Page 1
RMS-SNMP01A SNMP Card User Manual Issue Date 2020-01-09 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
About This Document About This Document Purpose This document describes the RMS-SNMP01A in terms of its features, appearance, installation, usage, and operation. The RMS-SNMP01A is an optional communications card which is designed for the UPS2000-G-(6 kVA–20 kVA) and UPS2000-A-(6 kVA–10 kVA) series.
Page 7
5.1 Introduction to the NetEco 1000U .........................62 5.2 Applying for Access Rights ...........................62 5.3 Managing the UPS..............................62 6 Managing the UPS by Using the NMS Complying with Huawei Standard ....63 6.1 SNMP Card Versions ............................63 6.2 Installing the UPS MIB Library ..........................63 6.3 Managing the UPS by Using the NMS ........................63...
The SNMP card allows users to remotely manage the UPS by using a network management system (NMS), Huawei NetEco, or a web browser on a computer network. A maximum of 16 SNMPv3 users and 80 NMS users can manage the UPS.
3 Installation and Basic Settings 3.3 Installing the SNMP Card The methods for installing SNMP cards are the same on different UPSs of Huawei. The SNMP card is installed in the optional card slot INTELLISLOT at the rear panel of the UPS.
User Manual 3 Installation and Basic Settings 3.5.3 GSM Modem A GSM modem provided by Huawei can be configured for the SNMP card. The GSM modem model needs to be determined based on the actual situation. Figure 3-7 shows the GSM modem appearance.
Page 25
If the Hall current sensor is prepared by the customer, the customer should refer to the model recommended by Huawei. The rated current of the sensor should be 50 A, 100 A, and so on, and the corresponding output voltage at rated current should be 4 V. For example, if the 0–50 A Hall sensor range is chosen, ensure that the sampling current ±...
Page 27
The RMS-SNMP01A card does not support connection to a temperature and humidity sensor and an external dry contact card at the same time. Figure 3-14 Connecting cables to the external dry contact card Refer to the external dry contact card user manual and set the card address to 8.
Figure 4-7 Adding compatibility view settings 4.2.3 Privacy Statement Before performing any maintenance or change operations, Huawei engineers must obtain the formal written authorization from the customer, and must perform operations in compliance with local laws and regulations. ...
On the WebUI, only part of the email address is displayed. For example, support@huawei.com is displayed as su****t@huawei.com. The email password is displayed as ciphertext *****. The system provides the personal data encryption protection. The email address and password are encrypted using a secure encryption algorithm with a cipher key.
Page 58
NMS complying with the RFC1628 standard, such as UNMS of Generex, to manage the UPS remotely. Click Download HUAWEI-UPS-MIB to download the MIB file which allows a third-party NMS complying with Huawei standard to manage the UPS remotely. Issue 08 (2020-01-09)
Page 59
7 Managing the UPS by Using the NMS Complying with RFC1628 Standard. If a third-party NMS complying with Huawei standard is adopted, download the HUAWEI_UPS_MIB file. For details about the function of a third-party NMS managing UPS, see Managing the UPS by Using the NMS Complying with Huawei Standard.
RMS-SNMP01A SNMP Card User Manual 4 Managing the UPS on the WebUI If you use Huawei NetEco, set Trap port to 162. 4.6.6 RCCMD The UPS2000 SNMP card integrates the functions of the Generex RCCMD server: When the UPS generates an alarm, the SNMP card sends a shutdown command notification message, execution command, or trap message to the RCCMD client.
Download the MIB files on the web browser. For details, see section 4.6.1 Comm. Config Page. When you load the MIB library by using the NMS, load the HUAWEI-MIB-V3.34.mib file and then the HUAWEI-UPS-MIB.mib file. For details, see the NMS user manual. 6.3 Managing the UPS by Using the NMS 6.3.1 Applying for Access Rights...