hit counter script

Station Communication; Iec 61850-8-1 Communication Protocol; Application Iec 61850-8-1 - ABB Relion SAM600 Applications Manual

Switchgear control unit version 2.2
Hide thumbs Also See for Relion SAM600:
Table of Contents

Advertisement

1MRK 511 445-UEN B
Section 7
7.1

IEC 61850-8-1 communication protocol

7.1.1

Application IEC 61850-8-1

IEC 61850-8-1 communication protocol allows vertical communication to HSI clients and allows
horizontal communication between two or more intelligent electronic devices (IEDs) from one
or several vendors to exchange information and to use it in the performance of their functions
and for correct co-operation.
GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850–8–1 standard,
allows the IEDs to communicate state and control information amongst themselves, using a
publish-subscribe mechanism. That is, upon detecting an event, the IED(s) use a multi-cast
transmission to notify those devices that have registered to receive the data. An IED can, by
publishing a GOOSE message, report its status. It can also request a control action to be
directed at any device in the network.
Figure
11
the interface to the substation LAN. The LAN itself is left to the system integrator.
IED
1
KIOSK 1
IEC09000135 V1 EN-US
Figure 11:
Figure12
Switchgear control unit SAM600-IO
Application manual

Station communication

shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8–1 specifies only
Engineering
Workstation
SMS
IED
IED
2
3
KIOSK 2
SA system with IEC 61850–8–1
shows the GOOSE peer-to-peer communication.
© Copyright 2017 ABB. All rights reserved
Station HSI
Base System
IED
IED
IED
1
2
3
Station communication
Gateway
CC
Printer
IED
IED
IED
1
2
3
KIOSK 3
IEC09000135_en.v