11.1 Repeater connection ..........................23 12. CONFIGURING THE ID2 FIRE ALARM PANEL ....................24 12.1 CONFIGURING THE ZONES ........................24 12.1.1 FROM A BLANK INFINITY ID2 PANEL ....................24 12.1.2 FROM A PREVIOUSLY CONFIGURED PANEL ..................24 12.2 Verifying the Zone configuration ......................24 12.3 Labelling the Panel and Zones ........................
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 1. SAFETY INFORMATION WARNING: Read this section completely before commencing installation. 1.1 Installation Information THIS FIRE ALARM CONTROL PANEL IS CLASS 1 EQUIPMENT AND MUST BE EARTHED This equipment must be installed and maintained by a qualified and technically experienced person.
The ID2 Fire Alarm Control and Indicating Equipment (CIE) has been designed to Detection & Fire Alarm Systems – Control & Indicating Equipment As well as meeting the requirements of EN 54-2:1997 +A1, the Infinity ID2 also has the following options with requirements:- Clause 7.8...
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 3.0 Panel description & design concept The ID2 is an eight zone intelligent fire alarm control panel designed to EN54 part 2 & 4. The ID2 has been designed to use zone powered sounders but also has 2 conventional sounder circuits. All sounders on a ID2 panel will activate on any alarm.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 4 USING THIS MANUAL It is beyond the scope of this manual to teach the user all the intricacies of fire alarm system design. If in doubt about what is required, read BS 5839: Pt 1: 2013 “Fire Detection and Alarm Systems for buildings (UK Code of Practice for System Design, Installation, commissioning and maintenance)”...
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 5 DESIGNING A SYSTEM This manual is not designed to teach Fire Alarm System design. It is assumed that the System has been designed by a competent person, and that the installer has an understanding of Fire Alarm System components and their use.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 6. INSTALLING THE SYSTEM 6.1 Considerations before Installation 6.1.1 MOUNTING THE CONTROL PANEL The control panel should be installed in accordance with the following recommendations:- The panel should be close to the main entrance of the building, so that it can be viewed by any fire- •...
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 6.2 First Fix 6.2.1 MOUNTING THE FIRE ALARM PANEL The ID2 comes with many cable entry holes. If another entry hole is required, it is strongly recommended that the, the termination PCBs should be removed and stored in a safe place.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 6.2.4 CONNECTING THE MAINS POWER Figure 3: Power Supply PCB layout and Mains connection details The panel should be connected to 220-240V AC by a 3A rated spur to the fuse box with 1mm to 2.5mm...
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 6.2.5 CONNECTING THE BATTERIES Figure 4: Battery location and connection details Although there are many sizes of suitable battery, the sizes we usually recommend for the ID2 are 12V 7Ah, To calculate the exact requirement, use the equation in section 20.1, STANDBY...
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7. ZONE WIRING The ID2 can be wired with up to 8 separate radial circuits each with 15 devices per circuit. It may also be wired as a single loop.
7.1 Specific device wiring instructions All products will come with their own wiring instructions. This should be used when connecting a product. But as a general guideline, here are the connection details of most Zeta Addressable products. 7.1.1 CP3/AD Manual Call Point The CP3/AD call point has a built in isolator which can be wired in circuit or not used.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N Deep Base MKII-CB/D Common Base MKII-CB 7.1.3 ZAI - MI Input Module The end of line resistor value is 20K and the trigger resistor value is 1 K .
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7.1.5 ZASC – MI Sounder Control Module The ZASC requires an external 24vdc power supply (as shown in the above diagram). The EOL for the sounder circuit is 10KΩ. When using the ZASC make sure the PSU being used has a fault output relay, so that in the event of a power supply fault it is reported to the control panel.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7.1.7 Xtratone Sounder/Sounder Flasher The Xtratone sounder or sounder flasher is a wall mount sounder. The programming of the sounder is done via the D.I.L switch mounted on the inside (front). It may also be programmed via the handheld programming tool.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7.1.9 Addressable Remote LED Indicator Ceiling Mount (MKII-ARL/C) Wall Mount (MKII-ARL/W) There are two versions of the remote LED, Wall mounted and Ceiling mounted. The ceiling mounted version requires a standard detector base.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7.2 Setting the device zone & ID (detectors, call points & sounders) The ID2 divides the loop addresses into zones and Ids. The panel translates the address into a zone and ID. Each zone starts with ID1, in order to simplify the addressing.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 7.3 LOOP MODE - MAXIMUM LOOP LENGTH RECOMMENDATIONS Some care must be taken when calculating the appropriate cable gauge for the system. The main limitation is that during an alarm condition (maximum current draw), the voltage at all devices must be at least 17 Volts with at least 5V of superimposed data signal.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 8 SOUNDERS The ID2 has two conventional sounder circuits on board. 9. AUXILIARY OUTPUTS 9.1 Auxiliary output wiring Auxiliary Fire Relay (AUX): This is a SELV volt free relay that operates in the alarm condition. It can be connected to emergency lights, local fire fighting equipment such as sprinkler systems, magnetic door holders, air conditioning shut off, etc.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 10. FIELD DEVICE TERMINATION 10.1 Terminating the wiring Figure 6: Cable connections All cables entering the enclosure should have cable glands, which will prevent unwanted openings in the enclosure.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 11 OTHER CONNECTIONS 11.1 Repeater connection The ID2 has an RS485 connection for a serial repeater. The repeaters have full control. Up to 2 repeaters can be powered from the Aux24V DC output on the panel. If 3 or more are to be connected, then they must be powered from external 24V power supplies.
