SIPROTEC 5 Compact
Hardware Description
V9.50 and higher
Manual
C53000-G5340-C002-7
Preface
Table of Contents
Introduction
Forms of Devices and On-Site Operation
Panels
Electronic Modules
Communication
Working on the Device
Technical Data
Ordering Information
Literature
Glossary
Index
1
2
3
4
5
6
7

Advertisement

Table of Contents
loading

Summary of Contents for Siemens V9.50

  • Page 1 Preface Table of Contents Introduction Forms of Devices and On-Site Operation SIPROTEC 5 Compact Panels Hardware Description Electronic Modules Communication V9.50 and higher Working on the Device Manual Technical Data Ordering Information Literature Glossary Index C53000-G5340-C002-7...
  • Page 2 Document version: C53000-G5340-C002-7.03 Trademarks Edition: 03.2023 SIPROTEC, DIGSI, SIGRA, SIGUARD, SIMEAS, SAFIR, SICAM, Version of the product described: V9.50 and higher and MindSphere are trademarks of Siemens. Any unauthor- ized use is prohibited.
  • Page 3: Preface

    Preface Purpose of the Manual This manual describes the hardware of the SIPROTEC 5 Compact device family and provides general informa- tion on the product structure, the modules and technical data. Target Audience Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and maintenance of automation, selective protection and control equipment, and operational crew in electrical installations and power plants.
  • Page 4 EN 61000-6-2 and EN 61000-6-4 (for EMC directive), the standard EN IEC 63000 (for RoHS directive), and with the product standard EN 60255-27 (for Low Voltage Directive) by Siemens. The device is designed and manufactured for application in an industrial environment.
  • Page 5 Preface IND. CONT. EQ. 69CA Additional Support For questions about the system, contact your Siemens sales partner. Customer Support Center Our Customer Support Center provides a 24-hour service. Siemens AG Smart Infrastructure – Protection Automation Tel.: +49 911 2155 4466...
  • Page 6 The equipment (device, module) may be used only for such applications as set out in the catalogs and the technical description, and only in combination with third-party equipment recommended and approved by Siemens. Problem-free and safe operation of the product depends on the following: •...
  • Page 7 Preface Symbol Description Caution, risk of electric shock Caution, risk of danger, ISO 7000, 0434 Protective insulation, IEC 60417, 5172, safety class II devices Guideline 2002/96/EC for electrical and electronic devices Guideline for the Eurasian market Mandatory conformity mark for electronics and electrotechnical products in Morocco OpenSSL This product includes software developed by the OpenSSL Project for use in OpenSSL Toolkit (http://...
  • Page 8 SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 9: Table Of Contents

    Table of Contents Preface................................3 Introduction..............................11 Advantages of SIPROTEC 5 Compact.................. 12 Hardware Features......................15 Forms of Devices and On-Site Operation Panels..................17 Device Design........................18 2.1.1 General Description ....................18 2.1.2 Description ......................... 24 Surface-Mounted Devices....................27 2.2.1 Description........................27 Integrated Interfaces......................28 Terminals..........................29 Electronic Modules.............................
  • Page 10 Table of Contents 5.3.3 Connections of Voltage Terminals................56 5.3.3.1 Connections of Voltage Terminals with Spring Clips ..........56 5.3.3.2 Connections of Voltage Terminals with Screw Connection........56 5.3.4 Seal..........................57 5.3.5 Installation and Removal....................57 Technical Data............................59 Analog Inputs........................60 Supply Voltage........................61 Binary Inputs........................62 Relay Outputs........................
  • Page 11: Introduction

    Introduction Advantages of SIPROTEC 5 Compact Hardware Features SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 12: Advantages Of Siprotec 5 Compact

    Introduction 1.1 Advantages of SIPROTEC 5 Compact Advantages of SIPROTEC 5 Compact Thanks to the modular design of the software as well as the functional integration, SIPROTEC 5 Compact devices are well suited for all tasks in the energy sector. The devices include: •...
  • Page 13 [dw_7SX800_ SimpleFeeder, 1, en_US] Figure 1-2 Feeder Protection SIPROTEC 5 Compact Hardware SIPROTEC 5 Compact hardware provides the entire experience of Siemens for digital protection devices. • Durability and reliability – Robust housing –...
  • Page 14 Introduction 1.1 Advantages of SIPROTEC 5 Compact • User-friendly design – No opening of device necessary for installation and servicing – Integrated communication interfaces as standard – Electronically settable threshold for binary inputs – Rated current (1 A/5 A) of the current-transformer inputs configurable electronically –...
  • Page 15: Hardware Features

