PROFIenergy
8.2 DI operating mode
8.2
DI operating mode
Display
If no external supply voltage is connected, switching off supply voltages 1U
leads to switching off the associated channel status LED Qn.
Response to error detection
All channels that are in pause mode on "PE_MODE_PROCEED" report their diagnostic status as
in productive mode.
The following applies for all channels which switch to a different pause mode:
• During the "pause", error detection of "Load voltage 2L+" is not possible:
– Alarms for errors already pending before the "pause" are retained.
– After the "pause" is over, the error status is updated and incoming/outgoing errors are
Mode parameter
The following table shows the "Mode" parameter.
Table 3-27 Mode parameter
Element Code
Mode
NOTE
Supply voltages 1U
Supply voltages 1U
If all channels require switching off during the pause, all supply voltages are switched off if
no channel is assigned in PE_MODE_PROCEED.
1208
reported correspondingly.
0
: PE_MODE_PROCEED
D
1
: PE_MODE_SHUTDOWN
D
3
: PE_MODE_LAST_VALUE
D
4
: PE_MODE_SUBST_VALUE
D
and 2U
S
A
and 2U
can only be switched off separately for each module.
S
A
Explanation
Proceed at "pause"
•
Value status "GOOD"
Switch off at "pause"
•
Supply voltages 1U
and 2U
S
•
Pause substitute value: 0
•
Value status "BAD"
Last value at "pause"
•
Supply voltages 1U
and 2U
S
•
Pause substitute value: Last input value
•
Value status "BAD"
Substitute value at "pause"
•
Supply voltages 1U
and 2U
S
•
Pause substitute value: Configured pause substi
tute value
•
Value status "BAD"
CM 4xIO-Link 4xM12 (6ES7147-5JD00-0BA0)
Equipment Manual, 04/2021, A5E32352322-AE
and 2U
also
S
A
off
A
B
off
A
off
A