15 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Workflow with RXT10 and SBT generic plug-in 23 Sep 2011...
Page 16
SCPTmaxSendTime < approx. 20 min T2 = 0.0 C (frost alarm) SCPTmaxSendTime > approx. 30 min T2 = last valid T2 Ditto; at 0.0 C frost alarm 16 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies...
Page 17
With each simultaneous power failure of the RXC and the gateway, the system triggers frost alarm for 20 to 30 minutes. The same applies to power-up. 17 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Sources of errors...
Page 18
The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. 18 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Mounting...
Page 19
Material Color white, similar to RAL9010 Weight Without / with packaging 173 g / 248 g Connection terminals Supply LonWorks bus Connector for antenna 19 / 20 Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Technical data 23 Sep 2011...
Page 20
Dimensions Dimensions in mm 42.5 45.5 2500 20 / 20 2008 Siemens Schweiz AG 2008 - 2011 Siemens Switzerland Ltd. Änderungen vorbehalten Subject to change Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02 Building Technologies Dimensions 23 Sep 2011...