    Introduction 1.2 Hardware Features Hardware Features A device always consists of just one module (1/6 of 19 inches) and cannot be expanded with expansion modules. The hardware features are: • Module size: 1/6 of 19 inches • Type of construction: Flush-mounting devices with on-site operation panel fitted directly on the device •...
  • Page 16 SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 17: Forms Of Devices And On-Site Operation Panels

    Forms of Devices and On-Site Operation Panels Device Design Surface-Mounted Devices Integrated Interfaces Terminals SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 18: Device Design

    Forms of Devices and On-Site Operation Panels 2.1 Device Design Device Design General Description 2.1.1 Control [dw_steuerung_SIP5C, 1, en_US] Figure 2-1 SIPROTEC 5 Compact – Functional Integration – Control SIPROTEC 5 Compact includes all control and supervision function at bay level, required for an efficient operation of the switchgear.
  • Page 19 Forms of Devices and On-Site Operation Panels 2.1 Device Design Automation [dw_automation_SIP5C, 1, en_US] Figure 2-2 SIPROTEC 5 Compact – Functional Integration – Automation The integrated CFC (Continuous Function Chart) graphical automation editor enables you to create logic diagrams clearly and simply. DIGSI 5 supports this with powerful logic blocks based on the standard IEC 61131-3.
  • Page 20 Forms of Devices and On-Site Operation Panels 2.1 Device Design Monitoring [dw_Monitoring_SIP5C, 1, en_US] Figure 2-3 SIPROTEC 5 Compact – Functional Integration – Monitoring SIPROTEC 5 Compact devices can take on a wide variety of monitoring tasks. These can be divided into the following groups: •...
  • Page 21 Forms of Devices and On-Site Operation Panels 2.1 Device Design SIPROTEC 5 Compact provides the process interfaces, buffers, recorders, and automation functions necessary for monitoring equipment: • Process values are stored together with a time stamp in the operational log •...
  • Page 22 Forms of Devices and On-Site Operation Panels 2.1 Device Design Communication [dw_Communication_SIP5C, 1, en_US] Figure 2-4 SIPROTEC 5 Compact – Functional Integration – Communication SIPROTEC 5 Compact devices are equipped with high-performance communication interfaces. These are inte- grated interfaces to provide a high level of security and flexibility. The interface is independent of the protocol used.
  • Page 23 Forms of Devices and On-Site Operation Panels 2.1 Device Design [dw_SIP5Comp_rear_optical_interface, 1, --_--] Figure 2-5 Rear Panel with Optical Ethernet Interface Electrical Ethernet Interface The electrical Ethernet interface has 2 RJ45 interfaces. It can be configured with or without an integrated switch.
  • Page 24: Description

    Forms of Devices and On-Site Operation Panels 2.1 Device Design [dw_SIP5Comp_rear_electrical_interface, 1, --_--] Figure 2-6 Rear Panel with Electrical Interfaces Serial interface The serial RS485 interface features 1 RJ45 interface. It is used for serial protocol applications such as IEC 60870-5-103, DNP3 serial, or Modbus RTU. 2.1.2 Description SIPROTEC 5 Compact Design...
  • Page 25 Forms of Devices and On-Site Operation Panels 2.1 Device Design Operation Panel [le_SIP5C_operation panel, 2, --_--] Figure 2-7 SIPROTEC 5 Compact Operation Panel Color display LEDs (green or red, configurable) Display of the LED labeling in the display USB interface Numerical keys and function keys Control/command keys Context-sensitive keys with labeling in the display...
  • Page 26 Forms of Devices and On-Site Operation Panels 2.1 Device Design The operation panel enables the illustration of a control display and provides space for measured values and to display event lists. [sc_SIP5CompactDisplay v3, 1, --_--] Figure 2-8 Display – Control Display The O and I keys (red and green) for the direct control of equipment, a key for displaying the LED labeling, and the CTRL key for activating the system diagram complete the operation panel.
  • Page 27: Surface-Mounted Devices

