Multi V 5 Cooling Only General Information 1. Model Line-up & External Appearance 220V CHASSIS Model Name Model ARUV096BTE5 ARUV121BTE5 ARUV144BTE5 ARUV168BTE5 ARUV192BTE5 ARUV216BTE5 ARUV241BTE5 ARUV264BTE5 ARUV288BTE5 ARUV312BTE5 ARUV336BTE5 ARUV360BTE5 ARUV384BTE5 ARUV408BTE5 ARUV432BTE5 ARUV456BTE5 ARUV480BTE5 ARUV504BTE5 ARUV530BTE5 ARUV554BTE5 ARUV578BTE5 ARUV603BTE5 ARUV626BTE5 ARUV650BTE5...
Page 5
Multi V 5 Cooling Only General Information 1. Model Line-up & External Appearance 460V CHASSIS Model Name Model ARUV096DTE5 ARUV121DTE5 ARUV144DTE5 ARUV168DTE5 ARUV192DTE5 ARUV216DTE5 ARUV241DTE5 ARUV264DTE5 ARUV288DTE5 ARUV312DTE5 ARUV336DTE5 ARUV360DTE5 ARUV384DTE5 ARUV408DTE5 ARUV432DTE5 ARUV456DTE5 ARUV480DTE5 ARUV504DTE5 ARUV530DTE5 ARUV554DTE5 ARUV578DTE5 ARUV603DTE5 ARUV626DTE5 ARUV650DTE5...
Page 6
Multi V 5 Cooling Only General Information 2. Combination of Outdoor Units 220V Module(RT) Number of Model Name Units ARUV096BTE5 ARUV121BTE5 ARUV144BTE5 ARUV168BTE5 ARUV192BTE5 ARUV216BTE5 ARUV241BTE5 ARUV264BTE5 ARUV288BTE5 ARUV312BTE5 ARUV336BTE5 ARUV360BTE5 ARUV384BTE5 ARUV408BTE5 ARUV432BTE5 ARUV456BTE5 ARUV480BTE5 ARUV504BTE5 ARUV530BTE5 ARUV554BTE5 ARUV578BTE5 ARUV603BTE5 ARUV626BTE5...
Multi V 5 Cooling Only General Information 2. Combination of Outdoor Units 460V Module(RT) Number of Model Name Units ARUV096DTE5 ARUV121DTE5 ARUV144DTE5 ARUV168DTE5 ARUV192DTE5 ARUV216DTE5 ARUV241DTE5 ARUV264DTE5 ARUV288DTE5 ARUV312DTE5 ARUV336DTE5 ARUV360DTE5 ARUV384DTE5 ARUV408DTE5 ARUV432DTE5 ARUV456DTE5 ARUV480DTE5 ARUV504DTE5 ARUV530DTE5 ARUV554DTE5 ARUV578DTE5 ARUV603DTE5 ARUV626DTE5...
Page 8
Multi V 5 Cooling Only General Information 3. Nomenclature Model Name Signification Multi V System with Outdoor Unit using R410A ARU : Global line-up Combination of Inverter Type and Cooling Only, Heat Pump or Heat Recovery V : Inverter, Cooling Only Total Cooling capacity in Btu/h unit EX) 144kBtu/h '144', 96kBtu/h...
Page 9
Multi V 5 Cooling Only General Information 4. Indoor Unit and Outdoor Unit Capacity Index 4.1 Indoor Unit Selection See the indoor unit capacity tables for given Indoor and Outdoor temperature Select the unit whose capacity is the nearest to or bigger than given load. Note Individual Indoor Unit capacity is subject to change by combination.
Page 10
Multi V 5 Cooling Only General Information 4. Indoor Unit and Outdoor Unit Capacity Index Indoor Unit Combination Ratio Outdoor Unit Capacity(RT) 100% 110% 120% 130% 160% 200% 123.1 147.7 172.3 197.0 221.6 246.2 270.8 295.4 320.1 126.6 151.9 177.2 202.6 227.9 253.2...
Page 11
Cooling Only Outdoor Units Multi V 5 1.Specifications 2.Dimensions 3.Piping Diagrams 4.Wiring Diagrams 5.Field Wiring 6.Electric Characteristics 7.Capacity Tables 8.Capacity Correction Factor 9.Operation Limits 10.Sound Levels 11.Accessories...
Page 12
Multi V 5 Cooling Only Outdoor Units 1. Specifications 1.1 220V Combination Unit ARUV096BTE5 ARUV121BTE5 ARUV096BTE5 ARUV121BTE5 Model Name Independent Unit Btu/h 96,000 120,000 Cooling (Norminal) 28.1 35.2 Capacity Btu/h 92,000 114,000 Cooling (Rated) 27.0 33.4 Cooling (Norminal) 5.90 8.51 Input Cooling (Rated) 5.49...
Page 13
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV096BTE5 ARUV121BTE5 ARUV096BTE5 ARUV121BTE5 Model Name Independent Unit Refigerant name R410A R410A 10.0 10.0 Refigerant Precharged Amount 22.0 22.0 Control Electronic Expansion Valve Electronic Expansion Valve 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz...
Page 14
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV144BTE5 ARUV168BTE5 ARUV144BTE5 ARUV168BTE5 Model Name Independent Unit Btu/h 144,000 168,000 Cooling (Norminal) 42.2 49.2 Capacity Btu/h 138,000 160,000 Cooling (Rated) 40.4 46.9 Cooling (Norminal) 10.32 12.39 Input Cooling (Rated) 9.65 10.20 EER (Norminal)
Page 15
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV144BTE5 ARUV168BTE5 ARUV144BTE5 ARUV168BTE5 Model Name Independent Unit 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60 Number of maxmum connectable indoor units 23(35) 26(40) Note...
Page 16
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV192BTE5 ARUV216BTE5 ARUV192BTE5 ARUV216BTE5 Model Name Independent Unit Btu/h 192,000 216,000 Cooling (Norminal) 56.3 63.3 Capacity Btu/h 184,000 206,000 Cooling (Rated) 53.9 60.4 Cooling (Norminal) 13.91 15.54 Input Cooling (Rated) 11.85 14.55 EER (Norminal)
Page 17
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV192BTE5 ARUV216BTE5 ARUV192BTE5 ARUV216BTE5 Model Name Independent Unit 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60 Number of maxmum connectable indoor units 29(45) 32(50) Note...
Page 18
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV241BTE5 ARUV264BTE5 ARUV241BTE5 ARUV264BTE5 Model Name Independent Unit Btu/h 240,000 264,000 Cooling (Norminal) 70.3 77.4 Capacity Btu/h 222,000 252,000 Cooling (Rated) 65.1 73.9 Cooling (Norminal) 19.20 22.24 Input Cooling (Rated) 17.40 20.80 EER (Norminal)
Page 19
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV241BTE5 ARUV264BTE5 ARUV241BTE5 ARUV264BTE5 Model Name Independent Unit 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60 Number of maxmum connectable indoor units 35(44) 39(48) Note...
Page 20
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV288BTE5 ARUV312BTE5 ARUV168BTE5 ARUV192BTE5 Model Name ARUV121BTE5 ARUV121BTE5 Independent Unit Btu/h 288,000 312,000 Cooling (Norminal) 84.4 91.5 Capacity Btu/h 274,000 298,000 Cooling (Rated) 80.3 87.3 Cooling (Norminal) 20.90 22.42 Input Cooling (Rated) 18.06...
Page 21
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV288BTE5 ARUV312BTE5 ARUV168BTE5 ARUV192BTE5 Model Name ARUV121BTE5 ARUV121BTE5 Independent Unit Refigerant name R410A R410A 23.0 24.0 Refigerant Precharged Amount 50.7 52.9 Control Electronic Expansion Valve Electronic Expansion Valve 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz...
Page 22
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV336BTE5 ARUV360BTE5 ARUV216BTE5 ARUV241BTE5 Model Name ARUV121BTE5 ARUV121BTE5 Independent Unit Btu/h 336,000 360,000 Cooling (Norminal) 98.5 105.5 Capacity Btu/h 320,000 336,000 Cooling (Rated) 93.8 98.5 Cooling (Norminal) 24.05 27.71 Input Cooling (Rated) 22.41...
