278 Technical data
Input
Inverter
ratings
unit
Frame
type
size
ACS880-
I
104- ...
A
1030A-7
2×R8i
1159
1170A-7
2×R8i
1316
1540A-7
3×R8i
1733
1740A-7
3×R8i
1958
2300A-7
4×R8i
2588
2860A-7
5×R8i
3218
3420A-7
6×R8i
3848
■
Definitions
U
Nominal AC supply voltage of drive system
N
I
Nominal rms input current
1
I
Nominal output current (available continuously with no over-loading)
2
P
Typical motor power in no-overload use
N
The horsepower ratings are typical NEMA motor sizes at 460 V (ACS880-104-xxxxA-5) and 575 V
(ACS880-104-xxxxA-7) respectively.
Apparent power in no-overload use
S
N
I
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
Ld
P
Typical motor power in light-overload use
Ld
I
Maximum output current. Available for 10 seconds at start; otherwise as long as allowed by drive
max
temperature.
I
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
Hd
P
Typical motor power in heavy-duty use
Hd
Note:
•
The ratings apply at an ambient temperature of 40 °C (104 °F).
•
The ratings apply to units without option +C132 (marine type approval). For ratings of
units with option +C132, see ACS880 +C132 marine type-approved drive modules and
module packages supplement (3AXD50000037752 [English])
•
To achieve the rated motor power given in the table, the rated current of the drive must
be higher than or equal to the rated motor current.
•
The DriveSize dimensioning tool available from ABB is recommended for selecting the
drive, motor and gear combination.
No-overload use
I
I
1
max
2
A
A
1550
1030
1760
1170
2310
1540
2610
1740
3450
2300
4290
2860
5130
3420
Output ratings
Light-overload
P
S
I
N
N
Ld
kW
kVA
A
1000
1231
989
1100
1398
1123
1400
1840
1478
1600
2080
1670
2000
2749
2208
2800
3418
2746
3200
4087
3283
Heavy-duty use
use
P
I
Ld
Hd
kW
A
900
770
1000
875
1400
1152
1600
1302
2000
1720
2400
2139
3200
2558
P
Hd
kW
710
800
1100
1200
1600
2000
2400