1MRS758407 C
3.10.3.2
Settings
RESTCTR1_ct Non group settings (Basic)
Table 45: RESTCTR1_ct Non group settings (Basic)
Parameter
Values (Range)
Primary current
1.0...6000.0
Secondary current
1=0.2A
2=1A
3=5A
Amplitude Corr
0.9000...1.1000
RESTCTR1_ct Non group settings (Advanced)
Table 46: RESTCTR1_ct Non group settings (Advanced)
Parameter
Reverse polarity
3.11

GOOSE function blocks

GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32 data
types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by
bad data quality bits or GOOSE communication failure. See IEC 61850 engineering
guide for details.
The OUT output passes the received GOOSE value for the application. Default value
(0) is used if VALID output indicates invalid status. The IN input is defined in the
GOOSE configuration and can always be seen in SMT sheet.
Settings
The GOOSE function blocks do not have any parameters available in PCM600.
3.11.1

GOOSERCV_BIN function block

SMU615
Technical Manual
Unit
A
Values (Range)
Unit
0=False
1=True
Step
Default
0.1
100.0
2=1A
0.0001
1.0000
Step
Default
0=False
Basic functions
Description
Primary current
Secondary current
Amplitude correction
Description
Reverse the polarity of the re-
sidual CT
71