The specific approvals and certification for the drive can 1.6 Approvals and Certifications be found on the nameplate. For more information, contact the local Danfoss office or partner. The following list is a selection of possible type approvals and certifications for Danfoss drives:...
Page 75
Check for loose or missing wiring. No feedback from the heat sink temperature sensor. It may be necessary to contact the Danfoss supplier or The signal from the IGBT thermal sensor is not available on service department. Note the code number for further the power card.
Page 76
• Check for proper wire size. ALARM 50, AMA calibration failed • Contact the Danfoss supplier or Danfoss service Check the motor cables for short circuits or department. leakage currents. ALARM 51, AMA check U...
Page 77
The control card and power card are incompatible. To below the maximum limit. If the drive is unable to limit check compatibility, contact the Danfoss supplier with the the frequency, it trips and issues an alarm. The latter may type code from the unit nameplate and the part numbers happen in the flux mode if the drive loses control of the of the cards.
If the load remains Consult Danfoss if uncertain about the torque character- excessive long enough, the drive trips on inverter time. istics of an application.
LCP or the control card is imbalance of supply voltage is not more than 3%. defective. Replace the LCP. If the problem persists, replace the control card. Danfoss calculates mains imbalance per an IEC specifi- cation. 8.5.4 DC Bus Voltage Test •...
Connect a 24 V DC supply to the DC bus of the unit is safe to start. drive. Preferably, use a Danfoss split bus power supply. Connect it to the DC bus output of the Disconnect motor cables from output terminals moduleor, or to the busbars connecting the top (U, V, W).
9 Special Test Equipment Special test tools have been developed to aid in troubleshooting Danfoss products. The tools are required to perform some of the testing procedures outlined in this guide. The following test equipment described in this section is available from Danfoss.
690 V AC drives (T7) requires 610–1000 in field). V DC supply. • Current scaling card for the appropriate module. The Danfoss split bus power supply (p/n • 130B3146) is designed to provide 650 V DC, Tools for opening the service kit enclosure. •...
Remove the control shelf assembly from its package. Remove the LCP from the control shelf. Use some type of mounting hardware to install the control shelf. Danfoss does not supply the mounting brackets for the control shelf. For correct EMC installation, refer to Illustration 12.6.
All spare parts are suitable for conformal coated drives and can be used in either coated or non-conformal coated drives. 15.1.1 Using the Drive Configurator Tool For the latest spare parts information, visit the Danfoss website using the following directions. Go to https://vltconfig.danfoss.com/.
Page 370
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.