Page 23
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV336BTE5 ARUV360BTE5 ARUV216BTE5 ARUV241BTE5 Model Name ARUV121BTE5 ARUV121BTE5 Independent Unit Refigerant name R410A R410A 24.0 26.0 Refigerant Precharged Amount 52.9 57.3 Control Electronic Expansion Valve Electronic Expansion Valve 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz...
Page 24
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV384BTE5 ARUV408BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV144BTE5 ARUV168BTE5 Independent Unit Btu/h 384,000 408,000 Cooling (Norminal) 112.5 119.5 Capacity Btu/h 360,000 382,000 Cooling (Rated) 105.5 112.0 Cooling (Norminal) 29.52 31.59 Input Cooling (Rated) 27.05...
Page 25
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV384BTE5 ARUV408BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV144BTE5 ARUV168BTE5 Independent Unit 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60 Number of maxmum connectable indoor units 55(64) 58(64) Note...
Page 26
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV432BTE5 ARUV456BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV192BTE5 ARUV216BTE5 Independent Unit Btu/h 432,000 456,000 Cooling (Norminal) 126.6 133.6 Capacity Btu/h 406,000 428,000 Cooling (Rated) 119.0 125.5 Cooling (Norminal) 33.11 34.74 Input Cooling (Rated) 29.25...
Page 27
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV432BTE5 ARUV456BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV192BTE5 ARUV216BTE5 Independent Unit 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60 Number of maxmum connectable indoor units 61(64) Note 1.
Page 28
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV480BTE5 ARUV504BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV144BTE5 Independent Unit ARUV121BTE5 Btu/h 480,000 504,000 Cooling (Norminal) 140.6 147.7 Capacity Btu/h 444,000 474,000 Cooling (Rated) 130.2 138.9 Cooling (Norminal) 38.40 38.03 Input Cooling (Rated)
Page 29
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV480BTE5 ARUV504BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV144BTE5 Independent Unit ARUV121BTE5 Refigerant name R410A R410A 32.0 39.0 Refigerant Precharged Amount 70.5 86.0 Control Electronic Expansion Valve Electronic Expansion Valve 220-240, 3, 50 220-240, 3, 50 Power Supply...
Page 30
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV530BTE5 ARUV554BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV168BTE5 ARUV192BTE5 Independent Unit ARUV121BTE5 ARUV121BTE5 Btu/h 528,000 552,000 Cooling (Norminal) 154.7 161.8 Capacity Btu/h 496,000 520,000 Cooling (Rated) 145.4 152.4 Cooling (Norminal) 40.10 41.62 Input...
Page 31
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV530BTE5 ARUV554BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV168BTE5 ARUV192BTE5 Independent Unit ARUV121BTE5 ARUV121BTE5 Refigerant name R410A R410A 39.0 40.0 Refigerant Precharged Amount 86.0 88.2 Control Electronic Expansion Valve Electronic Expansion Valve 220-240, 3, 50 220-240, 3, 50 Power Supply...
Page 32
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV578BTE5 ARUV603BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV216BTE5 ARUV241BTE5 Independent Unit ARUV121BTE5 ARUV121BTE5 Btu/h 576,000 600,000 Cooling (Norminal) 168.8 175.8 Capacity Btu/h 542,000 558,000 Cooling (Rated) 158.9 163.6 Cooling (Norminal) 43.25 46.91 Input...
Page 33
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV578BTE5 ARUV603BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV216BTE5 ARUV241BTE5 Independent Unit ARUV121BTE5 ARUV121BTE5 Refigerant name R410A R410A 40.0 42.0 Refigerant Precharged Amount 88.2 92.6 Control Electronic Expansion Valve Electronic Expansion Valve 220-240, 3, 50 220-240, 3, 50 Power Supply...
Page 34
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV626BTE5 ARUV650BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV144BTE5 ARUV168BTE5 Btu/h 624,000 648,000 Cooling (Norminal) 182.8 189.8 Capacity Btu/h 582,000 604,000 Cooling (Rated) 170.6 177.1 Cooling (Norminal) 48.72 50.79 Input...
Page 35
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV626BTE5 ARUV650BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV144BTE5 ARUV168BTE5 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60 Number of maxmum connectable indoor units Note 1.
Page 36
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV674BTE5 ARUV698BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV192BTE5 ARUV216BTE5 Btu/h 672,000 696,000 Cooling (Norminal) 196.9 203.9 Capacity Btu/h 628,000 650,000 Cooling (Rated) 184.1 190.6 Cooling (Norminal) 52.31 53.94 Input...
Page 37
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV674BTE5 ARUV698BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV192BTE5 ARUV216BTE5 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60 Number of maxmum connectable indoor units Note 1.
Page 38
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV723BTE5 ARUV747BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV241BTE5 ARUV144BTE5 ARUV121BTE5 Btu/h 720,000 744,000 Cooling (Norminal) 210.9 218.0 Capacity Btu/h 666,000 696,000 Cooling (Rated) 195.3 204.0 Cooling (Norminal) 57.60 57.23 Input...
Page 39
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV723BTE5 ARUV747BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV241BTE5 ARUV144BTE5 ARUV121BTE5 Refigerant name R410A R410A 48.0 55.0 Refigerant Precharged Amount 105.8 121.3 Control Electronic Expansion Valve Electronic Expansion Valve 220-240, 3, 50 220-240, 3, 50 Power Supply...
Page 40
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV771BTE5 ARUV795BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV168BTE5 ARUV192BTE5 ARUV121BTE5 ARUV121BTE5 Btu/h 768,000 792,000 Cooling (Norminal) 225.0 232.1 Capacity Btu/h 718,000 742,000 Cooling (Rated) 210.5 217.5 Cooling (Norminal) 59.30 60.82...
Page 41
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV771BTE5 ARUV795BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV168BTE5 ARUV192BTE5 ARUV121BTE5 ARUV121BTE5 Refigerant name R410A R410A 55.0 56.0 Refigerant Precharged Amount 121.3 123.5 Control Electronic Expansion Valve Electronic Expansion Valve 220-240, 3, 50 220-240, 3, 50...
Page 42
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV819BTE5 ARUV844BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV216BTE5 ARUV241BTE5 ARUV121BTE5 ARUV121BTE5 Btu/h 816,000 840,000 Cooling (Norminal) 239.1 246.1 Capacity Btu/h 764,000 780,000 Cooling (Rated) 224.0 228.7 Cooling (Norminal) 62.45 66.11...
Page 43
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV819BTE5 ARUV844BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV216BTE5 ARUV241BTE5 ARUV121BTE5 ARUV121BTE5 Refigerant name R410A R410A 56.0 58.0 Refigerant Precharged Amount 123.5 127.9 Control Electronic Expansion Valve Electronic Expansion Valve 220-240, 3, 50 220-240, 3, 50...
Page 44
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV867BTE5 ARUV891BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV241BTE5 ARUV241BTE5 ARUV144BTE5 ARUV168BTE5 Btu/h 864,000 888,000 Cooling (Norminal) 253.1 260.1 Capacity Btu/h 804,000 826,000 Cooling (Rated) 235.7 242.2 Cooling (Norminal) 67.92 69.99...
Page 45
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV867BTE5 ARUV891BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV241BTE5 ARUV241BTE5 ARUV144BTE5 ARUV168BTE5 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60 Number of maxmum connectable indoor units Note 1.
Page 46
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV915BTE5 ARUV939BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV241BTE5 ARUV241BTE5 ARUV192BTE5 ARUV216BTE5 Btu/h 912,000 936,000 Cooling (Norminal) 267.2 274.2 Capacity Btu/h 850,000 872,000 Cooling (Rated) 249.2 255.7 Cooling (Norminal) 71.51 73.14...
Page 47
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV915BTE5 ARUV939BTE5 ARUV241BTE5 ARUV241BTE5 Model Name ARUV241BTE5 ARUV241BTE5 Independent Unit ARUV241BTE5 ARUV241BTE5 ARUV192BTE5 ARUV216BTE5 220-240, 3, 50 220-240, 3, 50 Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60 Number of maxmum connectable indoor units Note 1.
Page 48
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV964BTE5 ARUV241BTE5 Model Name ARUV241BTE5 Independent Unit ARUV241BTE5 ARUV241BTE5 Btu/h 960,000 Cooling (Norminal) 281.2 Capacity Btu/h 888,000 Cooling (Rated) 260.4 Cooling (Norminal) 76.80 Input Cooling (Rated) 69.60 EER (Norminal) 3.66 EER (Rated) 3.74...
