hit counter script

Advertisement

ABB ABILITY™ ELECTRIFICATION MONITORING AND CONTROL FOR DISTRIBUTION NETWORKS
ABB ZEE600
Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB ZEE600

  • Page 1 — ABB ABILITY™ ELECTRIFICATION MONITORING AND CONTROL FOR DISTRIBUTION NETWORKS ABB ZEE600 Operation Manual...
  • Page 3 Document ID: 2NGA000149 Issued: 2019-12-17 Revision: A Product version: 1.0 © Copyright 2019 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment. In case of discrepancies between the English and any other language version, the wording of the English version shall prevail.
  • Page 7: Table Of Contents

    Product documentation...............3 Product documentation set............3 Document revision history............. 3 Related documentation..............4 Symbols and conventions..............4 Symbols..................4 Document conventions..............4 Section 2 ABB ZEE600 overview............. 5 Overview.....................5 Main screen..................7 Single-line diagram pages............. 9 System diagnostic pages...............9 Plant automation pages...............12 Reporting pages................12 Real-time trend...............12...
  • Page 8 Configuring printers................53 Configuring bay properties............... 54 Changing theme................55 Selecting electrical symbol standard..........55 Selecting electrical symbol alarms and text........57 Managing variables................57 Creating backups................62 Restoring backups................62 Shutting down system..............63 Section 4 Glossary................. 65 ABB ZEE600 Operation Manual...
  • Page 9: Section 1 Introduction

    Introduction Section 1 Introduction This manual The operation manual contains information about the features of ABB ZEE600. The manual provides instructions for monitoring and controlling. Intended audience This manual addresses the operator who operates the system frequently. The operator must be trained in and have a basic knowledge of how to operate the system.
  • Page 10: Related Documentation

    Section 1 2NGA000149 A Introduction 1.3.3 Related documentation Product manuals can be downloaded from the ABB Web site www.abb.com/mediumvoltage. Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
  • Page 11: Section 2 Abb Zee600 Overview

    Section 2 ABB ZEE600 overview Overview ABB zenon Electrification Edition 600 (ABB ZEE600 in short) is a specialized variant of ABB zenon (ABB Ability Operations Data Management zenon), which handles process visualization, control and distribution substation data management in electrification solutions for several customer segments.
  • Page 12 ABB ZEE600 Process control Scalability Process awareness GUID-1993AFA6-E888-42C3-A042-8BC3CF7600BE V2 EN Figure 3: ABB ZEE600 overview ABB ZEE600 handles several essential facets of substation and electrical process monitoring, control and data management. • Process awareness • Process control • Process monitoring •...
  • Page 13: Main Screen

    Section 2 2NGA000149 A ABB ZEE600 overview ABB ZEE600 can be used in two installation scenarios. • In a mix of new and existing installations in primary distribution substations, as a human-machine interface (HMI), communication gateway and a data handling unit.
  • Page 14 Section 2 2NGA000149 A ABB ZEE600 overview GUID-6F5D953A-A08D-48CA-9678-3D3DBB703FC6 V1 EN Figure 4: Main screen Main pages Navigation bar Content window Task bar Language selection Login/Logout Active user (also used to switch users) Alarm message indication and shortcut to the active alarms list...
  • Page 15: Single-Line Diagram Pages

    Section 2 2NGA000149 A ABB ZEE600 overview is changed in zenon Editor. Runtime can reload the changed files in the ongoing operation, but system-related changes are excluded as they generally require Runtime to be restarted. The task bar has a button for selecting the display language, and shows the logged in user and the current time and date.
  • Page 16 Section 2 2NGA000149 A ABB ZEE600 overview GUID-91837E9C-8E74-4AEE-94F1-1F2DECB55071 V1 EN Figure 5: System diagnostic example To ensure a uniform representation, standard symbols from the library are used to represent the network plans. Most symbols have an identifier that symbolizes the device accessibility.
  • Page 17 Section 2 2NGA000149 A ABB ZEE600 overview GUID-4222F0D0-D52B-4487-AC68-D39E53D8D2D6 V1 EN Figure 6: System diagnostic dialog box Table 1: System diagnostic symbols Symbol Description Personal computer GUID-18DF10F9-0285-43F7-8B1E-DC0214D7F9BB V1 EN Server GUID-113C71EE-7496-48F1-BADC-A13702D01446 V1 EN Network switch GUID-3E124C60-196A-44A8-829F-CABEAA8115BB V1 EN AC500 PLC GUID-5B2BF0B0-003B-4847-817A-8646E24B0AAD V1 EN...
  • Page 18: Plant Automation Pages

