Revision 02
2.5
The thermal loading limitations imposed when using the HLU-231 List 7B in Controlled
Environmental Vaults (CEV) or other enclosures are determined by applying the HLU-231 List 7B
power parameters to the manufacturer requirements for each specific housing.
2.6
The power consumption listed in Table 12 is the total power that the HLU-231 List 7B consumes or
draws from its -48 VDC shelf power source. This parameter is needed when the HLU-231 List 7B is
located remote to its serving CO. It determines the battery capacity required to maintain an 8-hour
stand-by battery reserve for emergency situations. It thus limits the maximum number of plugs per
remote enclosure. Use this data to perform this analysis on a case by case basis.
HiGain Line Unit HLU-231
January 31, 1997
PairGain Engineering - Plant Series
Section 150-231-172
Page 43