    Forms of Devices and On-Site Operation Panels 2.2 Surface-Mounted Devices Surface-Mounted Devices Description 2.2.1 A surface-mounting frame for the SIPROTEC 5 Compact device can be ordered as an accessory to install it on the wall. Thanks to a new concept, these devices thus have terminal connection diagrams that are identical to the corresponding flush-mounting devices.
  • Page 28: Integrated Interfaces

    Forms of Devices and On-Site Operation Panels 2.3 Integrated Interfaces Integrated Interfaces Integrated Interfaces USB Connection on the Front The device can be accessed with the DIGSI 5 operating program by plugging a standard USB cable into the USB-B socket on the front side. The complete configuration and setting of the device can be carried out via this connection.
  • Page 29: Terminals

    Forms of Devices and On-Site Operation Panels 2.4 Terminals Terminals SIPROTEC 5 Compact Terminals Innovative terminals were developed for the SIPROTEC 5 Compact family. All terminals are individually remov- able (Figure 2-11). This enables prewiring of the systems and simple device replacement without costly rewiring.
  • Page 30 Forms of Devices and On-Site Operation Panels 2.4 Terminals Current terminals The 8-pole current terminal with 4 integrated current transformers is available in 2 variants: • 4 protection-class current transformers • 3 protection-class current transformers + 1 sensitive protection-class current transformer The terminal design provides the following advantages for the connection of currents: •...
  • Page 31 Forms of Devices and On-Site Operation Panels 2.4 Terminals [dw_terminal_block_standard, 1, --_--] Figure 2-13 Industry Standard Terminal SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 32 SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 33: Electronic Modules

    Electronic Modules Power-Supply Module PS050 Input and Output Module IO050 Input and Output Module IO060 SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 34: Power-Supply Module Ps050

    Electronic Modules 3.1 Power-Supply Module PS050 Power-Supply Module PS050 Description 3.1.1 The power-supply module PS050 is always permanently installed in the base module. Its central task is to supply power to all modules. The following can be found on the PS050 module: •...
  • Page 35: Input And Output Module Io050

    Electronic Modules 3.2 Input and Output Module IO050 Input and Output Module IO050 Description 3.2.1 The terminals for the following are located on the input and output module IO050: • 13 binary inputs • 3 binary outputs The connections are on: •...
  • Page 36: Terminals

    Electronic Modules 3.2 Input and Output Module IO050 Terminals 3.2.2 Overview of Terminals [dw_IO050, 1, en_US] Figure 3-2 IO050 – Connection Diagram SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 37: Input And Output Module Io060

    Electronic Modules 3.3 Input and Output Module IO060 Input and Output Module IO060 Description 3.3.1 The terminals for the following are located on the input and output module IO060: • 10 binary inputs • 6 binary outputs (fast make contacts, type F) The connections are on: •...
  • Page 38: Terminals

    Electronic Modules 3.3 Input and Output Module IO060 Terminals 3.3.2 Overview of Terminals [dw_IO060, 1, en_US] Figure 3-3 IO060 – Connection Diagram SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 39: Communication

    Communication Integrated Interfaces Communication Applications of the Plug-in Modules SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 40: Integrated Interfaces

    Communication 4.1 Integrated Interfaces Integrated Interfaces USB Connections on the Front The device can be accessed with the DIGSI 5 operating program by plugging a standard USB cable into the USB-B socket on the front side of the base module. The complete configuration and setting of the device can be carried out via this connection.
  • Page 41 Communication 4.1 Integrated Interfaces Ensure that you route the communication lines separately from network circuits. [le_SIP5Comp_communication_ports, 1, --_--] Figure 4-1 SIPROTEC 5 Compact Communication Connections Protective grounding terminal Integrated redundant Ethernet interface F Serial interface/IRIG-B time synchronization E SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 42: Communication Applications Of The Plug-In Modules

    Communication 4.2 Communication Applications of the Plug-in Modules Communication Applications of the Plug-in Modules You can find information on communication applications for the plug-in modules in the following tables. Plug-In Modules and Integrated Interfaces for the Communication Table 4-1 Communication Applications and Plug-in Modules / Integrated Interfaces Integrated Serial Module Type: Module Type:...
  • Page 43 Communication 4.2 Communication Applications of the Plug-in Modules Integrated Serial Module Type: Module Type: Interface Port or Plug-In Module ETH-YC-2FO ETH-YA-2EL for SIPROTEC 5 Compact Line mode ■ ■ – PRP (Ethernet ring redundancy) ■ ■ – ■ ■ – HSR (Ethernet ring redundancy) RSTP (Ethernet ring redundancy) ■...
  • Page 44 Communication 4.2 Communication Applications of the Plug-in Modules Plug-In Module DNP3 serial ■ – – Modbus TCP – ■ ■ Modbus RTU ■ – – SUP Ethernet (Slave Unit Protocol) for connecting external temperature or 20 mA measuring – ■ ■...
  • Page 45: Working On The Device