    Section 2 2NGA000149 A ABB ZEE600 overview Symbol Description 620 series protection and control relay GUID-B69C880D-A00F-47BB-8EDC-96794E8C39B1 V1 EN 630 series protection and control relay GUID-F68838A6-21D1-44C4-B9FA-273BA3944779 V1 EN REX640 protection and control relay GUID-B8A17EF6-7819-445D-8E0F-6974C7EDD9B3 V1 EN 2.2.3 Plant automation pages The plant automation page subset hosts the management of the automations available in the plant, for example, automatic network reconfigurations or load shedding but these page contents are not created by the wizard.
  • Page 19 Section 2 2NGA000149 A ABB ZEE600 overview GUID-98470270-0381-45E5-A639-DAA86CB75166 V1 EN Figure 7: Trend tab 1 Filter buttons 2 Diagram control buttons 3 Diagram 4 Cursor output list 5 Variable information Table 2: Trend diagram filter buttons Name Description Filter profiles...
  • Page 20 Section 2 2NGA000149 A ABB ZEE600 overview Table 3: Trend diagram control buttons Name Description Play Updates screen Stop Stops screen refreshing Refresh search Refreshes the display Zoom Zooms the display Rezoom Reduces the display Zoom - Reduces the display's time intervals...
  • Page 21: Comtrade Viewer

    2.2.4.2 COMTRADE Viewer The fault recording page offers the possibility to evaluate COMTRADE files in ABB ZEE600. The control supports IEEE C37.111 IEEE Standard Common Format for Transient Data Exchange (COMTRADE) for Power Systems standard-compliant files.
  • Page 22: Report Viewer

    IEC 61850 MMS file transfer protocol. An embedded logic in ZEE600 cyclically scans all connected IEDs searching for new available data. The uploaded files are stored in a specific folder on the local runtime PC. A sub-folder is created automatically for each device.
  • Page 23: Energy Management

    Section 2 2NGA000149 A ABB ZEE600 overview 2.2.4.4 Energy management Energy management allows access to the historical data of up to 100 devices with a maximum of four individually configurable measured values. This configuration is done outside the visualization using Historian Energy Consumption Configurator Wizard.
  • Page 24 Section 2 2NGA000149 A ABB ZEE600 overview GUID-91E103E5-E12B-4B19-A28A-E490A67A21B2 V1 EN Figure 11: Energy management diagram 1 General buttons 2 Diagram control buttons 3 Diagram 4 Cursor output list 5 Variable information Table 4: General energy management diagram buttons Name Description...
  • Page 25: Bay Dialog Box

    Section 2 2NGA000149 A ABB ZEE600 overview Table 5: Energy management diagram control buttons Name Description Play Updates the screen Stop Stops screen refreshing Refresh search Refreshes the screen Zoom Zooms the screen Rezoom Reduces the screen Zoom - Reduces the screen time intervals...
  • Page 26 Section 2 2NGA000149 A ABB ZEE600 overview This dialog box usually consists of five tabs, which switch on different status and control areas. GUID-D0D9C781-63F4-4F02-942C-FE0FE8BA6664 V1 EN Figure 12: Bay dialog box 1 Tabbed pages 2 Description 3 Predefined device-specific alarm texts...
  • Page 27: Secure Access And Operation

