ABB i-bus® KNX PARAMETERS
7.4.122
Control value after bus voltage recovery
This parameter is used to define the control value set after bus voltage recovery. The set control value is
valid until a new control value is calculated by the controller in the controller mode or a new control value
is received via the bus
The reaction set here applies during the sending and switching delay as well.
After bus voltage recovery, it can take up to 2 seconds until the device has started and the outputs can
be activated.
Option
As before bus voltage failure
Selection
Prerequisites for visibility
• The parameter is in the parameter window
7.4.123
Control value after ETS download
This parameter is used to define the control value set after ETS download. The set control value is valid
until a new control value is calculated by the controller in the controller mode or a new control value is re-
ceived via the bus
Option
Unchanged
Selection
Prerequisites for visibility
• The parameter is in the parameter window
Note about navigation in the PDF: Key combination 'Alt + left arrow'
jumps to the previous view/page
(ABB i-bus®
Note
The last control value before bus voltage failure is applied.
The control value can be set.
The following dependent parameters are shown:
•
Control value
(ABB i-bus®
The last control value before ETS download is applied.
The control value can be set.
The following dependent parameters are shown:
•
Control value
KNX) in the actuator mode.
Channel X
KNX) in the actuator mode.
Channel X
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B 124
\ parameter window
Channel function
\ parameter window
Channel function
.
.