12.1 CONFIGURING THE ZONES 24-09-2012 09:35 Devices Found 12.1.1 FROM A BLANK INFINITY ID2 PANEL 1. After the system has been installed, and the cabling checked and the addresses of Press ENTER to each device set, connect the loop cable to the CIE termination PCB (connection 1-8 as Configure Panel shown in Section 21.1), and power up the system(mains &...
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 12.3 Labelling the Panel and Zones Panel / Zone Text 1. To add a Zone label, go to engineer menu 1and select option 2Panel / Zone Text. Panel...
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N These are the Triggers that will cause the I/O`s relay to operate EG the option ZONAL DETECTOR would cause the I/O`s relay to operate if there is an alarm from a Detector in its Zone.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 12.8.5 CONFIGURING ALARM OUTPUT RESOUND OPERATION Alarm Resound Some installations require the sounders to operate in a certain way to new alarms if the Any New Alarm sirens have been silenced. To Access the settings, go to Engineer menu 1 / Config alarms / Resound .
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 13 ALARM VERIFICATION The ID2 includes an option to use alarm verification. It is intended for use in apartments, and similar buildings, where it is desirable that an alarm from a smoke detector from one apartment (or area) would need to be confirmed before the whole system goes into alarm.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 14 RESTORING THE PANELS DEFAULT SETTINGS Because the ID2 allows several configuration changes, we have also included Misc Settings an option to reset the panel back to its default operation. From Engineer Menu 2, 1: Language Select Option 6 (Misc).
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 15 VIEWING PANEL INFORMATION 15.1 Menu Structure To help locate the different features available, the menu structure of the ID2 panel is shown here. MENU LAYOUT MAIN MENU...
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 15.2 Viewing device status On the ID2, all Zone devices can be viewed from the Main Menu, or viewed & edited from Engineer Menu 1. Enter Engineer menu 1 as described above, and select option 1...
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 15.4 Using the event log The ID2 has a 1000 entry event log. In the event of the log View Event Log being full, it will wrap around, and overwrite the earliest entries.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 16. THE FIRE ALARM CONDITION 16.1 Viewing a fire alarm event The way the ID2 panel shows fire alarm information has been changed slightly from previous versions of the panel.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 17. DISABLEMENT On the ID2, there are 2 disablement options. A whole zone of devices can be disabled, or an individual device in a zone can be disabled. Both types of disablement can be used at the same time if required.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 17.3 Device disablement The ID2 panel can also disable individual devices (detector, Optical Normal call point, sounder or interface). To do this, enter ENGINEER Device Disabled MENU 1 and select ID DEVICE. Select the required device, them...
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 18. TEST MODE 18.1 Why use test mode To aid commissioning and assist routine maintenance check, a silent, non-latching ‘one man test’ facility is available. When a detector or manual call point is triggered on any zone in Test, the Device will light it`s LED, When the smoke has cleared, or the call point has been reset, the LED will turn out.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 19. GENERAL FAULT FINDING On the ID2 panel, Faults are divided into 2 types, “Faults” and “Device Faults”. Device Faults are any fault associated with a particular Device on the system. Faults are everything else, EG, power supply etc. In the event of multiple faults, the Faults are grouped together first, followed by the device faults.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 19.4 Supply faults FAULT MESSAGE Caused by Remedy BATTERY FAULT Loss of Battery power Check “battery fuse 2A” is intact. Check that battery connections are secure POWER SUPPLY FAULT Loss of Mains power Check that main power is present.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL 1.N & LOOP O.N 19.7 System fault A system fault is an abnormal microprocessor running condition due to various unexpected phenomena. This will result in the panel attempting to correct itself. Should this fault occur, the System Fault LED, General Fault LED, General Fault relay and fault internal buzzer will be constantly active until the control panel is reset.
Zeta Fyreye MKII Input Unit 1.0 mA 3.6 mA Zeta Fyreye MKII Input Output Unit 1.0 mA 3.6 mA Zeta Fyreye MKII Input Output Unit – mains switching 1.3 mA 2.9 mA Zeta Fyreye MKII Sounder Control Module 0.6 mA 0.8 mA Zone Fyreye MKII Zone Monitor Unit 3.5 mA...
20.3 Example battery calculation A system comprises of a 4 zone Infinity ID2 panel, with 10 sounder-flasher bases, 1 call point, 1 Wall sounder flasher (xtratone), and one I/O per zone and the required standby is 24 hours. It will need to operate in alarm for ½...