Page 49
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV964BTE5 ARUV241BTE5 Model Name ARUV241BTE5 Independent Unit ARUV241BTE5 ARUV241BTE5 220-240, 3, 50 Power Supply V, Ø, Hz 220, 3, 60 Number of maxmum connectable indoor units Note 1. Due to our policy of innovation some specifications may be changed without notification. 2.
Multi V 5 Cooling Only Outdoor Units 1. Specifications 1.2 460V Combination Unit ARUV096DTE5 ARUV121DTE5 ARUV096DTE5 ARUV121DTE5 Model Name Independent Unit Btu/h 96,000 120,000 Cooling (Norminal) 28.1 35.2 Capacity Btu/h 92,000 114,000 Cooling (Rated) 27.0 33.4 Cooling (Norminal) 5.90 8.51 Input Cooling (Rated) 5.49...
Page 51
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV096DTE5 ARUV121DTE5 ARUV096DTE5 ARUV121DTE5 Model Name Independent Unit Refigerant name R410A R410A 10.0 10.0 Refigerant Precharged Amount 22.0 22.0 Control Electronic Expansion Valve Electronic Expansion Valve Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60 Number of maxmum connectable indoor units...
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV144DTE5 ARUV168DTE5 ARUV144DTE5 ARUV168DTE5 Model Name Independent Unit Btu/h 144,000 168,000 Cooling (Norminal) 42.2 49.2 Capacity Btu/h 138,000 160,000 Cooling (Rated) 40.4 46.9 Cooling (Norminal) 10.32 12.39 Input Cooling (Rated) 9.65 10.20 EER (Norminal)
Page 53
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV144DTE5 ARUV168DTE5 ARUV144DTE5 ARUV168DTE5 Model Name Independent Unit Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60 Number of maxmum connectable indoor units 23(35) 26(40) Note 1. Due to our policy of innovation some specifications may be changed without notification. 2.
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV192DTE5 ARUV216DTE5 ARUV192DTE5 ARUV216DTE5 Model Name Independent Unit Btu/h 192,000 216,000 Cooling (Norminal) 56.3 63.3 Capacity Btu/h 184,000 206,000 Cooling (Rated) 53.9 60.4 Cooling (Norminal) 13.91 15.54 Input Cooling (Rated) 11.85 14.55 EER (Norminal)
Page 55
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV192DTE5 ARUV216DTE5 ARUV192DTE5 ARUV216DTE5 Model Name Independent Unit Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60 Number of maxmum connectable indoor units 29(45) 32(50) Note 1. Due to our policy of innovation some specifications may be changed without notification. 2.
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV241DTE5 ARUV264DTE5 ARUV241DTE5 ARUV264DTE5 Model Name Independent Unit Btu/h 240,000 264,000 Cooling (Norminal) 70.3 77.4 Capacity Btu/h 222,000 252,000 Cooling (Rated) 65.1 73.9 Cooling (Norminal) 19.20 22.24 Input Cooling (Rated) 17.40 20.80 EER (Norminal)
Page 57
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV241DTE5 ARUV264DTE5 ARUV241DTE5 ARUV264DTE5 Model Name Independent Unit Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60 Number of maxmum connectable indoor units 35(44) 39(48) Note 1. Due to our policy of innovation some specifications may be changed without notification. 2.
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV288DTE5 ARUV312DTE5 ARUV168DTE5 ARUV192DTE5 Model Name ARUV121DTE5 ARUV121DTE5 Independent Unit Btu/h 288,000 312,000 Cooling (Norminal) 84.4 91.5 Capacity Btu/h 274,000 298,000 Cooling (Rated) 80.3 87.3 Cooling (Norminal) 20.90 22.42 Input Cooling (Rated) 18.06...
Page 59
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV288DTE5 ARUV312DTE5 ARUV168DTE5 ARUV192DTE5 Model Name ARUV121DTE5 ARUV121DTE5 Independent Unit Refigerant name R410A R410A 23.0 24.0 Refigerant Precharged Amount 50.7 52.9 Control Electronic Expansion Valve Electronic Expansion Valve Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60...
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV336DTE5 ARUV360DTE5 ARUV216DTE5 ARUV241DTE5 Model Name ARUV121DTE5 ARUV121DTE5 Independent Unit Btu/h 336,000 360,000 Cooling (Norminal) 98.5 105.5 Capacity Btu/h 320,000 336,000 Cooling (Rated) 93.8 98.5 Cooling (Norminal) 24.05 27.71 Input Cooling (Rated) 22.41...
Page 61
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV336DTE5 ARUV360DTE5 ARUV216DTE5 ARUV241DTE5 Model Name ARUV121DTE5 ARUV121DTE5 Independent Unit Refigerant name R410A R410A 24.0 26.0 Refigerant Precharged Amount 52.9 57.3 Control Electronic Expansion Valve Electronic Expansion Valve Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60...
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV384DTE5 ARUV408DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV144DTE5 ARUV168DTE5 Independent Unit Btu/h 384,000 408,000 Cooling (Norminal) 112.5 119.5 Capacity Btu/h 360,000 382,000 Cooling (Rated) 105.5 112.0 Cooling (Norminal) 29.52 31.59 Input Cooling (Rated) 27.05...
Page 63
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV384DTE5 ARUV408DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV144DTE5 ARUV168DTE5 Independent Unit Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60 Number of maxmum connectable indoor units 55(64) 58(64) Note 1.
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV432DTE5 ARUV456DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV192DTE5 ARUV216DTE5 Independent Unit Btu/h 432,000 456,000 Cooling (Norminal) 126.6 133.6 Capacity Btu/h 406,000 428,000 Cooling (Rated) 119.0 125.5 Cooling (Norminal) 33.11 34.74 Input Cooling (Rated) 29.25...
Page 65
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV432DTE5 ARUV456DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV192DTE5 ARUV216DTE5 Independent Unit Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60 Number of maxmum connectable indoor units 61(64) Note 1.
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV480DTE5 ARUV504DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV144DTE5 Independent Unit ARUV121DTE5 Btu/h 480,000 504,000 Cooling (Norminal) 140.6 147.7 Capacity Btu/h 444,000 474,000 Cooling (Rated) 130.2 138.9 Cooling (Norminal) 38.40 38.03 Input Cooling (Rated)
Page 67
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV480DTE5 ARUV504DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV144DTE5 Independent Unit ARUV121DTE5 Refigerant name R410A R410A 32.0 39.0 Refigerant Precharged Amount 70.5 86.0 Control Electronic Expansion Valve Electronic Expansion Valve Power Supply V, Ø, Hz 460, 3, 60...
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV530DTE5 ARUV554DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV168DTE5 ARUV192DTE5 Independent Unit ARUV121DTE5 ARUV121DTE5 Btu/h 528,000 552,000 Cooling (Norminal) 154.7 161.8 Capacity Btu/h 496,000 520,000 Cooling (Rated) 145.4 152.4 Cooling (Norminal) 40.10 41.62 Input...
Page 69
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV530DTE5 ARUV554DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV168DTE5 ARUV192DTE5 Independent Unit ARUV121DTE5 ARUV121DTE5 Refigerant name R410A R410A 39.0 40.0 Refigerant Precharged Amount 86.0 88.2 Control Electronic Expansion Valve Electronic Expansion Valve Power Supply V, Ø, Hz 460, 3, 60...
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV578DTE5 ARUV603DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV216DTE5 ARUV241DTE5 Independent Unit ARUV121DTE5 ARUV121DTE5 Btu/h 576,000 600,000 Cooling (Norminal) 168.8 175.8 Capacity Btu/h 542,000 558,000 Cooling (Rated) 158.9 163.6 Cooling (Norminal) 43.25 46.91 Input...
Page 71
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV578DTE5 ARUV603DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV216DTE5 ARUV241DTE5 Independent Unit ARUV121DTE5 ARUV121DTE5 Refigerant name R410A R410A 40.0 42.0 Refigerant Precharged Amount 88.2 92.6 Control Electronic Expansion Valve Electronic Expansion Valve Power Supply V, Ø, Hz 460, 3, 60...
