hit counter script
S&C PureWave Operation And Maintenance Manual

S&C PureWave Operation And Maintenance Manual

Hide thumbs Also See for PureWave:

Advertisement

S&C PureWave® UPS System
250 kW, 500 kW, 750 kW, and 1000 kW; 208-600 Volts

Table of Contents

Section
Introduction
Qualified Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Read this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . . 2
Retain this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . 2
Proper Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warranty Qualifications . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Understanding Safety-Alert Messages . . . . . . . . . . . . . . 3
Following Safety Instructions . . . . . . . . . . . . . . . . . . . . . 3
Replacement Instructions and Labels . . . . . . . . . . . . . . . 3
Hazardous Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Securing the Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Emergency Procedures and Equipment . . . . . . . . . . . . . 4
Additional Safety Instructions . . . . . . . . . . . . . . . . . . . . . 4
Location of Safety Labels . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Enclosure Configurations . . . . . . . . . . . . . . . . . . . . . . . 14
Enclosure Bays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
LCD Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Air Control and Ventilation . . . . . . . . . . . . . . . . . . . . . . . 20
Operating Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Service Personnel Controls . . . . . . . . . . . . . . . . . . . . . 23
May 22, 2017
© S&C Electric Company 2007-2017, all rights reserved
. . . . . . . . . . . . . . . . . . . . . . . . 13
Operation and Maintenance
Page
Section
Monitoring Computer . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Remote Disable (optional) . . . . . . . . . . . . . . . . . . . . . . 25
System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Transition States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Alarms List and Troubleshooting Tips . . . . . . . . . . . . . . 28
Warning Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Inhibit Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Bypass Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Bypass Isolate Alarms . . . . . . . . . . . . . . . . . . . . . . . . . 30
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Maintenance Bypass Procedure . . . . . . . . . . . . . . . . . . 31
to the Ready State . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Bypass Isolation Procedure . . . . . . . . . . . . . . . . . . . . . 31
Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Generator Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Monitoring Software Security . . . . . . . . . . . . . . . . . . . . 33
Monitoring Software . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Maintenance Checklist Overview . . . . . . . . . . . . . . . . . 37
Quarterly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 38
Annual Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Instruction Sheet 653-502
Page

Advertisement

Table of Contents
loading

Summary of Contents for S&C PureWave

  • Page 1: Table Of Contents

    Maintenance Bypass Procedure ....31 Safety Equipment, Precautions, and Practices ..4 Returning the PureWave UPS System Emergency Procedures and Equipment ... . . 4 to the Ready State .
  • Page 2: Qualified Persons

    Safety Precautions on pages 3 through 5. The latest version of this publication is available online in PDF format at sandc.com/Support/Product-Literature.asp. Retain this This instruction sheet is a permanent part of your S&C PureWave UPS System. Designate a location where you can easily retrieve and refer to it. Instruction Sheet...
  • Page 3: Understanding Safety-Alert Messages

    Instructions Read this instruction sheet thoroughly and carefully before operating your PureWave UPS System. If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Authorized Distributor. Their telephone numbers are listed on S&C’s website,...
  • Page 4: Hazardous Voltages

