Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Parameter list ..........................27 Trouble shooting ............................43 List of alarms and faults .......................43 Product support..........................49 Spare parts...........................49 This Getting Started Guide describes how you install and commission the SINAMICS G120C converter. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Product overview The SINAMICS G120C is a range of converters for controlling the speed of three phase motors. The converter is available in three frame sizes. You find a label with the order number: ● On the front of the converter after removing the blind cover or the operator panel.
Static discharges on surfaces or interfaces (e.g. terminal or connector pins) can cause malfunctions or defects. ESD protective measures should therefore be observed when working with converters or converter components. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 8
Use of mobile radio devices (e.g. telephones, walkie-talkies) in the immediate vicinity of the devices (< 1.8 m) can interfere with the functioning of the equipment. WARNING Filtered drives can only be used on power systems with grounded neutral point. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 9
Repair WARNING Repairs on equipment may only be carried out by Siemens Service, by repair centers authorized by Siemens or by authorized personnel who are thoroughly acquainted with all the warnings and operating procedures contained in this manual.
Page 10
5. Release of environmental pollutants or emissions as a result of improper operation of the system and/or failure to dispose of components safely and correctly. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Installing 3.2 Electrical installation Electrical installation Connecting line, motor and further components SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 13
Connect the shield to the mounting plate or to the shield plate through a good electrical connection and through the largest possible surface area. Screening example for converter frame size A SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 14
Installing 3.2 Electrical installation Overview of process and user interfaces SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 15
The handling of shielded cables is shown in section Electrical installation (Page 10). SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
3. Select your chosen I/O configuration (macro) during basic commissioning. 4. Change the function of the inappropriate terminals. Fixed speeds See also section: Releasing "Safe Torque Off" (Page 26). SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 17
Automatic / Manual - change over from field bus to jog Factory setting with G120C DP and G120C PN: See also section: Description files for fieldbus configuration (Page 18). SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 18
See also section: Releasing "Safe Torque Off" (Page 26). Analog setpoint See also section: Releasing "Safe Torque Off" (Page 26). Process industry See also section: Description files for fieldbus configuration (Page 18). SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 19
Installing 3.3 Pre-defined interface configurations Two or three wire control Macro 12 is factory setting with the G120C USS/MB and G120C CAN. Communication with the higher-level control via USS SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
The EDS file for CAN is Internet: CANopen required to operate the (http://support.automation.si converter as a node on a CAN emens.com/WW/view/en/48 bus and announce the device 351511) to the configuration tool. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
IOP - with handheld 6SL3255-0AA00-4HA0 For mobile use of the IOP PC tools for commissioning, diagnostics and controlling of the converter PC Connection Kit 6SL3255-0AA00-2CA0 Includes a STARTER DVD and USB port. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 22
● Select the drive in your project and go online ● In your drive open the "Configuration" mask (double click) ● Start basic commissioning with the "Assistent" button For further information refer to converter operating instructions. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 23
Futher steps see next section (Page 22). Overview of the BOP-2 menu OK ESC OK ESC OK ESC OK ESC OK ESC OK ESC OK ESC OK ESC SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
The predefined configurations can be found in the section titled Pre-defined interface configurations (Page 14). Set the minimum motor speed. Set the motor ramp-up time. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 25
This procedure can take up to one minute. Switch over from HAND to AUTO. Now you have finished the basic commissioning and the motor identification. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Confirm the parameter number using the OK Confirm the parameter value using the OK key. key. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Ready to start Closed-loop torque control active Ready External fault 1 (F07860) Operation enabled CDS bit 1 Fault active r0056 CO/BO: Status word, closed-loop control Coast down active (OFF2) SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 30
Rated motor speed [rpm] p0320 Motor rated magnetizing current/short-circuit r0208 Rated power unit line supply voltage [V] current [A] r0209 Power unit, maximum current p0322 Maximum motor speed [rpm] SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 31
CO: CU analog inputs input voltage/current actual 39 BTU/min 40 BTU/h 41 mbar AI0 (terminals 3/4) 42 inch wg 43 ft wg 44 m wg 45 % r.h. 46 g/kg SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 32
BI: No quick stop/quick stop (OFF3) signal source p0849 BI: No quick stop/quick stop (OFF3) signal source p0852 BI: Enable operation p0854 BI: Master control by PLC p0855 BI: Unconditionally release holding brake SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 34
A higher value results in a longer search time. p2000] p1206 Set fault number without automatic restart r1119 CO: Ramp-function generator setpoint at the input p1210 Automatic restart mode [100 % ≙ p2000] SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 39
CO: Techn. controller fixed value 3 [100 ≙ 100%] maximum value [%] p2204 CO: Techn. controller fixed value 4 [100 ≙ 100%] p2238 Techn. controller motorized potentiometer minimum value [%] SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 40
CO/BO: NAMUR message bit bar No inversion Inversion of the technology controller actual value signal p3320 Fluid flow machine P = f(n), Y coordinate: P flow 1%, point 1 SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 41
Know-how protection Control Unit reference serial number p8611 CAN Pre-defined Error Field [hex] p7760 Write protection/know-how protection status p8620 CAN Node-ID 1 = Write protection active r8621 CAN Node-ID effective SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 42
CAN Transmit Mapping for TPDO 3 [hex] r8955 CBE20 MAC Address of Station p8733 CAN Transmit Mapping for TPDO 4 [hex] r8960 PN Subslot assignment p8734 CAN Transmit Mapping for TPDO 5 [hex] SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 43
SI version, safety functions integrated in the drive (processor 1) r9771 SI common functions (processor 1) r9772 CO/BO: SI status (processor 1) r9773 CO/BO: SI status (processor 1 + processor 2) SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 44
Commissioning 4.2 Further settings SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
F01033 Unit switchover: Reference Set the value of the reference parameter to a value other than 0.0 (p0304, parameter value invalid p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004). SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 46
Motor temperature sensor fault Make sure that the sensor is connected correctly. Check the parameterization (p0601). F07086 Unit switchover: Parameter limit Check the adapted parameter values and if required correct. F07088 violation SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 47
Motor blocked Make sure that the motor can rotate freely. Check the torque limit: r1538 for a positive direction of rotation; r1539 for a negative direction of rotation. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 48
IP address, subnet mask or default gateway is not correct. IP address or station name used twice in the network. Station name contains invalid characters. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 49
Reduce the pulse frequency. F30005 I2t converter overload Check the rated currents of the motor and Power Module. Reduce current limit p0640. When operating with U/f characteristic: Reduce p1341. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
Page 50
PROFINET: Second controller "Shared Device" is activated (p8929 = 2). However, only the connection to a missing PROFINET controller is present. For further information, please refer to the List Manual. SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...
United Kingdom +33 (0) 821 801 122 +49 (0)911 895 7222 +39 (02) 24362000 +34 902 237 238 +44 161 446 5545 Further service telephone numbers: Product support (http://support.automation.siemens.com/WW/view/en/4000024) Table 5- 4 Manuals with further information Information Manual Content Available...
Page 52
Trouble shooting 5.3 Spare parts SINAMICS G120C frequency converter Getting Started, 03/2012, FW V4.5, A5E03831830B AA...