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV626DTE5 ARUV650DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV144DTE5 ARUV168DTE5 Btu/h 624,000 648,000 Cooling (Norminal) 182.8 189.8 Capacity Btu/h 582,000 604,000 Cooling (Rated) 170.6 177.1 Cooling (Norminal) 48.72 50.79 Input...
Page 73
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV626DTE5 ARUV650DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV144DTE5 ARUV168DTE5 Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60 Number of maxmum connectable indoor units Note 1.
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV674DTE5 ARUV698DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV192DTE5 ARUV216DTE5 Btu/h 672,000 696,000 Cooling (Norminal) 196.9 203.9 Capacity Btu/h 628,000 650,000 Cooling (Rated) 184.1 190.6 Cooling (Norminal) 52.31 53.94 Input...
Page 75
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV674DTE5 ARUV698DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV192DTE5 ARUV216DTE5 Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60 Number of maxmum connectable indoor units Note 1.
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV723DTE5 ARUV747DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV241DTE5 ARUV144DTE5 ARUV121DTE5 Btu/h 720,000 744,000 Cooling (Norminal) 210.9 218.0 Capacity Btu/h 666,000 696,000 Cooling (Rated) 195.3 204.0 Cooling (Norminal) 57.60 57.23 Input...
Page 77
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV723DTE5 ARUV747DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV241DTE5 ARUV144DTE5 ARUV121DTE5 Refigerant name R410A R410A 48.0 55.0 Refigerant Precharged Amount 105.8 121.3 Control Electronic Expansion Valve Electronic Expansion Valve Power Supply V, Ø, Hz 460, 3, 60...
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV771DTE5 ARUV795DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV168DTE5 ARUV192DTE5 ARUV121DTE5 ARUV121DTE5 Btu/h 768,000 792,000 Cooling (Norminal) 225.0 232.1 Capacity Btu/h 718,000 742,000 Cooling (Rated) 210.5 217.5 Cooling (Norminal) 59.30 60.82...
Page 79
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV771DTE5 ARUV795DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV168DTE5 ARUV192DTE5 ARUV121DTE5 ARUV121DTE5 Refigerant name R410A R410A 55.0 56.0 Refigerant Precharged Amount 121.3 123.5 Control Electronic Expansion Valve Electronic Expansion Valve Power Supply V, Ø, Hz...
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV819DTE5 ARUV844DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV216DTE5 ARUV241DTE5 ARUV121DTE5 ARUV121DTE5 Btu/h 816,000 840,000 Cooling (Norminal) 239.1 246.1 Capacity Btu/h 764,000 780,000 Cooling (Rated) 224.0 228.7 Cooling (Norminal) 62.45 66.11...
Page 81
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV819DTE5 ARUV844DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV216DTE5 ARUV241DTE5 ARUV121DTE5 ARUV121DTE5 Refigerant name R410A R410A 56.0 58.0 Refigerant Precharged Amount 123.5 127.9 Control Electronic Expansion Valve Electronic Expansion Valve Power Supply V, Ø, Hz...
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV867DTE5 ARUV891DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV241DTE5 ARUV241DTE5 ARUV144DTE5 ARUV168DTE5 Btu/h 864,000 888,000 Cooling (Norminal) 253.1 260.1 Capacity Btu/h 804,000 826,000 Cooling (Rated) 235.7 242.2 Cooling (Norminal) 67.92 69.99...
Page 83
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV867DTE5 ARUV891DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV241DTE5 ARUV241DTE5 ARUV144DTE5 ARUV168DTE5 Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60 Number of maxmum connectable indoor units Note 1.
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV915DTE5 ARUV939DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV241DTE5 ARUV241DTE5 ARUV192DTE5 ARUV216DTE5 Btu/h 912,000 936,000 Cooling (Norminal) 267.2 274.2 Capacity Btu/h 850,000 872,000 Cooling (Rated) 249.2 255.7 Cooling (Norminal) 71.51 73.14...
Page 85
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV915DTE5 ARUV939DTE5 ARUV241DTE5 ARUV241DTE5 Model Name ARUV241DTE5 ARUV241DTE5 Independent Unit ARUV241DTE5 ARUV241DTE5 ARUV192DTE5 ARUV216DTE5 Power Supply V, Ø, Hz 460, 3, 60 460, 3, 60 Number of maxmum connectable indoor units Note 1.
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV964DTE5 ARUV241DTE5 Model Name ARUV241DTE5 Independent Unit ARUV241DTE5 ARUV241DTE5 Btu/h 960,000 Cooling (Norminal) 281.2 Capacity Btu/h 888,000 Cooling (Rated) 260.4 Cooling (Norminal) 76.80 Input Cooling (Rated) 69.60 EER (Norminal) 3.66 EER (Rated) 3.74...
Page 87
Multi V 5 Cooling Only Outdoor Units 1. Specifications Combination Unit ARUV964DTE5 ARUV241DTE5 Model Name ARUV241DTE5 Independent Unit ARUV241DTE5 ARUV241DTE5 Power Supply V, Ø, Hz 460, 3, 60 Number of maxmum connectable indoor units Note 1. Due to our policy of innovation some specifications may be changed without notification. 2.
Page 88
Multi V 5 Cooling Only Outdoor Units 2. Dimensions ARUV096BTE5 / ARUV121BTE5 ARUV096DTE5 / ARUV121DTE5...
Page 89
Multi V 5 Cooling Only Outdoor Units 2. Dimensions ARUV144BTE5 / ARUV168BTE5 / ARUV192BTE5 / ARUV216BTE5 ARUV241BTE5 / ARUV264BTE5 ARUV144DTE5 / ARUV168DTE5 / ARUV192DTE5 / ARUV216DTE5 ARUV241DTE5 / ARUV264DTE5...
Page 90
Multi V 5 Cooling Only Outdoor Units 3. Wiring Diagrams 3.1 220V 3.1.1 8 / 10 RT (UXA, 1 Comp)
Page 91
Multi V 5 Cooling Only Outdoor Units 3. Wiring Diagrams 3.1.2 12 RT (UXB, 1 Comp)
Page 92
Multi V 5 Cooling Only Outdoor Units 3. Wiring Diagrams 3.1.3 14 RT (UXB, 2 Comp)
Page 93
Multi V 5 Cooling Only Outdoor Units 3. Wiring Diagrams 3.1.4 16 / 18 / 20 / 22 RT (UXB, 2 Comp)
Page 94
Multi V 5 Cooling Only Outdoor Units 3. Wiring Diagrams 3.2 460V 3.2.1 8 / 10 RT (UXA, 1 Comp)
Page 95
Multi V 5 Cooling Only Outdoor Units 3. Wiring Diagrams 3.2.2 12 RT (UXB, 1 Comp)
Page 96
Multi V 5 Cooling Only Outdoor Units 3. Wiring Diagrams 3.2.3 14 RT (UXB, 2 Comp)
Page 97
Multi V 5 Cooling Only Outdoor Units 3. Wiring Diagrams 3.2.4 16 / 18 / 20 / 22 RT (UXB, 2 Comp)
Page 98
Multi V 5 Cooling Only Outdoor Units 4. Piping Diagrams 4.1 8 / 10 / 12 RT (1 Comp) Cooling / Oil Return Operation High Temperature High Pressure Gas High Temperature High Pressure Liquid Low Temperature Low Pressure Gas Indoor Heat Exchanger Indoor Heat Exchanger Electronic Electronic...
Page 99
Multi V 5 Cooling Only Outdoor Units 4. Piping Diagrams 4.2 14 / 16 / 18 / 20 / 22 RT (2 Comp) Cooling / Oil Return Operation...
Page 100
Multi V 5 Cooling Only Outdoor Units 5. Field Wiring 5.1 220V Example Connection of Power & Communication Cable Single Outdoor Unit Outdoor Voltage range(V) Frequency Power supply Outdoor Indoor (3Ø 3wires) 60Hz [Outdoor Unit] (Main Switch) 50Hz 220-240 220-240 R S T Switch...
Page 101
Multi V 5 Cooling Only Outdoor Units 5. Field Wiring WARNING • Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe). • Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
Page 102
Multi V 5 Cooling Only Outdoor Units 5. Field Wiring 5.2 460V Example Connection of Power & Communication Cable Single Outdoor Unit Outdoor Voltage range(V) Frequency Power supply Outdoor Indoor (3Ø 3wires) 60Hz [Outdoor Unit] (Main Switch) R S T Switch Fuse Indoor...
