Default functions, disabling function ............52 Null function ....................52 Default functions ..................52 Table of the parameters that can be set (example: Desigo / CFC) ..54 2/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Contents...
TX-I/O™ Power supply module / bus connection module data sheet CM2N8183 P-bus bus Interface module data sheet CM2N8180 Profinet BIM data sheet CM2N8186 TX-I/O™ Engineering and installation guide CM110562 Replacement of legacy modules CM110563 3/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Introduction 2018-10-25...
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
Each BACS has its own tools. Tool override, "Functional test", etc. Signal type Designation of the signal of a physical input Total Room Automation New: Desigo Room automation 5/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Introduction 2018-10-25...
3-color I/O status LEDs (if supported by signal type) Example of a read The Y250T function (control signal, three-position output) uses 2 I/O points. operation One TXM1.6R relay module can accommodate 3 actuators. 6/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Introduction 2018-10-25...
Various flashing patterns For details about errors please refer to the section "Indication, operation, and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 7/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Indicators and operator controls...
ON ("N/O contact active") Open N/C contact D20R *) Closed OFF ("N/C contact active") *) If D20R is not supported: use D20 with Polarity = Inverse. 8/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Indicators and operator controls 2018-10-25...
• The I/O status LED and LCD display change accordingly. Pressing "+" or "–" when local override is disabled produces an "error" indication. 9/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
– Configuration and parameter-setting of the I/O functions (see [8], [9]) – Communication via the bus – Measurement and control application in the room automation station / the automation station 10/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Indicators and operator controls...
4...20 mA current measuring signal type measures no current. Quality Value = The status and quality information are coded in the process value (raw data). part of process value 11/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Indicators and operator controls 2018-10-25...
N/O Contact Integration I/O status LED via P-Bus Normal Service Alarm Process value Signal Processing (D20, D20R) N/O, N/C Contact Block diagram of function 12/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital input functions 2018-10-25...
Page 13
Diagram: Cause and effect For details, especially in relation to flashing pattern and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 13/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
• The LCD panel (if available) shows the source signal type (status contact, N/O or N/C contact) • The LCD panel shows the change (a block of 3 fields which change with each pulse): 14/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
– Start-up monitoring for analysis of faults Hardware • The function requires one I/O point • The TX-I/O modules support only inputs with N/O contacts. Function 15/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital input functions 2018-10-25...
Page 16
Response in the unpolled pulse is stored in the module. and the incoming pulses on the module event of a fault continue to be displayed.. 16/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital input functions...
– Repeat does not overwrite start – Heartbeat (due to COVperiod) does not overwrite upcoming events • The signal operation can be selected: Contact_NO (default), Contact_NC) 17/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital input functions...
Page 18
DualClick Enable Sends Tg12, Tg13, if both buttons Sends no Tg 12, Tg 13. Also no status Disabled pressed within tp transition to DualClick 18/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital input functions 2018-10-25...
Page 19
The I/O status LED is ON when when the N/O connected contact is closed For details, especially in relation to flashing pattern and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 19/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
+ 3 n + 7 Active I/O point MIValue Stage Example of a modified table None 0 / Auto n + 1 n + 2 20/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital input functions 2018-10-25...
Page 21
Inputs cannot be operated on the module. For details, especially in relation to flashing pattern and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 21/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
– Last value (last value from buffer) • COV Limit and COV Period define the amount of change and the interval for updates to be sent on the island bus by the module. 22/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
Page 23
• When communication is restored, the bus master polls the counter reading again. 23/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
6) When the process value is out of range, an error message will be sent. 7) AI PT1K375: No restriction concerning hum injection for TXM1.8U und TXM1.8X. 8) An open circuit of a single conductor cannot be detected for these signal types. 24/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
Page 25
• The I/O status LED and the module status LED flash For details, especially in relation to flashing pattern and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 25/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
• TXM1.8RB, see section 5.11) Function LED color Normal Service Alarm I/O status LED Local Override LO LED Process Signal Processing value Block diagram of function 26/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions 2018-10-25...
Page 27
• Address key is swiveled out • Failure of the module supply voltage DC 24 V (Powerdown) • Failure of bus master (Masterdown, no datagram received for more than 4 s) 27/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
Page 28
Additionally a time delay can be set. *) When using a normally-closed contact, a closed contact can be forced even if the relay is de-energized. 28/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions...
