Page 1
FCM20xx-U2, FCM20xx-U3 Operating unit, Operating unit (+ LED module), Operating unit (+ Switch module) Installation Mounting Smart Infrastructure A6V10315030_d_en_-- 2024-02-14...
Page 2
Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Industry, Inc. Smart Infrastructure 2 Gatehall Drive Parsippany, NJ 07054 Tel.
Table of contents Operating unit FCM20xx ................Description ..................... Mounting and wiring the operating unit ............View of PMI & mainboard................Indicators......................Adjustment elements..................Technical data ....................LED module FTO2008 and LED module (red/yellow, yellow) FTO2018... Description ..................... Views......................Adjustment elements..................Technical data ....................
Operating unit FCM20xx 1 Operating unit FCM20xx Fig. 1: View of FCM2018 operating unit Fig. 2: View of FCM2019 and FCM2035 operating unit (+ LED module) Fig. 3: View of FCM2043 operating unit (+ switch module) A6V10315030_d_en_-- 2024-02-14 5 | 26...
Operating unit FCM20xx Description 1.1 Description The operating unit is installed in the panels and comes in different versions: ● FCM2018 operating unit with control and display elements ● FCM2019 operating unit (+LED module) with extra integrated LED module ● FCM2035 operating unit (+LED module) with extra integrated LED module [ULC] ●...
Operating unit FCM20xx Mounting and wiring the operating unit ● Can be controlled via peripheral data bus for fire detection controls ● Each LED can be configured individually Document references The templates for the inscription strips and the operating instructions with button and LED designations have the following document IDs: Desigo Cerberus PRO...
Page 8
Operating unit FCM20xx Mounting and wiring the operating unit FHD2004 Inner door with window Operating unit FCM20xx 4x fixing nut for operating unit 4x set screw for operating unit (welded) Mounting steps 1. Plug the operating unit (2) onto the set screws (4) of the inner door (1) from behind, as shown above.
Page 9
Operating unit FCM20xx Mounting and wiring the operating unit DIN rail kit FHA2031 Periphery bus connection on periphery board (X201) Ribbon cable fixing with cable support Peripheral data bus connection on PMI & mainboard (X3) Inner door with FCM2018 operating unit Peripheral data bus output connection to optional LED or switch module Peripheral data bus input connection from PMI &...
Operating unit FCM20xx View of PMI & mainboard Inscription LEDs Inscription for the standard keys in the center Inscription for standard keys on the right Inscription for LED module (depending on whether operating unit is present or not) Inscription for panel and alarm 1.3 View of PMI &...
Operating unit FCM20xx Indicators Element Des. Function Plug connections Connection for periphery board or fire terminal board (supply and data signals) Ethernet connection Connection for 18-pin cable to the MXL line card (FCL2004) N.C. Slot for network module SAFEDLINK FN2001 Slot for RS485 class A module (isolated) FCA2016 Not used Slot for RS485 class A module (isolated) FCA2016...
Operating unit FCM20xx Adjustment elements Color Function Condition Meaning Yellow 'CPLD fail' (reset and Normal operation watchdog logic) Logic unit failed; replace component or contact hotline 'TEMP', CPU module Normal operation excess temperature CPU >113 °F / 45 °C indicator Yellow 'SPEED', Ethernet Data transfer at 10 Mbit/s transmission indicator Data transfer at 100 Mbit/s H842...
Operating unit FCM20xx Technical data ● A6V10315021 for Desigo ● A6V10333434 for Cerberus PRO S33: Switch for ground fault supervision of the Ethernet connection Position Function Default setting Setting for networking via FCnet/C-WEB Setting for networking via Ethernet S38: Switch for ground fault supervision of the system supply ●...
Page 14
Operating unit FCM20xx Technical data Interfaces Serial modules ● For class A RS485 module for connecting an external printer or FT2014/FT2015 [X14] and [X19] Internal bus ● For MXL line card (FCL2004) synchronization [X11] Networking ● Network module (SAFEDLINK) incl. degraded mode function [X13] Ethernet ●...
LED module FTO2008 and LED module (red/yellow, yellow) FTO2018 Description 2 LED module FTO2008 and LED module (red/ yellow, yellow) FTO2018 2.1 Description The LED module FTO2008 and the LED module (red/yellow, yellow) FTO2018 are zone indicators which allow events (e.g., alarms and troubles) from 24 zones to be displayed.
LED module FTO2008 and LED module (red/yellow, yellow) FTO2018 Adjustment elements Element Des. Function Indicators H301… LEDs for indication on front (designation on PCB) H371 Switch Switch for device address Connectors X400 Peripheral data bus connection (input) X402 Peripheral data bus connection (output) X407 Not used X409...
LED module FTO2008 and LED module (red/yellow, yellow) FTO2018 Technical data 2.4 Technical data Supply input Voltage DC 24 V Operating current Max. 5 mA + 1 mA per LED (max. 48 LEDs) Supply output Voltage DC 24 V Curent Looped, max. 1 A LEDs Quantity 48 LEDs for 24 zones: LED module ●...
Switch module Fire/Voice FTO2023 Description 3 Switch module Fire/Voice FTO2023 3.1 Description The 'Switch Module- Fire/Voice' FTO2023 is a programmable control module with 24 'Zones' and can be installed in a fire control panel, Fire voice control panel or in 'Remote microphone' VR2005 'Panels'. An FTO2023 can be used to indicate events, provide status information, and activate fire/voice functions.
Switch module Fire/Voice FTO2023 Views ● Each LED may be configured as OFF, flashing, or constantly ON ● Audible confirmation when a button is pressed ● Can be controlled via CAN bus for Fire voice control panels or via peripheral data bus for fire control panels ●...
Switch module Fire/Voice FTO2023 Adjustment elements Element Des. Function Indicators H301 Status LED for CAN bus H625 Status LED for microprocessor Switches and S326 Switch for device address (ONES) keys S327 Switch for device address (TENS) S328 Reset button Connector plug X202 Peripheral data bus connector B and jumper...
Switch module Fire/Voice FTO2023 Technical data CAN bus addresses between 1 and 99 are valid on the 'Switch Module- Fire/Voice' FTO2023. The hardware addresses set for each module must correspond to the matching addresses 201 to 299 in Desigo Fire Safety Works/Cerberus-Engineering-Tool. The CAN bus address 0 is reserved and must not be used for the option modules.
Page 23
Switch module Fire/Voice FTO2023 Technical data CAN bus (input and output) for Fire voice X204, X205 control panels Plug connection with ribbon cable A6V10315030_d_en_-- 2024-02-14 23 | 26...
FCC Statement 4 FCC Statement WARNING Installation and usage of equipment is not in accordance with instructions manual Radiation of radio frequency energy Interference to radio communications ● Install and use equipment in accordance with instructions manual. ● Read the following information. This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications.