13.3 Timer

13.3
Timer
13.3.1
Timer
Timer
Timers are integrated in the SIMOCODE pro system. These are activated via the plugs "+" or
"-".
The Timer output switches to "1" when the timer reaches 0 from the preset limit. The Timer is
reset with "Reset".
The timer consists of:
● 2 plugs (input and reset)
● 1 socket (Timer Output)
● 1 "Actual Value" analog socket with the actual value.
The actual value is available as a socket for further internal processing and can also be
transmitted to the automation system.
If an input signal is pending, the timer can issue an output signal according to the chosen
timer type:
● With closing delay
● With closing delay with memory
● With OFF delay
● With fleeting closing.
In total, 6 timers (1 to 6) for the SIMOCODE pro V PN basic unit are available.
Note
The output is always 0 if a Reset is pending.
Note
The response of the sockets of all Timers (Input, Reset) has been completely changed to
level-active for Basic Unit 1 from version *E05* and higher and Basic Unit 2 from version
*E03* and higher. Use of an unchanged parameter file utilizing integrated Timers may thus
result in a different response if such Basic Units are used. For example, if "fixed level - 1" is
set at the Timer input, the timer function is automatically restarted after the Timer reset
occurs. However, in Timers with the parameterized Type = "fleeting closing" there is no
change in the response.
120
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
SIMOCODE PRO V PN FDI