    Enclosure circuits. Safety Equipment, S&C PureWave UPS System and battery instruction sheets must be available to all operators and other employees. If doors to the electrical controllers or panels to the Precautions, and system enclosure must be opened, refer to the instruction sheet for procedures for Practices guarding against electric shock.
  • Page 5 Safety Information Location of Safety Labels − continued For 750-kW and 1000-kW PureWave UPS Systems (1000-kW system pictured) S&C Instruction Sheet 653- 502...
  • Page 6 Safety Information Location of Safety Labels − continued For 750-kW and 1000-kW PureWave UPS Systems (1000-kW system pictured) S&C Instruction Sheet 653-502...
  • Page 7 Safety Information Location of Safety Labels − continued For 750-kW and 1000-kW PureWave UPS Systems (1000-kW system pictured) Inside wall of the circuit breaker section of the switchgear bay S&C Instruction Sheet 653- 502...
  • Page 8 Safety Information Location of Safety Labels − continued For 750-kW and 1000-kW PureWave UPS Systems View of the back side of the circuit breaker View of the back side of the swing-out control section door of the switchgear bay panel inside the control bay.
  • Page 9 Safety Information Location of Safety Labels − continued For 250-kW and 500-kW PureWave UPS Systems (500-kW system pictured) S&C Instruction Sheet 653- 502...
  • Page 10 Safety Information Location of Safety Labels − continued For 250-kW and 500-kW PureWave UPS Systems (500-kW system pictured) S&C Instruction Sheet 653-502...
  • Page 11 Safety Information Location of Safety Labels − continued For 250-kW and 500-kW PureWave UPS Systems Views of the control bay (with the door open showing the dead-front panels). S&C Instruction Sheet 653- 502...
  • Page 12 Safety Information Location of Safety Labels − continued For 250-kW and 500-kW PureWave UPS Systems View of the switchgear bay with door open. S&C Instruction Sheet 653-502...
  • Page 13: Safety Precautions

    Safety Precautions DANGER The S&C PureWave UPS System operates at high ac and dc voltages. Failure to observe these precautions will result in serious personal injury or death. Some of these precautions may differ from your company’s operating procedures and rules.
  • Page 14: Components And Controls

    Do not enter the system enclosure unless trained, certified, and authorized to do so by S&C Electric Company. Physical entry into the PureWave UPS System should never be attempted while the system is enabled or when the modules are online. Voltages up to 800 Vdc and 600 Vac should be expected under normal operating conditions.
  • Page 15 Air-inlet vent hood Air-outlet vent hood Switchgear bay Battery bay Battery bay Control bay Battery bay Figure 3. Front view of the 750-kW PureWave UPS System. Air conditioner Air-inlet vent hood Air-outlet vent hood Switchgear bay Battery bay Battery bay...
  • Page 16: Enclosure Bays

    Components and Controls Enclosure Bays The enclosure of the PureWave UPS System consists of three types of bays: Battery bay—Each battery bay contains a 250-kW battery module and a power conver- sion module (PCM). The PCM is located in its own compartment in the battery bay and is comprised of one inverter module consisting of power-conversion electronics and con- trols.
  • Page 17 See Figures 6 and 7. Input circuit breaker Bypass circuit breaker Output circuit breaker Figure 6. View of the switchgear bay for the 250-kW and 500-kW PureWave UPS system. Input circuit breaker Bypass circuit breaker Output circuit breaker Figure 7. View of the switchgear bay for the 750-kW and 1000-kW PureWave UPS system.
  • Page 18 Components and Controls Enclosure Bays − Control bay—The control bay houses the monitoring computer, control system, power continued electronic switch (PES), and ac filter capacitor. In addition, an EMERGENCY DISABLE mushroom switch and a RESET pushbutton are located behind the door. See Figure 8 for a view of the control bay.
  • Page 19: Doors

    Components and Controls Doors To open a bay door, remove the padlock from the security cover located over the center bolt. Three bolts (top, center, and bottom) secure the door closed. Loosen the three bolts so they detach from the enclosure (the bolt will not completely detach from the door).
  • Page 20: Lcd Screen

    LCD screen Next to the control bay is the LCD screen, which displays information regarding the state of the PureWave UPS System. See Figure 10. The bottom line of the LCD screen displays the general messages as stated in Table 1.
  • Page 21: Operating Controls

    When the system is in the Bypass state and the RESET pushbutton is pushed, all latched alarm(s) will be reset if the alarm(s) have cleared. ENABLE/DISABLE switch RESET pushbutton Figure 11. Location of operating controls for the 250-kW and 500-kW PureWave UPS Systems. S&C Instruction Sheet 653- 502...
  • Page 22 Components and Controls Operating Controls − continued ENABLE/DISABLE switch RESET pushbutton Figure 12. Location of the operating controls for the 750-kW and 1000-kW PureWave UPS Systems. S&C Instruction Sheet 653-502...
  • Page 23: Service Personnel Controls

