7.3.13 Re-fit the Controller Electronics
Re-fit the electronics into the controller case, checking that:
•
All cards are seated correctly in their sockets
•
The primary connections to the Dimming transformer have been set to the
correct voltage
•
All plugs and sockets are securely mated
•
All fixings are tight – especially those securing cards to side or back panels of
the cabinet.
7.4
On Site Testing
Once delivered to site and with reference to the Works Specification, check that:
•
The cabinet is free from external physical damage
•
All cards are seated correctly in their sockets
•
The connections between the Dimming Transformer and the MDU are correct
and are secure
•
All plugs and sockets are securely mated
•
All fixings are tight – especially those securing cards to side or back panels of
the cabinet.
•
After the site cabling has been terminated, additionally check:
•
The cable connections to the CET bars are tight
•
The street cables are terminated correctly into the appropriate Lamp Switch
Cards, MDU, I/O card or Loop Termination Card connectors.
7.5
Controller Commissioning
The ST950 family of controllers support both the traditional RS232 handset port and
now a USB handset port. The traditional handset commands are supported but the
user will find that the web interface provides a more detailed view of the controller
status to allow easier testing and commissioning.
7.5.1
Controller Setup
The following steps should be performed during commissioning:
•
If required, remove the CPU Card and fit the optional RTC battery backup kit
(section 7.5.2).
•
Load the IC4 configuration (section 7.5.3)
•
Add the required Licence(s) (section 7.5.4)
•
If required, configure the communications systems (e.g. IP data) (section
7.5.5)
•
If required, configure and start MOVA referring to the MOVA7 handbook -
667/HB/46000/003
Security classification
Version
Last Editor
Document Name
Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
Unrestricted
5
Neil Atkinson
ST950 ICM Handbook
Intelligent Traffic Systems
Sopers Lane, Poole, Dorset, BH17 7ER
Page
67 of 125
Status
Issued
Date
18-Dec-2018
Document No.
667/HE/46950/000