    Working on the Device First Steps Battery Installing Current and Voltage Terminals SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 46: First Steps

    Working on the Device 5.1 First Steps First Steps Electrical Inspection 5.1.1 Device Protection DANGER Danger when connecting the SIPROTEC 5 Compact device Noncompliance with the safety notes will result in death, severe injury, or considerable material damage. The device must be situated in the operating area for at least 2 hours before you connect it to the ²...
  • Page 47 ² Grounding an On-Site Operation Panel Siemens recommends the use of contact washers on painted metal mounting walls. If the mounting wall ² is not metallic, place a metal layer, for example a layer of sheet metal, between the mounting wall and the on-site operation panels.
  • Page 48: Battery

    Working on the Device 5.2 Battery Battery Description 5.2.1 The battery lies in an externally accessible battery compartment. The battery compartment is located on the bottom of the device. You need not open the device when replacing the battery. If the auxiliary voltage fails, the battery ensures continued operation of the internal clock and storage of certain data (statistical values, values of thermal models) for at least 6 months.
  • Page 49 Working on the Device 5.2 Battery NOTICE Exercise caution when disposing of the battery. The battery contains lithium. Lithium batteries are subject to the statutory regulations governing the disposal of batteries. Noncompliance with the specified measures can result in material damage. Dispose of the battery in compliance with national and international regulations.
  • Page 50: Environmental Protection Hints

    When disposing of or transferring a mobile storage device, Siemens strongly recommends physically destroying it or completely deleting data from the mobile storage device by using a commercially available computer data erasing software.
  • Page 51 Working on the Device 5.2 Battery REACH/RoHS Declaration You can find our current REACH/RoHS declarations at: https://www.siemens.com/global/en/home/products/energy/ecotransparency/ecotransparency-down- loads.html NOTE You can find more information about activities and programs to protect the climate at the EcoTransparency website: https://www.siemens.com/global/en/home/products/energy/ecotransparency.html SIPROTEC 5 Compact, Hardware Description, Manual...
  • Page 52: Installing Current And Voltage Terminals

    Working on the Device 5.3 Installing Current and Voltage Terminals Installing Current and Voltage Terminals Description 5.3.1 [le_SIP5Comp_current_voltage_terminals, 1, --_--] Figure 5-4 Current and Voltage Terminals with Spring Clips Voltage-terminal block Current-terminal block Spring clips The spring clips fix the terminal block in place. [dw_terminal position IO111, 1, --_--] Figure 5-5 Voltage Terminal with Screw Connection –...
  • Page 53 Working on the Device 5.3 Installing Current and Voltage Terminals NOTE You can read the type of the current transformer used on the side of the terminal block, for example 3xI 1xIE. The reference number is located on the connector interface and can only be read when removed. •...
  • Page 54: Connections Of Current Terminals

    Stranded-wire conductor with ring-type lug • Stranded-wire conductor with bootlace ferrule • Solid conductor Siemens recommends the use of ring-type lugs with the dimensions shown in the following figure. Use copper cables only. [dwringka-030211-01.tif, 1, en_US] Figure 5-9 Ring-Type Lug D (for bolt) 5.0 mm (0.2 in)
  • Page 55 Working on the Device 5.3 Installing Current and Voltage Terminals [dwklest1-030211-01.tif, 1, --_--] Figure 5-10 Example of a Current Terminal with Connection of Cross Connectors and Single Cables [dwklest2-030211-01.tif, 1, --_--] Figure 5-11 Example of a Current Terminal with Connection of 2 Single Cables You can connect solid conductors as well as stranded-wire conductors with ring-type lug or bootlace ferrule.
  • Page 56: Connections Of Voltage Terminals