    Components and Controls Service Personnel In addition to the operating controls located inside the switchgear bay, redundant oper- ating controls are located in the control bay. These controls are intended to be used by Controls authorized service personnel. See Figure 13 for the location of these controls. ENABLE/DISABLE–This mushroom pushbutton performs the same functionality as the toggle switch in the switchgear bay.
  • Page 24: Monitoring Computer

    The monitoring computer is used to log system events and to monitor the status of the PureWave UPS System. The computer is located on the back of the swing-out panel located in the control bay. Information from the computer can be accessed via an Ether- net connection.
  • Page 25: Contacts

    Run state. Remote Disable If supplied, a normally closed input contact must be provided by the user to the PureWave UPS System. Upon opening of the input contact, the system will go to the Bypass state, (Optional) and an output contact will close to indicate the system has been remotely disabled.
  • Page 26: Operation

    An electrically operated bypass circuit breaker permits continued service to the customer from the utility in the event the PureWave UPS System is out of service for maintenance. See Figure 15 for a diagram of the PureWave UPS System.
  • Page 27: States

    In this state, the PureWave UPS System is ready to protect the load in the event of a disturbance. In this state, the PureWave UPS System is running to protect the load from a utility disturbance. The inverters are on and the PES is open.
  • Page 28: Alarms List And Troubleshooting Tips

    Operation Alarms List and The PureWave UPS System contains an extensive self-diagnosis system. If any abnormal condition occurs or if the system cannot protect the load from a disturbance, the system Troubleshooting Tips will activate an alarm. The alarms can be categorized by alarm type. Alarm types are cat- egorized as Warning, Inhibit, Bypass, and Bypass Isolate.
  • Page 29: Inhibit Alarms

    Load Over Current Indicates the load current has exceeded 115% of the current rating of the system Troubleshooting Tip: Check the load against what the PureWave UPS System was sized for. Load Over Power Indicates the load power has exceeded 115% of the power rating of the system Troubleshooting Tip: Check the load against what the PureWave UPS System was sized for.
  • Page 30: Bypass Alarms

    Operation Bypass Alarms A Bypass alarm indicates a condition that requires attention and places the system in the Bypass state. The system is not available to protect the load from power disturbances. See Table 6 for the listed Bypass alarms. Table 6.
  • Page 31: Start-Up

    Procedure PureWave UPS can be placed in the Bypass Isolate state via the following procedure: Make sure the ENABLE/DISABLE selector switch is turned to the Disable STEP 1.
  • Page 32: Battery Charging

    The PureWave UPS System will go into the Run state while the transfer switch STEP 9. returns the critical load to the utility. If the load is at 50% or less of the PureWave UPS System rating, the system will wait for 10 seconds before actuating the transfer signal. S&C Instruction Sheet 653-502...
  • Page 33: Monitoring

    Monitoring Overview The PureWave UPS System can be monitored in three ways. The system can be monitored through the LCD screen display, through the computer provided in the control bay via a local connection, and remotely using an Ethernet connection.
  • Page 34 Monitoring Monitoring Software − Icons — continued continued Utility source–If this icon is red, it indicates the utility is a good source. If the icon is green, it indicates the utility is not good (the source is not within voltage and frequency tolerance).
  • Page 35 Monitoring Software − Displayed Parameters continued Figure 18 shows the areas of the One-Line screen where the user can find measured parameters of the PureWave UPS System. Time and date of last Run event Power source information Length of last Run event Figure 18.
  • Page 36 Status Screen continued The Status screen shows all the alarms for the PureWave UPS System and displays the active alarms using color indicators. In addition, the screen shows the current, voltage, and other parameters of the system as displayed in Figure 19.
  • Page 37: Maintenance