Page 103
Multi V 5 Cooling Only Outdoor Units 5. Field Wiring Series Outdoor Unit When the power source is connected In series between the units. Outdoor ※ The below System is representative Multi V 5 System. Power supply Actual combination of outdoor unit may be different by product line-up of region. (3Ø...
Page 104
Multi V 5 Cooling Only Outdoor Units 5. Field Wiring WARNING • Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe). • Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
Page 105
Multi V 5 Cooling Only Outdoor Units 6. Electric Characteristics Wiring of Main Power Supply and Equipment Capacity 1. Use a separate power supply for the Outdoor Unit and Indoor Unit. 2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain liquid,etc.) when proceeding with the wiring and connections 3.
Page 106
Multi V 5 Cooling Only Outdoor Units 6. Electric Characteristics ■ 220V Unit Power Supply COMP Model Volts Voltage-range TOCA RLA(Cooling) 8 RT Min.:198, Max.:242 35.7 40.0 11.0 10.5 1.77 10 RT Min.:198, Max.:242 36.0 40.0 11.0 17.2 1.77 12 RT Min.:198, Max.:242 36.4 40.0...
Page 107
Multi V 5 Cooling Only Outdoor Units 6. Electric Characteristics ■ 460V Unit Power Supply COMP Model Volts Voltage-range TOCA RLA(Cooling) 8 RT Min.:414, Max.:506 21.4 24.0 1.20 10 RT Min.:414, Max.:506 25.2 28.0 1.20 12 RT Min.:414, Max.:506 27.3 30.0 10.5 1.80...
Page 108
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables 7.1 Cooling Capacity 7.1.1 Single Unit ARUV096BTE5 / ARUV096DTE5 Cooling Capacity (8RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 27.8 2.50 33.1 3.06 35.5 3.55 36.5 3.62 37.6...
Page 109
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 19.0 1.82 22.6 2.22 26.3 2.63 28.1 2.84 29.9 3.05 33.2 3.40 33.9 3.43 19.0 1.88 22.6 2.31 26.3 2.72 28.1 2.92...
Page 110
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (8RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 13.2 1.23 15.9 1.46 18.4 1.69 19.7 1.83 21.0 1.95 23.5 2.22 26.1 2.48 13.2 1.25 15.9 1.48 18.4...
Page 111
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables ARUV121BTE5 / ARUV121DTE5 Cooling Capacity (10RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 34.9 3.61 41.5 4.41 44.5 5.12 45.8 5.22 47.1 5.26 49.3 5.31 50.6 5.33 34.9...
Page 112
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (10RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 23.8 2.63 28.3 3.20 32.9 3.79 35.2 4.10 37.5 4.40 41.5 4.90 42.4 4.94 23.8 2.71 28.3 3.33 32.9...
Page 113
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (10RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 16.6 1.76 19.9 2.10 23.0 2.43 24.6 2.63 26.3 2.81 29.4 3.20 32.7 3.58 16.6 1.79 19.9 2.13 23.0...
Page 114
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables ARUV144BTE5 / ARUV144DTE5 Cooling Capacity (12RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 41.8 4.38 49.8 5.35 53.3 6.21 54.9 6.33 56.4 6.38 59.1 6.43 60.7 6.46 41.8...
Page 115
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (12RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 28.5 3.19 33.9 3.88 39.5 4.60 42.2 4.97 44.9 5.34 49.8 5.94 50.9 5.99 28.5 3.29 33.9 4.04 39.5...
Page 116
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (12RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 19.9 1.99 23.8 2.36 27.6 2.74 29.5 2.95 31.5 3.16 35.3 3.60 39.2 4.02 19.9 2.02 23.8 2.39 27.6...
Page 117
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables ARUV168BTE5 / ARUV168DTE5 Cooling Capacity (14RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 48.7 5.26 58.0 6.42 62.2 7.45 64.0 7.60 65.8 7.66 68.9 7.72 70.7 7.76 48.7...
Page 118
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (14RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 33.2 3.83 39.5 4.66 46.0 5.52 49.2 5.97 52.4 6.41 58.1 7.14 59.3 7.19 33.2 3.95 39.5 4.85 46.0...
Page 119
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (14RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 23.2 2.38 27.8 2.83 32.2 3.28 34.4 3.54 36.7 3.78 41.1 4.31 45.7 4.82 23.2 2.42 27.8 2.87 32.2...
Page 120
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables ARUV192BTE5 / ARUV192DTE5 Cooling Capacity (16RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 55.8 5.90 66.4 7.21 71.2 8.37 73.2 8.54 75.3 8.60 78.9 8.67 80.9 8.71 55.8...
Page 121
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (16RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 38.0 4.30 45.2 5.23 52.7 6.20 56.3 6.70 59.9 7.20 66.4 8.01 67.9 8.08 38.0 4.44 45.2 5.44 52.7...
Page 122
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (16RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 26.5 2.86 31.8 3.40 36.8 3.94 39.4 4.26 42.0 4.55 47.1 5.18 52.3 5.80 26.5 2.91 31.8 3.45 36.8...
Page 123
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables ARUV216BTE5 / ARUV216DTE5 Cooling Capacity (18RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 62.7 6.59 74.7 8.06 80.0 9.35 82.3 9.54 84.6 9.61 88.7 9.69 91.0 9.73 62.7...
Page 124
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (18RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 42.7 4.80 50.9 5.84 59.2 6.93 63.3 7.48 67.4 8.04 74.7 8.95 76.3 9.02 42.7 4.96 50.9 6.08 59.2...
Page 125
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (18RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 29.8 3.04 35.7 3.61 41.4 4.19 44.3 4.52 47.2 4.84 52.9 5.51 58.8 6.16 29.8 3.09 35.7 3.66 41.4...
Page 126
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables ARUV241BTE5 / ARUV241DTE5 Cooling Capacity (20RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 69.6 8.14 82.9 9.95 88.9 11.55 91.4 11.78 94.0 11.88 98.5 11.97 101.0 12.02 69.6 8.35 82.9 10.31 88.9 12.02 91.4 12.10 94.0 12.20 98.5 12.29 101.0 12.40...
Page 127
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (20RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 47.5 5.93 56.5 7.21 65.8 8.56 70.3 9.25 74.8 9.94 83.0 11.06 84.8 11.15 47.5 6.12 56.5 7.51 65.8...
Page 128
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (20RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 33.1 3.76 39.7 4.47 45.9 5.18 49.2 5.60 52.5 5.98 58.8 6.81 65.3 7.62 33.1 3.82 39.7 4.53 45.9...
Page 129
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables ARUV264BTE5 / ARUV264DTE5 Cooling Capacity (22RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 76.7 9.43 91.3 11.53 97.8 13.38 100.7 13.65 103.5 13.76 108.4 13.87 111.3 13.92 76.7 9.67 91.3...
Page 130
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (22RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 52.2 6.87 62.2 8.36 72.4 9.91 77.4 10.71 82.4 11.51 91.3 12.81 93.3 12.91 52.2 7.09 62.2 8.70 72.4 10.25 77.4...
Page 131
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (22RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 36.5 4.35 43.7 5.17 50.6 6.00 54.2 6.48 57.8 6.92 64.7 7.88 71.9 8.81 36.5 4.42 43.7 5.24 50.6...
Page 132
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables 7.1.2 2 Units Combination ARUV288BTE5 / ARUV288DTE5 Cooling Capacity (24RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 83.6 8.87 99.5 10.83 106.7 12.57 109.8 12.82 112.9 12.92 118.2 13.03 121.3 13.09 83.6 9.09 99.5...
Page 133
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (24RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 57.0 6.46 67.8 7.86 78.9 9.31 84.4 10.07 89.9 10.81 99.6 12.04 101.7 12.13 57.0 6.66 67.8 8.18 78.9...
Page 134
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (24RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 39.8 4.14 47.7 4.93 55.2 5.71 59.0 6.17 63.0 6.59 70.5 7.51 78.4 8.40 39.8 4.21 47.7 5.00 55.2...