    The single cable connection type is available for the connection. You can connect solid conductors as well as stranded-wire conductors with and without bootlace ferrule as single cables. Siemens recommends using twin bootlace ferrules of series PN 966 144 made by Tyco Electronics for the connection of 2 single cables.
  • Page 57: Seal

    Working on the Device 5.3 Installing Current and Voltage Terminals Connection Elements and Conductor Cross-Sections NOTE Observe the manufacturer specifications when using a bootlace ferrule. Mechanical Requirements The fasteners and their associated components are designed for the following mechanical requirements: Permissible tightening torque at clamping screw 0.7 Nm Seal...
  • Page 58 Working on the Device 5.3 Installing Current and Voltage Terminals Installation Pull the cover cap off the terminal. ² Carefully insert the terminal block into the spring clips. ² Both spring clips must engage clearly audibly. ² SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 59: Technical Data

    Technical Data Analog Inputs Supply Voltage Binary Inputs Relay Outputs Light-Emitting Diodes in the On-Site Operation Panel User Interface, on the Front Integrated Ethernet Interface Integrated Serial Interface for Short Distances Electrical Tests 6.10 Mechanical Tests 6.11 Environmental Conditions 6.12 Operating Conditions 6.13 Reference Conditions and Influencing Variables...
  • Page 60: Analog Inputs

    Technical Data 6.1 Analog Inputs Analog Inputs Current Inputs All current, voltage, and power data are specified as RMS values. Rated frequency f 50 Hz, 60 Hz rated Protection-class current trans- Rated current I Measuring range rated formers 0 A to 250 A 0 A to 50 A Instrument transformers 0 A to 8 A...
  • Page 61: Supply Voltage

    Technical Data 6.2 Supply Voltage Supply Voltage Power supply Power supply via integrated power supply Permissible voltage ranges DC 19 V to DC 250 V AC 92 V to AC 265 V at 50 Hz, 60 Hz Auxiliary nominal voltage V DC 24 V, 48 V, 60 V, 110 V, 220 V AC 100 V, 230 V at 50 Hz, 60 Hz Ripple voltage, peak-peak, IEC 60255-11, IEC 61000-4-17...
  • Page 62: Binary Inputs

    Technical Data 6.3 Binary Inputs Binary Inputs Binary Input Standard Binary Input Rated voltage range DC 24 V to 250 V Current consumption, picked up Approx. DC 0.6 mA to DC 2.5 mA (independent of the control voltage) Power consumption, max. 0.6 W Pickup time Approx.
  • Page 63: Relay Outputs

    Technical Data 6.4 Relay Outputs Relay Outputs Relay Outputs Fast relay (type F) Making capacity Max. 1000 W (L/R = 40 ms) Max. 3600 VA (power factor ≥ 0.35, 50 Hz to 60 Hz) Breaking capacity Max. 30 W (L/R = 40 ms) Max.
  • Page 64: Light-Emitting Diodes In The On-Site Operation Panel

    Technical Data 6.5 Light-Emitting Diodes in the On-Site Operation Panel Light-Emitting Diodes in the On-Site Operation Panel Light-Emitting Diodes in the On-Site Operation Panel Status Color Quantity Green ERROR Routable (adjustable with DIGSI 5) 2-colored: red or green Only the defined color can be used in operation.
  • Page 65: User Interface, On The Front

    Technical Data 6.6 User Interface, on the Front User Interface, on the Front User Interface, Front Side You can find a USB connection of type B for the connection to a laptop computer or to a PC on the front side of the device.
  • Page 66: Integrated Ethernet Interface

    Technical Data 6.7 Integrated Ethernet Interface Integrated Ethernet Interface Integrated Electrical Ethernet Interface 6.7.1 Integrated Ethernet Interface (Port F) This connection is used to load the device with DIGSI 5 via Ethernet. This terminal also enables IEC 61850 Ethernet communication or communication with another protocol via Ethernet, for example, for connecting an external RTD unit.
  • Page 67 Risk of burns due to high temperatures of the SFP pluggable transceivers Noncompliance with the safety notes may result in medium or light injuries. The SFP pluggable transceivers can be disconnected and plugged in while in operation. Siemens ² recommends switching off the device.
  • Page 68 Technical Data 6.7 Integrated Ethernet Interface ✧ Pull on the bracket in order to pull the SFP pluggable transceiver out of the slot. The removal must be possible with free movement and without great exertion of force. ✧ Provide the SFP pluggable transceiver with the dust protection cap so that the optics are protected from contamination.
  • Page 69: Integrated Serial Interface For Short Distances

