Configuring the Climatix touch panel .............22 Set screen brightness ................22 Set the time and date ................. 22 Test the serial ports ................... 23 Set the language ..................23 Maintenance and care .................24 2 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...
Page 3
Technical specifications............... 25 Technical data ...................25 Interface description ..................27 LED indicators ...................28 DIP switches ....................29 Dimensions (in mm) ...................29 3 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...
This symbol marks texts that contain safety information to prevent wrong operation. This symbol marks passages you should read with special care. Texts marked with this symbol provide additional information, notes and so on. 5 | 30 A6V11348824_en--_a Siemens Smart Infrastructure 2018-04-10...
This document may be duplicated and distributed only with the expressed permission of Siemens, and may be provided only to authorized persons or companies with the requisite technical knowledge. Siemens reserves the right to make any modification to this document without prior notice. 1.4.4 Quality assurance These documents were prepared with great care.
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
Time scheduler and trend view functions via HMI-TOOLS ● Data tag management via HMI-TOOLS ● Time sync with Climatix controller via HMI-TOOLS ● Graphical extendable database with HVAC pictures and animations via HMI-TOOLS ● Support C-like script language programming 8 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...
The application in the Climatix controller must support Modbus communication via RS485 interface and/or local service interface (T-HI). With Climatix POL6XX controller Climatix POL6XX communication concept (here C600) With Climatix POL4XX controller Climatix POL4XX communication concept (here POL42X) 9 | 30 A6V11348824_en--_a Siemens Smart Infrastructure 2018-04-10...
The following is the mechanical design of the Climatix capacitive touch panel, POL8T2.40. Description Description Display / touch screen RS485 communication port LED indicators DIP switches Label Recesses for a mounting clip USB-A port Power supply connection USB-B port 10 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...
Make sure that both ends of the cable are connected tightly and firmly. The RS485 port is a communication port. It cannot be used for programming. 12 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...
Check the package content for visible signs of transport damage and for completeness. Note: Do not install parts damaged during shipment. Contact your Siemens representative in the event of damaged parts. Check operating Note the information in the following sections of these operating instructions before...
Grounding Terminal- Field wiring terminal for connection of equipment-grounding conductor shall be green-colored or plainly identified on or adjacent to connector or provided on instruction manual and shipped with the device by “G”, “GR”, “GRD”, 14 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...
This provides a pathway for electrostatic discharge and blocks high-frequency interference. (Recommendation: Resistance, 1 M Ω; Capacitance, 4700 pF.) 4. Switch off the power supply. 5. Insert the remaining wire ends into the mains terminal, and secure them with a screwdriver. 15 | 30 A6V11348824_en--_a Siemens Smart Infrastructure 2018-04-10...
USB Type B male connector on one end. 1. Connect the USB cable to the USB-A port on the Climatix touch panel. 2. Connect the other end of the USB cable to the configuration PC. 16 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...
2. Connect an RS485 connector on a communication cable to the Climatix touch panel. 3. Connect the other RS485 connector on the communication cable to the controller. For safety instructions, see Notes on communication [➙ 12]. 17 | 30 A6V11348824_en--_a Siemens Smart Infrastructure 2018-04-10...
Check the connected cables and change them as needed. Climatix touch panel has a DEMO application in order to show main functionalities and features. Please download your own application developed with HMI-TOOL configuration software. 18 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...
You can configure the customized keyboard for an operating element in the configuration software. ASCII keyboard Numeric keypad 19 | 30 A6V11348824_en--_a Siemens Smart Infrastructure 2018-04-10...
*.zip Preparation To create an upgrade image on a USB stick: 1. Contact Siemens regional company to get an upgrade file (.zip) for your touch panel firmware. 2. Format the USB stick as FAT32 format. 3. Extract the zip file (MLO, ubi.img, u-boot.img and uImage) to USB stick root.
5. Wait until a request for confirmation of GUI download appears. 6. Confirm the GUI download process. 7. After the upgrade process is completed, the Climatix touch panel restarts automatically. 8. The Climatix touch panel runs new GUI application. 21 | 30 A6V11348824_en--_a Siemens Smart Infrastructure 2018-04-10...
6.1 Set screen brightness Press Brightness, and adjust the screen brightness. 6.2 Set the time and date Press Date / time and use + or - to set the date and time, and press Ok. 22 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...
7. In the monitor software, enter test data and send it. 8. If the Receiving a character textbox displays the same data, the test is successful. 6.4 Set the language Press Language, select the desired display language and press Ok. 23 | 30 A6V11348824_en--_a Siemens Smart Infrastructure 2018-04-10...
Do not clean the Climatix touch panel with compressed air or steam jet blowers. Do not use aggressive solvents or scouring powder. 24 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...
60529 ● Front IP 65 ● Rear panel IP 20 ESD protection EN 61000-4-2 Housing material ABS + PC Configuration software HMI-TOOLS (third party engineering software) Touchpad 2-point high-precision capacitive touch screen 25 | 30 A6V11348824_en--_a Siemens Smart Infrastructure 2018-04-10...
Page 26
Dimensions (mm) 150 × 93 × 38.5 Cut-out (mm) 141 × 84 Weight (kg) 0.28 Ordering data Article type (ASN) POL8T2.40/STD Material (SSN) S55626-H824-A100 Minimum order quantity Product package* Touch panel Mounting clips Power supply terminal Power supply and communication cables are not included in product package.
DC 5 V out, max. 500 mA Data - Data + Ground Serial port interface Figure RS485 Connect to controller port REF (for RS485) Data - RS485 B- (for RS485 connection) Data + RS485 A+ (for RS485 connection) 27 | 30 A6V11348824_en--_a Siemens Smart Infrastructure 2018-04-10...
The three LED indicators are located on the front of the Climatix touch panel. Marking Indicator name Color Mode Description Power supply Green Powered on No power Operation Yellow No detected fault CPU fault detected in the device Communication Yellow Flashing Communication in progress communication 28 | 30 Siemens A6V11348824_en--_a Smart Infrastructure 2018-04-10...