    Maintenance The following checklists provide the inspection activities that are to be performed on a periodic basis (as specified) for the PureWave UPS System. The amount of dust and dirt Checklist Overview varies from site to site. Therefore, schedules for maintenance should be reviewed by the user based on the given site conditions and, if required, the frequency of the recommended maintenance may increase to ensure the reliability of their PureWave UPS System.
  • Page 38: Quarterly Maintenance

    ¨ Coordinate with the site facilitator to obtain keys for locks (if applicable) to unlock the doors to the PureWave UPS System enclosure(s). ¨ Confirm with the site facilitator that the PureWave UPS System is de-energized before conducting maintenance on the system.
  • Page 39 Quarterly Maintenance For the 250-kW and 500-kW PureWave UPS Systems, use the following steps. (For the 750-kW and 1000-kW PureWave UPS Systems, go to page 40.) The air-inlet − continued vent is located on the switchgear bay door. The inlet filter is located on the inside of the switchgear bay door.
  • Page 40 Quarterly Maintenance For the 750-kW and 1000-kW PureWave UPS Systems, use the following steps. (For the 250-kW and 500-kW PureWave UPS Systems, go to page 39.) The air-inlet vent − continued hood is located on top of the switchgear bay. The air-outlet vent hood is located on top of the control bay.
  • Page 41 ¨ Perform general housekeeping, to ensure there no garbage or debris is in or around the enclosure. ¨ Bring the PureWave UPS System back online. ¨ Record the system state: _______________________________________________________ ¨ Close and lock all the enclosure doors and return site keys to the facility supervisor (if applicable).
  • Page 42: Annual Maintenance

    ¨ Coordinate with the site facilitator to obtain keys for locks (if applicable) to unlock the doors to the PureWave UPS System enclosure(s). ¨ Confirm with the site facilitator that the PureWave UPS System is de-energized. ¨ Verified By:_________________________ Date: ___________ Required Tools ¨...
  • Page 43 DANGER − continued The PureWave UPS System must be de-energized before performing maintenance on the equipment. Failure to do so can result in serious injury or even death. Maintenance should only be conducted by S&C Electric Company personnel or person- nel who are properly trained by S&C Electric Company.
  • Page 44 DANGER − continued The PureWave UPS System must be de-energized before performing maintenance on the equipment. Failure to do so can result in serious injury or even death. Maintenance should only be conducted by S&C Electric Company personnel or personnel who are properly trained by S&C Electric Company.
  • Page 45 ¨ Inspect the air-outlet vent hood at the top of the control bay. Clean any debris or obstructions that can restrict air flow going out of the PureWave UPS System. See Figure 25 for the location of the air-outlet vent hood.
  • Page 46 Maintenance Annual Maintenance For the 250-kW and 500-kW PureWave UPS Systems, use the following steps for the switchgear bay. (For the 750-kW and 1000-kW PureWave UPS Systems, go to − continued page 47.) ¨ Inspect the air-inlet vent located on the switchgear bay door. Clean any debris and obstructions that can restrict air flow going into the PureWave UPS System.
  • Page 47 Maintenance Annual Maintenance For the 750-kW and 1000-kW PureWave UPS Systems, use the following steps for the switchgear bay. (For the 250-kW and 500-kW PureWave UPS Systems, go to − continued page 46.) ¨ Inspect the air-inlet vent hood at the top of the switchgear bay. Clean any debris or obstructions that can restrict air flow going into the PureWave UPS System.
  • Page 48 Contact S&C Electric Company to conduct calibration verification and operational testing services. WARNING The following procedures require the PureWave UPS System to have utility power. The system should be placed in the Bypass Isolate state before conducting the proceeding equipment testing procedures.
  • Page 49 ¨ Perform general housekeeping to ensure no garbage or debris is in or around the enclosure. ¨ Bring the PureWave UPS System back online. ¨ Record the system state: _______________________ ¨ Close and lock all the enclosure doors and return site keys to the facility supervisor (if applicable).

Table of Contents