    Technical Data 6.8 Integrated Serial Interface for Short Distances Integrated Serial Interface for Short Distances Special Features of the Integrated Serial Interface 6.8.1 The integrated serial interface is equipped with 1 RJ45 connection. The serial signals of the RS485 interface are routed to the RJ45 connection (see the following figure).
  • Page 70: Integrated Serial Interface

    Technical Data 6.8 Integrated Serial Interface for Short Distances [dw_serma2_SIP5_Compact_IRIG-B, 1, en_US] Figure 6-3 Communication with IRIG B for Time Synchronization SIPROTEC 5 Compact device SIPROTEC 5 device IRIG-B adapter cable 7XX8310-0CG00 Time-synchronization bus cable 7XV5104-0AAxx NOTE The IRIG-B connection cannot be used in parallel with another serial protocol. The IRIG-B adapter cable 7XX8310-0CG00, in particular the D-Sub connection, must be protected against mechanical stresses (tension or vibration) by suitable relief measures.
  • Page 71: Electrical Tests

    Technical Data 6.9 Electrical Tests Electrical Tests Standards IEC 60255 (product standard) IEEE Std C37.90 UL 508 Additional standards are listed for the individual tests. Installation Requirements Overvoltage category Degree of pollution Protection class Voltage-Immunity and Safety Tests Standards IEC 60255-27 Voltage test (routine test), current measurement inputs, voltage meas- AC 2.5 kV urement inputs, relay outputs...
  • Page 72 Technical Data 6.9 Electrical Tests Radiated electromagnetic field 20 V/m, 80 MHz to 1 GHz immunity 10 V/m, 1 GHz to 6 GHz Frequency sweep 80 % AM IEC 61000-4-3 1 kHz Radiated electromagnetic field 20 V/m, 80 MHz/160 MHz/380 MHz/450 MHz/900 MHz immunity 10 V/1.85 GHz/2.15 GHz Spot frequencies...
  • Page 73 Technical Data 6.9 Electrical Tests Standard for Fast Transient Surge 4 kV Withstand Capability 5 ns/50 ns IEEE Std C37.90.1 5 kHz Burst length 15 ms Repetition rate 300 ms Both polarities Ri = 50 Ω Test duration 60 s Common mode and differential mode test Standard for Withstand Capability 20 V/m...
  • Page 74: Mechanical Tests

    Technical Data 6.10 Mechanical Tests 6.10 Mechanical Tests Vibration and Shock Stress in Stationary Use Standards IEC 60255-21 and IEC 60068 Vibration Test (sinusoidal) Sinusoidal 10 Hz to 60 Hz: ± 0.075 mm amplitude 60 Hz to 150 Hz; 10 m/s acceleration IEC 60255-21-1, class 2 Frequency sweep 1 octave/min...
  • Page 75: Environmental Conditions

    Technical Data 6.11 Environmental Conditions 6.11 Environmental Conditions Temperatures Type test, in operation -40 °C to +65 °C (in compliance with IEC 60068-2-1 and IEC 60068-2-2, test Ad for 16 h and test Bd for 16 h) Temporarily permissible during operation (tested for -25 °C to +65 °C 96 h) Load conditions for the non-modular devices: With...
  • Page 76: Operating Conditions

    The protection device is designed for flush mounting in conventional relay rooms and systems such that electromagnetic compatibility (EMC) is ensured with proper flush mounting. Siemens additionally recommends: • Use contactors and relays that work within the same cabinet or the same relay panel with digital protection equipment, only with suitable quenching equipment.
  • Page 77: Reference Conditions And Influencing Variables

    Technical Data 6.13 Reference Conditions and Influencing Variables 6.13 Reference Conditions and Influencing Variables Reference Conditions Measurand current I ± 1 % rated Measurand voltage V ± 1 % rated Frequency f ± 1 % rated Sine waveform, total harmonic distortion ≤...
  • Page 78: Approvals

    Technical Data 6.14 Approvals 6.14 Approvals UL-Listed/UL-Approved Device E194016 SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 79: Design Data