Page 135
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables ARUV312BTE5 / ARUV312DTE5 Cooling Capacity (26RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 90.7 9.51 107.9 11.62 115.7 13.49 119.0 13.76 122.4 13.86 128.2 13.98 131.5 14.04 90.7 9.75 107.9 12.04 115.7 14.04 119.0 14.13 122.4 14.25 128.2 14.36 131.5 14.49...
Page 136
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (26RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 61.8 6.93 73.5 8.43 85.6 9.99 91.5 10.80 97.4 11.60 107.9 12.91 110.3 13.02 61.8 7.15 73.5 8.77 85.6...
Page 137
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (26RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 43.1 4.62 51.7 5.50 59.8 6.37 64.0 6.89 68.3 7.36 76.5 8.38 85.0 9.38 43.1 4.70 51.7 5.58 59.8...
Page 138
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables ARUV336BTE5 / ARUV336DTE5 Cooling Capacity (28RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 97.6 10.20 116.2 12.47 124.5 14.47 128.1 14.76 131.7 14.87 138.0 15.00 141.6 15.06 97.6 10.46 116.2 12.91 124.5 15.06 128.1 15.15 131.7 15.28 138.0 15.40 141.6 15.54 97.6...
Page 139
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (28RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 66.5 7.43 79.2 9.04 92.1 10.72 98.5 11.58 104.9 12.44 116.2 13.85 118.7 13.96 66.5 7.67 79.2 9.41 92.1...
Page 140
Multi V 5 Cooling Only Outdoor Units 7. Capacity Tables Cooling Capacity (28RT) Indoor air temp. (DB/WB, °C) Combination Outdoor air temp. (DB, °C) 46.4 4.80 55.6 5.71 64.4 6.62 68.9 7.15 73.5 7.65 82.3 8.71 91.5 9.74 46.4 4.88 55.6 5.79 64.4...
Page 219
Multi V 5 Cooling Only Outdoor Units 8. Capacity Correction Factor 8.1 8, 10, 12, 14, 16, 18, 20, 22, 24, 26RT Rate of change in Cooling capacity 0.88 0.86 0.84 0.82 0.90 110 - 0.89 0.88 0.88 0.87 0.86 0.86 0.85 0.84 0.84 0.83 0.83 0.82 100 - 0.90...
Page 220
Multi V 5 Cooling Only Outdoor Units 8. Capacity Correction Factor 8.3 50, 52, 54, 56, 58, 60, 62, 64RT Rate of change in Cooling capacity 0.86 0.84 0.82 0.80 0.77 0.76 0.84 0.83 0.82 0.81 0.80 0.79 0.78 0.77 0.77 0.76 0.75 0.74 110 - 0.90 100 -...
Page 221
Multi V 5 Cooling Only Outdoor Units 8. Capacity Correction Factor Note 1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load under standard conditions.(Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.) 2.
Page 222
Multi V 5 Cooling Only Outdoor Units 8. Capacity Correction Factor Equivalent length Equivalent length * (Cooling) Overall equivalent length =80 m x 0.5 + 40 m = 16RT 80 m * (Heating) Overall equivalent length =80 m x 0.2 + 40 m = Indoor Unit 56 m Gas pipe...
Page 223
Multi V 5 Cooling Only Outdoor Units 9. Operation Limits Cooling Operation 50°C 48°C 45°C 40°C 35°C 30°C 25°C 20°C 15°C 10°C 5°C 0°C -5°C -10°C -15°C 10°C 14°C 15°C 20°C 25°C 27°C 30°C Indoor Temperature(°C WB) Note 1. These figures assume the following operating conditions: Equivalent piping length:7.5m Level difference:0m 2.
Page 224
Multi V 5 Cooling Only Outdoor Units 10. Sound Levels 10.1 Sound Pressure Level Note • Data is valid at free field condition • Data is valid at nominal operating condition • Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed...
Page 229
Multi V 5 Cooling Only Outdoor Units 10. Sound Levels ARUV964BTE5 / ARUV964DTE5 Cooling NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 Approximate Hearing NC-20 NC-15 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
Page 230
Multi V 5 Cooling Only Outdoor Units 10. Sound Levels 10.2 Sound Power Levels Note • Data is valid at diffuse field condition • Data is valid at nominal operating condition • Sound level can be increased in static pressure mode or used air guide. •...
Page 235
Multi V 5 Cooling Only Outdoor Units 10. Sound Levels ARUV964BTE5 / ARUV964DTE5 Cooling NR-90 NR-85 NR-80 NR-75 NR-70 NR-65 NR-60 NR-55 NR-50 NR-45 NR-40 NR-35 NR-30 NR-25 NR-20 1000 2000 4000 8000 Octave Band Center Frequency (Hz)
Page 236
Multi V 5 Cooling Only Outdoor Units 11. Accessories Optional Accessories Name Model ARBLN01621 ARBLN03321 Y branch pipe ARBLN07121 ARBLN14521 ARBLN23220 ARBL054 ARBL057 ARBL104 Header ARBL107 ARBL1010 ARBL2010 ARCNN21 Connection pipe of Outdoor Units ARCNN31 ARCNN41...
Page 237
Cooling Only Installation of Outdoor Units Multi V 5 1.Alternative Refrigerant R410A 2.Select the Best Location 3.Installation Space 4.Lifting Method 5.Installation 6.Refrigerant piping Installation 7.Refrigerant piping system 8.Electrical Wiring 9.Setting Function...
Page 238
Multi V 5 Cooling Only Installation of Outdoor Units 1. Alternative Refrigerant R410A • The refrigerant R410A has the property of higher operating pressure in comparison with R22. Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this characteristic should also be considered during the installation.
Page 239
Multi V 5 Cooling Only Installation of Outdoor Units 2. Select the Best Location Select space for installing outdoor unit, which will meet the following conditions: • No direct thermal radiation from other heat sources • No possibility of annoying neighbors due to noise of unit •...
Page 240
Multi V 5 Cooling Only Installation of Outdoor Units 3. Installation Space 3.1 Individual Installation During the installation of the unit, consider service, inlet, and outlet and acquire the minimum space as shown in the figures below. Side space should be more than 49mm(1-15/16inch) for operating of Auto Dust Removal mode. Case 1 [Unit : mm(inch)] Case 2 [Unit : mm(inch)] Category...
Page 241
Multi V 5 Cooling Only Installation of Outdoor Units 3. Installation Space Case 1 Case 2 Category Installation Space (10mm Side Space 49mm) (Side Space 49mm) No limit for the 10(13/32) height of wall 300(11-13/16) Front Only 2 sides are walls No limit for the height of wall 10(13/32) 300(11-13/16)
Page 242
Multi V 5 Cooling Only Installation of Outdoor Units 4. Lifting Method • When carrying the suspended, unit pass the ropes under the unit and use the two suspension points each at the front and rear. • Always lift the unit with ropes attached at four points so that impact is not applied to the unit. •...
Page 243
Multi V 5 Cooling Only Installation of Outdoor Units 5. Installation • Install at places where it can endure the weight and vibration/noise of the outdoor unit. • The outdoor unit support block at the bottom shall have width of at least 100mm(3-15/16inch) under the units legs before being fixed.
Page 244
Multi V 5 Cooling Only Installation of Outdoor Units 5. Installation 5.2 Foundation for Installation • Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust. • Use the H-beam support as a base support •...
Page 245
Multi V 5 Cooling Only Installation of Outdoor Units 6. Refrigerant piping Installation 6.1 Precautions on Pipe connection / Valve operation Pipe connection is done by connecting from the end of the pipe Service Port to the branching pipes, and the refrigerant pipe coming out of the outdoor unit is divided at the end to connect to each indoor unit.
Page 246
Multi V 5 Cooling Only Installation of Outdoor Units 6. Refrigerant piping Installation 6.2 Connection of Outdoor units When installing outdoor unit series, refer below picture. (Master) (Slave1) (Slave2) (Slave3) A B C D Indoor unit side connection pipe Outdoor unit to outdoor unit connection pipe (1st branch) Outdoor unit to outdoor unit connection pipe (2st branch) Outdoor unit to outdoor unit connection pipe (3rd branch) Cooling Only System...
