hit counter script

Dry Operation - Mitsubishi Electric PMFY-P06NBMU-E Technical & Service Manual

Ceiling cassettes
Hide thumbs Also See for PMFY-P06NBMU-E:
Table of Contents

Advertisement

8-2. DRY OPERATION

TIME SUN MON TUE WED THU FRI SAT
TIMER
Hr
AFTER
AFTER
ERROR CODE
û Fû C
û Fû C
ONLY1Hr.
TEMP.
MENU
ON/OFF
BACK
MONITOR/SET
DAY
PAR-21MAA
CLOCK
OPERATION
Control modes
1-1. Dry mode temperature is controlled by TH21.
1. Thermostat function
1-2. Frozen prevention control
Indoor fan operation control depends on the compressor conditions.
2. Fan
Note: Remote controller setting is not acceptable.
3. Drain pump
Same control as COOL operation
Same control as COOL operation
4. Vane
(up/down vane change)
OC341F
<How to operate>
1 Press POWER ON/OFF button.
ON
OFF
2 Press the operation MODE button to display DRY.
FUNCTION
FILTER
3 Press the TEMP. button to set the desired temperature.
WEEKLY
SIMPLE
AUTO OFF
NOTE: The set temperature changes 2°F when the
ON/OFF
FILTER
CHECK
TEST
CLEAR
Dry mode ON Room temperature
Dry mode OFF Room temperature
3 min. passed since starting operation
Room
temperature
Dry mode
ON
Over 64˚F
OFF
Less than 64˚F
No control function
Dry mode
Fan speed notch
ON
[Low]
Stop
OFF
pressed once. Dry 67 to 87°F.
Control details
desired temperature + 2˚F
desired temperature
Room temperature (Ta)
Ta
83˚F
83˚F > Ta
79˚F
79˚F > Ta
75˚F
75˚F > Ta
Unconditional
Dry mode OFF
17
or
Dry mode
Dry mode
ON
OFF
time (min)
time (min)
9
3
7
3
5
3
3
3
3
10
button is
Remarks

Advertisement

Table of Contents
loading

Table of Contents