    Technical Data 6.15 Design Data 6.15 Design Data Masses Device Size Mass Type of construction Flush-mounting device 2.55 kg Bracket for the surface-mounting 1.07 kg version Dimensions Type of Construction Max. Total Width x Max. Total Height x Max. Total Depth , Each Rounded up to the Next Full mm (in Inches)
  • Page 80 Technical Data 6.15 Design Data Torques for Other Screw Types Screw Type Torque M4 x 14 (front cover) 0.4 Nm M4 x 14 (rear plate) 1.2 Nm M4 x 8 1.2 Nm SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 81: Assembly Dimensions

    Technical Data 6.16 Assembly Dimensions 6.16 Assembly Dimensions Dimensions [dw_SIP5-compact_dimensional_drawing, 2, en_US] Figure 6-4 Dimensions in the Different Views Flush-Mounting Device [dw_drilling_sourface_mounting_in_SIP5Comp, 1, en_US] Figure 6-5 Cut-Out Widths and Drilling Pattern SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 82 Technical Data 6.16 Assembly Dimensions Table 6-1 Cut-Out Widths Width of the Mounting Opening 1/6 device mm (2.8 +0.08 [dw_surface_mounting_in_SIP5Comp, 4, en_US] Figure 6-6 Flush-Mounting Devices, Dimensions from the Side and Front Views Table 6-2 Variable Housing Widths Dimension a Housing Widths in mm (in Inches) (Total Width: Housing Width + 4.6 mm (0.18 in)) 1/6 device...
  • Page 83 Technical Data 6.16 Assembly Dimensions Surface-Mounted Devices with Integrated On-Site Operation Panel [dw_console side view SIP5 Comp, 2, en_US] Figure 6-7 Surface-Mounted Device with Integrated On-Site Operation Panel; Dimensions in the Side and Front Views [dw_drilling-plans_for_SIP5compact_dimensions, 1, en_US] Figure 6-8 Drilling Pattern of a Surface-Mounted Device with Integrated On-Site Operation Panel SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 84: Battery

    Technical Data 6.17 Battery 6.17 Battery Type CR2032 Button cell Lithium Voltage Capacity 230 mAh Average service life of the battery, unpowered after removal of protec- At least 6 months tive film Service life of the battery in the activated state with protective film 10 years removed Use button cells from manufacturers like Varta, Panasonic, or Duracell.
  • Page 85: Display Resolution

    Technical Data 6.18 Display Resolution 6.18 Display Resolution LCD Graphic display (Liquid Crystal Display) 240 x 320 pixels SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 86 SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 87: Ordering Information

    Ordering Information Ordering Spare Parts and Accessories SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 88: Ordering Spare Parts And Accessories

    The product code unambiguously describes the selected product and also serves as an order number. Order Options NOTE You can find the selection and order options for SIPROTEC 5 Compact in the order configurator under: https://mall.industry.siemens.com/mall/en/de/entryPoints/StartConfigu- rator?ConfigId=33&nodeid=10313567&kmat=7SX800 Accessories 7.1.2 Table 7-1 Accessories...
  • Page 89: Literature

    Literature Compact Class – 7SX800 C53000-G5040-C003 Fault Recorder – 7KE85 C53000-G5040-C018 Hardware Description C53000-G5040-C002 Communication Protocols C53000-L1840-C055 Process Bus C53000-H3040-C054 DIGSI 5 – Software Description C53000-D5040-C001 SIPROTEC 5 – Security C53000-H5040-C081 PIXIT, PICS, TICS IEC 61850 C53000-G5040-C013 Operation C53000-G5040-C003 /10/ Engineering Guide C53000-G5040-C004 SIPROTEC 5 Compact, Hardware Description, Manual...
  • Page 90 SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 91: Glossary

    Glossary SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 92 SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...
  • Page 93: Index

    Index Activating the battery 46 IEC 60529 79 Assembly dimensions Installation requirements 71 Flush-mounting device 81 Instrument transformers 52 Surface-mounted version 83 Insulation test 71 Integrated Interface Serial 70 Interfaces 28 Battery 48 Battery compartment 48 Ordering Accessories 88 Communication interfaces 22 Communication module 42 Module designation 42 Conductor cross-section 54...
  • Page 94 Index Terminals 29 Current terminals 30 Voltage terminals 30 Voltage terminals 52, 56, 56 SIPROTEC 5 Compact, Hardware Description, Manual C53000-G5340-C002-7, Edition 03.2023...