Page 247
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system 7.1 Pipe Connection Method between outdoor unit / indoor unit Single Outdoor Unit Connection Y branch method Outdoor Unit 1st branch (Y branch) Indoor Unit Indoor Units L 150m [492ft] (200m [656ft] : Conditional application)* l 40m [131ft] (90m [295ft] : Conditional application)* h 40m [131ft]...
Page 248
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system Series Outdoor Unit Connection Y branch method ODU Capacity Master ≥ Slave 1 ≥Slave 2 ≥Slave 3 Outdoor Unit Indoor 1st branch (Y branch) Unit 10m [32.8ft] or less Indoor Units Connection branch pipe between outdoor units...
Page 249
Multi V 5 Installation of Outdoor Units 7. Refrigerant piping system ■ Limits of pipe length and difference in height Combination of Y Connection method Y branch only Header only branch/header A+B+b ≤ 150m [492ft] ) Longest pipe length (L) (200m [656ft]**) A+B+C+D+e ≤...
Page 250
Multi V 5 Installation of Outdoor Units 7. Refrigerant piping system ■ Refrigerant pipe diameter from branch to branch (B,C,D) Downward Indoor Unit total capacity Liquid pipe Gas pipe [kW(Btu/h)] [mm(inch)] [mm(inch)] Ø6.35(1/4) Ø12.7(1/2) ≤ 5.6(19,100) < 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8) <...
Page 251
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system Outdoor unit Connection Slave1 Master Slave2 Slave3 Indoor Unit 1st branch Refrigerant pipe diameter from outdoor unit to first branch l 40m h 40m * Maximum number of connectable units could be different in accordance with model line up of target region. A : Refrigerant pipe diameter from outdoor unit to first branch E : Refrigerant pipe diameter for outdoor unit capacity (Slave 1+ Slave 2+ Slave 3) F : Refrigerant pipe diameter for outdoor unit capacity (Slave 2+ Slave 3)
Page 252
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system 7.2 Indoor Unit Connection Indoor Unit connecting pipe from branch (a, b, c, d, e, f) Indoor Unit capacity [kW(Btu/h)] Liquid pipe [mm(inch)] Gas pipe [mm(inch)] Ø6.35(1/4) Ø12.7(1/2) 5.6(19,100)
Page 253
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system 7.3 Pipe Connection Method/Precautions for Series connections between Outdoor units • Separate Y branch joints are needed for series connections between outdoor units. • Please refer to the below connection examples to install pipe connections between outdoor units. 7.3.1 Pipe connection between outdoor units (General Case) 7.3.2 Pipes between outdoor units are 2m(6.6ft) or less 7.3.3 Pipes between outdoor units are 2m(6.6ft) or longer...
Page 254
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system 7.3.4 Examples of Wrong Pipe Connections • The pipes between the outdoor units must maintain horizontal levelness or give an inclination to prevent a back flow toward the slave outdoor unit. Otherwise, the unit may not operate properly. (Example 1) Toward indoor unit Toward indoor unit...
Page 255
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system (Example 2) Oil Trap 2m(6.6ft) ≤ Toward indoor unit ≤ 2m(6.6ft) • Install Oil trap if the ODU is at lower level than main piping. • When connecting the pipes between the outdoor units, the accumulation of oil in the slave outdoor unit should be avoided.
Page 256
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system 7.4 The amount of Refrigerant The calculation of the additional charge should take into account the length of pipe and CF(correctionFactor) value of indoor unit. Additional charge(kg) Total liquid pipe : Ø25.4 mm ×...
Page 257
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system 7.5 Selection of Y Branch and Header 7.5.1 Y Branch Gas pipe Liquid pipe Models [unit:mm] [unit:mm] I.D12.7 I.D12.7 I.D6.35 I.D.6.35 I.D9.52 I.D15.88 I.D15.88 I.D9.52 I.D15.88 I.D.6.35 ARBLN01621 I.D12.7 I.D.9.52...
Page 258
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system 7.5.2 Header Gas pipe Liquid pipe Models [unit:mm] [unit:mm] ID12.7 ID6.35 ID6.35 ID12.7 4 branch ID9.52 ID15.88 ARBL054 ID9.52 ID15.88 ID15.88 ID12.7 ID9.52 ID19.05 ID12.7 ID6.35 ID12.7 7 branch ARBL057 ID9.52...
Page 259
Multi V 5 Cooling Only Installation of Outdoor Units 7. Refrigerant piping system 7.6 Distribution Method 7.6.1 Horizontal Distribution Slave Master 3rd main pipe distribution Slave Master Slave Master Main pipe Distribution Main pipe Distribution 7.6.2 Vertical Distribution Slave Master Slave Master 7.6.3 The Others...
Page 260
Multi V 5 Cooling Only Installation of Outdoor Units 8. Electrical Wiring 8.1 Electrical Wiring 8.1.1 Caution 1. Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and guidance of each electric power company. CAUTION Be sure to have authorized electrical engineers do the electric work using special circuits in accordance with regulations and this installation manual.
Page 261
Multi V 5 Cooling Only Installation of Outdoor Units 8. Electrical Wiring Precautions when laying power wiring Use round pressure terminals for connections to the power terminal Power wire Round pressure terminal block. When none are available, follow the instructions below. •...
Page 262
Multi V 5 Cooling Only Installation of Outdoor Units 8. Electrical Wiring 8.1.2 Control box and connecting positioning of wiring • Remove all of the screws at front panel and remove the panel by pulling it forward. • Connect communication line between main and sub outdoor unit through the terminal block.
Page 263
Multi V 5 Cooling Only Installation of Outdoor Units 8. Electrical Wiring 8.1.3 Communication and Power Lines 1. Communication cable • Types : shielded cables • Use wires of size : over 1.0 ~ 1.5 mm (1.55 × 10 ~ 2.32 × 10 •...
Page 264
Multi V 5 Cooling Only Installation of Outdoor Units 8. Electrical Wiring 8.2 DIP Switch Setting 8.2.1 Checking according to dip switch setting You can check the setting values of the Master outdoor unit from the 7 segment LED. The dip switch setting should be changed when the power is OFF.
Page 265
Multi V 5 Cooling Only Installation of Outdoor Units 8. Electrical Wiring CAUTION Product may not properly operate if the relevant DIP switch is not properly setup. Master / Slave Dip Switch Setting Master/Slave Unit Slave Master Slave1 Slave2 Slave3 Dip switch setting (Factory setting) * In accordance with the number of combined outdoor unit or target region, Slave2 and Slave3 could not be applied...
Page 266
Multi V 5 Cooling Only Installation of Outdoor Units 8. Electrical Wiring 8.3 Automatic Addressing The address of indoor units would be set by auto addressing 1. Wait for 3 minutes after supplying power. (Master and Slave outdoor units, indoor units) 2.
Page 267
Multi V 5 Cooling Only Installation of Outdoor Units 8. Electrical Wiring The Procedure of Automatic Addressing Power On Waiting 3 minutes Press RED Button for 5 sec. (SW01C) Automatic addressing process start 7-segment LED = 88 Don’t press RED Button (SW01C) •...
Page 268
Set for only using Overall Defrost (not applying Partial Overall defrost Defrost) ODU address Address for monitoring cycle view with LG control solutions Snow removal & rapid defrost Function for snow removal and rapid defrost function Decrease airflow of IDU in case of shortage of heating...
Page 269
Multi V 5 Cooling Only Installation of Outdoor Units 9. Setting the function 9.2 Dip Switch Setting Select the mode/function/option/value using ‘►’, ‘ ’ Button and confirm that using the ‘ ’ button after dip switch No.5 is turned on. DIP-SW01 7-Segment SW04C (X : cancel)
Page 270
Multi V 5 Cooling Only Installation of Outdoor Units 9. Setting the function 9.3 Night Low Noise Function In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night which has low cooling load.
Page 271
Cooling Only Special Guide Multi V 5 1.Cautions for Refrigerant Leaks 2.Guide for installing at seaside...
Page 272
Multi V 5 Cooling Only Special Guide 1. Caution For Refrigerant Leaks The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available. 1.1 Introduction Though the R410A refrigerant is harmless and incombustible itself , the room to equip the air conditioner should be large to such an extent that the refrigerant gas will not exceed the limiting concentration even if the refrigerant...