    User administration IEC 62443 GUID-E72FE553-903A-4FB8-842B-3DD60F3A7DC2 V2 EN Figure 13: Operational security with ABB ZEE600 User administration The role-based user administration feature protects against cybersecurity threats. Up to 128 different access levels can be defined in zenon Editor and zenon Runtime in Active Directory (optional) without any limit on the number of users.
  • Page 28 Automation logic settings and parametrization To help the operator, specific events can be filtered on a separate dialog box. GUID-93DBB16A-3F55-4877-A729-B6C3A34C7A06 V2 EN Figure 14: ABB ZEE600 audit trail Antivirus An antivirus policy is demanded by end customer requirements, according to the project.
  • Page 29 Section 2 2NGA000149 A ABB ZEE600 overview Patch management and system updates Using a specific license contract, software patch management, system updates and system maintenance can be accessed. ABB ZEE600 Operation Manual...
  • Page 31: Section 3 Operating The System

    Open Editor and click the Start Runtime symbol in the toolbarRuntime files. • Click the Start menu in Windows. • Use Windows Autostart. • Use the service zenStartupMgr. Click the Runtime button. Another Runtime start button for the 64-bit version may also be visible. ABB ZEE600 Operation Manual...
  • Page 32: Logging In And Out

    Logging in and out 3.2.1 Logging in On the task bar, click the icon. This icon is available only if no user is logged in, which is indicated by the message No active user. ABB ZEE600 Operation Manual...
  • Page 33 If the login password is incorrect, a dialog box opens. After entering a wrong password three times or if a non-existing user tries to log in, the user gets locked and can only be unlocked by an administrator. GUID-E10D6B22-9B03-4830-B3CA-258EB0BA4872 V1 EN Figure 18: Notification of incorrect password ABB ZEE600 Operation Manual...
  • Page 34: Logging Out

    GUID-F2A4BA75-FECA-4A56-801E-7A10B0ED50CE V1 EN Figure 20: Notification of insufficient user rights 3.2.2 Logging out On the task bar, click the icon. GUID-E5D748B7-4AC2-4DC4-9BFA-A1D3BAC9F815 V1 EN Figure 21: Logout symbol in task bar In the confirmation window, click Logout. ABB ZEE600 Operation Manual...
  • Page 35: Switching Users

    Switching users It is possible to switch between users directly without logging out the registered user. On the task bar, click the username field. In the Login dialog box, enter the username and password and click Login. ABB ZEE600 Operation Manual...
  • Page 36: Changing Language

    GUID-5227F5EA-5DFC-472F-A022-862FD6B87216 V1 EN Figure 23: Switching users Changing language ABB ZEE600 includes the zenon feature for multi-language support and is developed in the English language. On the task bar, click the language selection button. Select a language code. The number of languages in the list depends on the settings made in Template Wizard.
  • Page 37: Controlling Objects

    In the confirmation window, click Confirm. GUID-8E210CE2-6FF3-4BA1-BB08-925D4342FADA V1 EN Figure 24: Confirming the command Insufficient user rights are indicated by a yellow symbol in the form of a human silhouette. ABB ZEE600 Operation Manual...
  • Page 38: Controlling Tap Changer

    Figure 26: Indication of interlocking active Controlling tap changer On the bay dialog box, select the MAIN tab. Select the tap changer in the bay control field. Click to move the tap changer up or down. ABB ZEE600 Operation Manual...
  • Page 39: Viewing Measurements

    The appearance of the MEASURE tab can vary from bay to bay, depending on the base configuration selected in Object Import Wizard as well as the imported variables. Only status displays matching the device are displayed. ABB ZEE600 Operation Manual...
  • Page 40: Opening Trends

    Figure 28: Viewing measurements Opening trends • On the bay dialog box, select the TRENDS tab. The bay-specific chart values page opens. The values to be set here have to be defined in Object Import Wizard. ABB ZEE600 Operation Manual...
  • Page 41: Opening Notes

    For more information, see the Energy management chapter in this manual. Opening notes Each bay dialog box has a notebook, which can be edited during runtime. On the bay dialog box, click the NOTES tab. Edit the notes. Click Save. ABB ZEE600 Operation Manual...
  • Page 42: Accessing Web Hmi

