VACON® NXP IP00 Drive Modules
Operating Guide
Drive type
Loadability
Enclo-
sure size
Low
Rated
continu-
ous cur-
rent I
(A)
NXP0205 5
205
FR9
NXP0261 5
261
NXP0300 5
300
FR10
NXP0385 5
385
NXP0460 5
460
NXP0520 5
520
FR11
NXP0590 5
590
NXP0650 5
650
NXP0730 5
730
FR12
NXP0820 5
820
NXP0920 5
920
NXP1030 5
1030
FR13
NXP1150 5
1150
NXP1300 5
1300
NXP1450 5
1450
FR14
NXP1770 5
1770
NXP2150 5
2150
See
12.9.1 Overload Capability
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
12.9.3 Power Ratings for Mains Voltage 500–690 V
Table 64: Power Ratings in Mains 500–690 V, 50/60 Hz, 3~
Drive type
Loadability
Enclo-
sure size
Low
Rated
continu-
ous cur-
rent I
(A)
FR8
NXP0062 6
62
NXP0080 6
80
Danfoss A/S © 2023.09
(1)
High
Rated
Rated
over-
continu-
load
ous cur-
current
rent I
L
H
(A)
(A)
(2)
226
170
287
205
330
245
424
300
506
385
572
460
649
520
715
590
803
650
902
730
1012
820
1133
920
1265
1030
1430
1150
1595
1300
1947
1600
2365
1940
(1)
High
Rated
Rated
overloa
continu-
d cur-
ous cur-
rent (A)
rent I
L
H
(A)
(2)
68
52
88
62
Motor shaft power
400 V supply
Rated
Max
Low
over-
current
over-
load
I
load P
S
current
(kW)
(A)
255
340
110
308
349
132
368
444
160
450
540
200
578
693
250
690
828
250
780
936
315
885
1062
355
975
1170
400
1095
1314
450
1230
1476
500
1380
1656
560
1545
1620
630
1725
2079
710
1950
2484
800
2400
2880
1000
2910
3492
1200
Motor shaft power
690 V supply
50 %
Max
Low
over-
current
over-
load
I
load P
S
current
(kW)
(A)
78
104
55
93
124
75
Specifications
500 V supply
High
Low
over-
over-
load P
load P
(kW)
(kW)
90
132
110
160
132
200
160
250
200
315
250
355
250
400
315
450
355
500
400
560
450
630
500
710
560
800
630
900
710
1000
900
1200
1100
1500
575 V supply
High
Low
over-
over-
load P
load P
(kW)
(kW)
45
60
55
75
AQ351737303996en-000201 / DPD00888 | 145
High
over-
load P
(kW)
110
132
160
200
250
315
355
400
450
500
560
630
710
800
900
1100
1300
High
over-
load P
(kW)
50
60