Page 273
Multi V 5 Cooling Only Special Guide 1. Caution For Refrigerant Leaks 1.2.2 Calculate refrigerant concentration level Calculate the volume of the room where indoor unit is installed as single room or the smallest room. 1. Without partition Outdoor unit Indoor unit 2.
Page 274
Multi V 5 Cooling Only Special Guide 1. Caution For Refrigerant Leaks In case the concentration exceeds the limit When the concentration exceeds the limit, change original plan or take one of the counter measure shown below: • Counter measure 1 Provide opening for ventilation.
Page 275
Multi V 5 Cooling Only Special Guide 2. Guide for installing at seaside CAUTION 1. Air conditioners must not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Avoid installing the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product.
Page 276
Control System Multi V 5 1.Solution Overview 2.Control System List 3.Function List 4.Accessory Compatibility List 5.Centralized Controller Compatibility List...
Page 277
Multi V 5 Control System 1. Solution Overview • 1) It is available 5 series controllers (ACP5, AC Smart5) only. • If you need more detail, please refer to the Control PDB or the manual of product. (http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON))
Page 278
Multi V 5 Control System 2. Control System List Dimensions Controller Compatible Category Model name Feature name Product (W x H x D, mm) • 5 inch color Display PREMTA000(A/B) • Touch Screen Premium All IDU • Group control (Max 16 indoor unit) Wired 137 x 121 x 16.5 •...
Page 279
Multi V 5 Control System 2. Control System List Outline of system 1. Installation Method ① ② ③ ※ ① : AWG#24 / ②, ③ : AWG#22 The total cable length must not exceed 50m. (It can cause communication error.) 2.
Page 280
Multi V 5 Control System 2. Control System List Dimensions Controller Compatible Category Model name Feature name Product (W x H x D, mm) • PC Access Controller All IDU PACM5A000 • DC 12 V Adaptor • Max 8,192 indoor unit control ERV DX AC Manager 5 270 x 155 x 65...
Page 281
Multi V 5 Control System 2. Control System List Outline of system When using a HUB, use Direct UTP Cable. AC Manager 5 Max.length of total transmission wiring for centralized control : 1km Ethernet (Direct UTP Cable) Web access Remote controller Remote controller •...
Page 282
Multi V 5 Control System 2. Control System List Dimensions Controller Compatible Category Model name Feature name Product (W x H x D, mm) PACS5A000 • 10.2 inch color Display • Touch Screen • DC 12 V Adaptor AC Smart 5 •...
Page 283
Multi V 5 Control System 2. Control System List Outline of system Max.length of total transmission wiring for centralized control : 1km Up to 128 units by individual control • Communication cable – Types : shielding wire – Use wires of size : over 0.75 ~ 1.5 mm –...
Page 284
Multi V 5 Control System 2. Control System List Dimensions Controller Category Model name Objective / Use Feature name (W x H x D, mm) PDRYCB000 • 1SET / 1 IDU PDRYCB100 • 1 Contact point For Connect • Input power AC 220V~240 V indoor unit to 120 x 120 x 36.5 –...
Page 285
CN-CC 24 V~ To Apply Power Source through PCB To Apply Power Source Directly to External Source CN_Ther/Oper CN_MODE Thermostat Thermostat LG does not LG does not CN_WIND CHANGEOVER_SW supply this section supply this section Connect separate (Field supply) (Field supply)
Page 286
Multi V 5 Control System 2. Control System List Dimensions Controller Category Model name Objective / Use Feature name (W x H x D, mm) PRDSBM • Push Button Type Cool/Heat To Select 74 x 120 x103 Selector Operation Mode •...
Page 287
Multi V 5 Control System 2. Control System List Outline of system Main PCB Transformer IO Module Variable Water Flow Valve Terminal Block Variable Water Field Flow Valve control KIT Supply (Accessory) Damper Damper Damper Actuator Actuator Actuator IO Module AC 220V Main PCB Terminal...
Page 288
Multi V 5 Control System 2. Control System List Dimensions Controller Category Model name Objective / Use Feature name (W x H x D, mm) PAHCMR000 • UI 4EA (AI/DI) Return Air • DO 3EA (Relay, A type) AHU Comm. Kit Temperature 300 X 300 X 155 •...
Page 289
) can be changed in MULTI V and Single outdoor setting. LG wired remote controller and LG Central Controller can be optionally applied, but only monitoring function is possible. • If you need more detail, please refer to the Control PDB or the manual of product.
Page 290
The DDC controls return air temperature (Tr) or room air temperature (TRoom) by transferring Modbus signal to the AHU Communication Kit for Return air control. To control room air, the LG wired controller can be purchased optionally. A fixed target evaporator or condensing temperature (T ) can be changed in MULTI V and Single outdoor setting.
Page 291
Multi V 5 Control System 2. Control System List Outline of system • DDC Control by Contact Signal : Variable T (0~10 V) LG Central (Field Supply) Controller AI / DI / DO Room (Monitoring only) Room Signal Remote Controller...
Page 292
Multi V 5 Control System 2. Control System List Dimensions Controller Category Model name Objective / Use Feature name (W x H x D, mm) PRCTIL0 • Length of cable : 1m (3m extension cable is included) LGMV data Maintenance monitoring via •...
Page 293
Multi V 5 Control System 2. Control System List Outline of system 1. Outdoor connection Connect LGMV cable to Multi V PCB LGMV port 2. Indoor unit connection Connect LGMV cable to Multi V Indoor unit communication port • If you need more detail, please refer to the Control PDB or the manual of product. (http://partner.lge.com/global : Home>...
Page 294
Multi V 5 Control System 2. Control System List Dimensions Controller Category Model name Objective / Use Feature name (W x H x D, mm) PLGMVW100 • The effective distance for wireless communication is 10m Maintenance Mobile LGMV monitoring • The effective distance may be 48 x 78 x 14.5 Accessory LGMV...
Page 295
Multi V 5 Control System 2. Control System List Outline of system • If you need more detail, please refer to the Control PDB or the manual of product. (http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON))
Page 296
Multi V 5 Control System 3. Function List Individual Controller Premium Wired Simple Wired Simple Wired Wireless Standard Wired Remote Controller Name Remote Remote Remote Remote Controller Controller Controller Controller Controller Product Image PREMTA000 PREMTB100 PREMTB001 PQRCVCL0Q PQRCHCA0Q Model Name PREMTA000A PQWRHQ0FDB PREMTBB10...
Page 297
Multi V 5 Control System 3. Function List Central Controller Controller Name AC Ez AC Ez touch AC Smart IV AC Smart 5 Product Image Model Name PQCSZ250S0 PACEZA000 PACS4B000 PACS5A000 Maximum Number of Indoor Units Individual / Group Control (On &...
Page 298
Multi V 5 Control System 3. Function List Controller Name ACP IV AC Manager IV AC Manager 5 ACP 5 Product Image Model Name PACP4B000 PACP5A000 PACM4B000 PACM5A000 Maximum Number of Indoor 8,192 8,192 Units Individual / Group Control (On & Off, Mode, Set Point, Fan Speed) Individual Controller Lock (Temperature, Mode,...
Page 299
Multi V 5 Control System 4. Accessory Compatibility List Product Model name Compatibility Wireless Remote PQWRH(C)Q0FDB ○ Controller PQRCVCL0Q(W) Simple ○* Simple PQRCHCA0Q(W) for Hotel ○* PREMTB001 Standard II(White) ○ Wired Remote PREMTBB01 Standard II (Black) ○ Standard Controller PREMTB100 Standard III (White) ○...
Page 300
Multi V 5 Control System 4. Accessory Compatibility List E.O.L Model Product Model name Compatibility Wireless Remote PQWRH(C)DF0 Controller Wired PQRCVSL0 RS2 Wired (black) Remote Standard PQRCVSL0QW RS2 Wired (White) Controller PQDSA Simple Contact PQDSA(1) PQDSB(1) Dry contact PQDSBC PQDSBNGCM1 Communication type PQDSBCGCD0 Dry Contact for Thermostat...
Page 301
Multi V 5 Control System 5. Centralized Controller Compatibility List Compatibility between Controllers Slave (B) Master (A) ACP IV AC Smart IV AC Ez AC Ez Touch ACP BACnet AC Smart 5 Lonworks ACP 5 AC Ez AC Ez Touch AC Smart IV, AC Smart 5 ACP IV, ACP 5...