    The WHMI window is the Web-based user interface integrated in the device. The design is the responsibility of the device manufacturer and is not part of the library presented here. • On the bay dialog box, click the WEB-HMI tab. ABB ZEE600 Operation Manual...
  • Page 43: Alarm And Event Handling

    Enables alarm deletion • Enables alarm printing and saving For quick error diagnosis and traceability, there are three different operating areas in the visualization. • Navigation alarm list • Active and historical alarm lists • Chronological event list ABB ZEE600 Operation Manual...
  • Page 44: Acknowledging Alarms Via Navigation Bar

    In the alarm list, click Acknowledge all to clear all alarms or Open to open the active alarms list, which provides more information about each fault. The active alarms list can also be accessed via the vertical menu. GUID-FD1DD702-B1F6-47FC-8797-A5D01A78D784 V1 EN Figure 33: Clearing alarms or opening the active alarms list ABB ZEE600 Operation Manual...
  • Page 45: Acknowledging Alarms Via Vertical Menu

    • In the Filter Profile list, select a filter to be applied. • In the Filter Profile text box, type a name and click Save to save the current settings as a filter profile. ABB ZEE600 Operation Manual...
  • Page 46: Defining New Alarm Filters

    3.10.2.1 Defining new alarm filters The filter dialog box has several settings that allow the alarm list to be filtered. In the Alarm List, click Filter to open the filter dialog box. ABB ZEE600 Operation Manual...
  • Page 47 Table 10: Text filter Item Description No text filter Does not select text filter Search for (word separated by space) Activates the search Search text Field for input of search term Table continues on next page ABB ZEE600 Operation Manual...
  • Page 48 Displays only alarms that have been current for at least the given number of seconds Millisecond Displays only alarms that have been current for at least the given number of milliseconds Use the control buttons to manage the selected settings. ABB ZEE600 Operation Manual...
  • Page 49: Opening Chronological Event List

    It is possible to filter the events and also print the filtered event list. On the vertical menu, click CEL to open the chronological event list. ABB ZEE600 Operation Manual...
  • Page 50 79 characters. Click Stop to prevent new elements from being automatically added to the event list. Click Custom record to create an event without text to be used for inserting an empty record for custom user comments. ABB ZEE600 Operation Manual...
  • Page 51: Defining New Event Filters

    Ring buffer Data comes from the ring buffer Historic data Data comes from an archive Maximum number Maximum number of historical alarms to be displayed 0: displays all Under Text filter, define the text filter properties. ABB ZEE600 Operation Manual...
  • Page 52 If the property Use hierarchical alarming of the Equipment Model is activated, the Alarm area column is empty. The check box is in the alarm handling item of the variable properties. Under Minimum time active, define how recent events are displayed. ABB ZEE600 Operation Manual...
  • Page 53: Printing Screen Contents

    Printing screen contents In the vertical menu, click Print Screen. The vertical menu closes and a screenshot of the visualization is sent to the preconfigured printer. Click Ok. GUID-5B5B19A6-AC21-4F3F-9698-D5EA85EB7D22 V1 EN Figure 38: Print Screen dialox box ABB ZEE600 Operation Manual...
  • Page 54: Activating Siren

    On the main screen, select Utilities from the vertical menu. Under User management, click Edit user. A list of all users is shown. GUID-EB370B2F-BA6A-4718-AD2F-45076CCCFBCC V1 EN Figure 39: Editing users Edit, create or delete users. ABB ZEE600 Operation Manual...
  • Page 55 5.2. In the New password box, enter the new password for the user. 5.3. In the Confirm password box, enter the new password again. Under User Groups, click to select or remove the user's user groups. ABB ZEE600 Operation Manual...
  • Page 56 After rejection, the message is sent to the next user in the list. If there is no other user entered in the list, the message is entered as "not successfully acknowledged". The function assigned to this is executed. In addition, a "rejected by" CEL entry is created in each case. Click Ok. ABB ZEE600 Operation Manual...
  • Page 57: Editing Groups