Reason: local override or each single I/O point is possible, Warning! which may create hazardous situations. Use a multistate signal type instead, where the outputs are electronically latched in the module. 29/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions...
Page 30
Normal = green (default) / Alarm = Red / Service = Yellow. For details, especially in relation to flashing pattern and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 30/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
In this case the triac can not be activated the module switches the output off and sets the process value to 0. The fault message is only sent when a command is pending. 31/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
DC 24 V supply breaks down. • As the relays are bistable, they stay in the backup position even without DC 24 V supply. 32/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions...
Page 33
• In the event of an error, the I/O status LED and the module status LED flash. For details, especially in relation to flashing patterns and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 33/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
Relay Inactive "ON" PulseTime Relay Active Relay (n) Relay Inactive "OFF" PulseTime Pulse/pause time BreakTime BreakTime I/O status LED (n+1) I/O status LED (n) 34/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions 2018-10-25...
Page 35
For details, especially in relation to flashing pattern and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 35/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
• In the case of an error the module status LED and the I/O status LED flash. For details, especially in relation to flashing pattern and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 36/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
(parameter Backup Value). Active I/O point MOValue Stage None n + 1 n + 2 n + 3 n + 4 n + 5 37/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions 2018-10-25...
Page 38
• The I/O status LEDs indicate the activity of the relays • In the case of an error the module status LED and all the I/O status LEDs assigned to the function flash. 38/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
Page 39
• Local operation can be disabled in the configuration. For details, especially in relation to flashing pattern and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 39/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
• PulseTime can be parameterized: 0.1...25.5 s (default = 0.5 s) (P-bus BIM: 0.5...25 s) • The relays are latched. • The signal type supports 1 to n mapping only. 40/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions...
Page 41
• Local operation can be disabled in the configuration. For details, especially in relation to flashing pattern and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 41/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
Additional runtime when traveling to or from 0 % (clearance between motor and drive). (Series D and higher) Note: Reaction Time is not part of the stroke model. 42/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
Page 43
OPEN command during 1.5 x runtime OPEN (series D and higher) • CONTINCLOSE Continuous CLOSE command • SINGLECLOSE CLOSE- command during 1.5 x runtime CLOSE (series D and higher) Parameterization 43/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions 2018-10-25...
Page 44
For details, especially in relation to flashing pattern and errors: refer to the section "Dis- play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6]. 44/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
Min. switch-on/-off times can be parameterized as an option to protect against excessive switching frequency. The triac does not switch on/off if the calculated switch- on / switch-off time is less than MinOnTime / MinOffTime. 45/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
Page 46
The triac can then not switch on The module switches off the output and sets process value to 0. The error message is sent only if a positioning command is available. 46/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
UP (to position "100%") n + 2 DOWN1 DOWN to middle position (end switch between position 0 and 100%) n + 3 Output n+3 must remain free 47/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions 2018-10-25...
Page 48
= Relay inactive Value = AOBBackup Value (Keep) AOBBackup Value Command/pulse length (UP / 0 s) BackupDelay Delay until BackupMode 0...900 s (300 s) 48/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions 2018-10-25...
Page 49
When power is restored, the relays remain inactive until a valid process value is available. • In case of bus failure: The behavior can be parameterized for each I/O function:: BackupMode, BackupValue and BackupDelay; see above parameters. 49/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Digital output functions 2018-10-25...
Y10S signal. Function I/O status LED Local override LO LED Process Signal Processing AO Signal value (Y10, Y420) Field device Block diagram of function 50/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Analog output functions 2018-10-25...
Page 51
P-bus BIM: The module keeps the last valid values Operation in the same state as before the fault: When fault is repaired automatic operation, remote override or local override 51/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Analog output functions...
The disabling function prevents local override of an I/O point. It should be configured to decommission any unused I/O points. There are no variables to set as parameters, and no island bus inputs or outputs. 52/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies...
Page 53
As soon as the modules are configured, you can use the functional tests of the building automation and control system. 53/54 Siemens TX-I/O™ Module system – Functions and operation CM110561en_08 Building Technologies Default functions, disabling function 2018-10-25...