    • Under Properties, click New group to create a new user group, enter the user name and click Ok. • Under User Groups, select a user group and click Delete group to delete ABB ZEE600 Operation Manual...
  • Page 58: Viewing User List

    The user list provides an overview of all existing users in the current system. Unlike the list under Edit user, there are no user controls available under User list. On the main screen, select Utilities from the vertical menu. Under User management, click User list. ABB ZEE600 Operation Manual...
  • Page 59: Configuring Printers

    Configuring printers The printer setup can be used to configure different printers for each category. Always monitor the printing process because ABB zenon does not notify if a print job has started successfully or if a printer has been configured.
  • Page 60: Configuring Bay Properties

    GUID-44DA6DFA-2F4F-4958-8B4B-341C27219058 V1 EN Figure 43: Editing the bay properties Table 21: Voltage levels Voltage level Letter ZEE bay management index >420kV 380...420 kV 220...380 kV 110...220 kV 60...110 kV 45...60 kV 30...45 kV Table continues on next page ABB ZEE600 Operation Manual...
  • Page 61: Changing Theme

    The selected theme affects all screens. 3.17 Selecting electrical symbol standard On the main screen, select Utilities from the vertical menu. Under Electrical Symbol Standard, select the electrical symbol standard that defines the appearance of the bay configurations. • • ANSI ABB ZEE600 Operation Manual...
  • Page 62 Section 3 2NGA000149 A Operating the system GUID-A6B55473-9005-497C-84AD-4FA2FE37E3E4 V1 EN Figure 45: Selecting the ANSI standard ABB ZEE600 Operation Manual...
  • Page 63: Selecting Electrical Symbol Alarms And Text

    The actual values of these variables can also be manipulated. The manipulation of variables can lead to unpredictable malfunction of the connected devices and affect the usability and functionality of ABB ZEE600 Operation Manual...
  • Page 64 Figure 47: Variable diagnosis with selected variables 1 Filter buttons 2 Control buttons 3 Variable list On the main screen, select Utilities from the vertical menu. Under Variable diagnosis, click open screen. Manage the variable list. ABB ZEE600 Operation Manual...
  • Page 65 Under Write set value, select which set values are written to the hardware. • All variables • Selected variables Under View, select the variable list value format. • Decimal • Hexadecimal • Binary • Octal • Exponential ABB ZEE600 Operation Manual...
  • Page 66 Editor. Maximum signal This corresponds Maximum Signal range of the to the range max. variables in the property in zenon Editor. Current status of Status the variable in plain text display Table continues on next page ABB ZEE600 Operation Manual...
  • Page 67 Editor. Actual value (raw Raw data of the This value variable's actual corresponds to data) value the actual value of the variable before the value adjustment. Table continues on next page ABB ZEE600 Operation Manual...
  • Page 68: Creating Backups

    3.20 Creating backups ABB zenon Editor has its own node in the project tree for making project backups. These can be found at the bottom of the project tree. In the project manager, right-click the Project backups node and select Create backup.
  • Page 69: Shutting Down System

    On the main screen, select Utilities from the vertical menu. Under Shutdown, click Shutdown zenon to manually stop the visualization. On the System shutdown dialog box, click Ok to confirm the action. GUID-1CC7CD14-4AA8-4E7A-B9E6-AB32D87BAEAD V1 EN Figure 48: Confirming the system shutdown ABB ZEE600 Operation Manual...
  • Page 71: Section 4 Glossary

    International standard for substation communication and modeling IEEE Institute of Electrical and Electronics Engineers, Inc. Programmable logic controller Remote terminal unit SCADA Supervision, control and data acquisition Single-line diagram Coordinated universal time WHMI Web human-machine interface ABB ZEE600 Operation Manual...
  • Page 72 — ABB Distribution Solutions www.abb.com/mediumvoltage © Copyright 2019 ABB. All rights reserved.

Table of Contents