hit counter script

6Es5 456-4Ua12 Digital Output Module - Siemens S5-155U System Manual

Hide thumbs Also See for S5-155U:
Table of Contents

Advertisement

8.4.14
6ES5 456-4UA12 Digital
Output Module
Rated supply voltage L
Number of outputs
Isolation
Range for supply voltage
Fusing
Output voltage
for logic 1
for logic 0
Residual current at logic 0
Switching current (resistive, inductive load)
ventilated
not ventilated
Switching current for lamps
ventilated
not ventilated
Contactor size
per fuse group
for all outputs
Max. inrush current for
≤ 3 ms
≤ 20 ms
≤ 50 ms
Permissible line length
Power supply
Digital section from system bus
Power dissipation (rated operation)
Enable input (F+/F-)
Voltage test to VDE 0160
Mechanical specifications
Dimensions (W x H x D)
Weight
System Manual
C79000-B8576-C199-03
115 to 230 V AC (47 to 63 Hz)
16, conditional short-circuit protection
Yes, 2 groups of 8 outputs
88 to 264 V AC
6.3 A fast, 1 fuse per 4 outputs
L- 1.5 V min.
30 V max.
5 mA max.
40 mA to 2 A;
40 mA to 1 A;
40 mA to 2 A, 2.5 A max. per 4 outputs
40 mA to 1 A, 2.5 A max. per 4 outputs
0 (Type 3TB40) to 14 (Type 3TB58) at 230 V AC
00 (Type 3TJ..) to 10 (Type 3TB54) at 115 V AC
0 (Type 3TB40) to 8 (Type 3TB52) at 230 V AC
00 (Type 3TJ..) to 4 (Type 3TB48) at 115 V AC
25 A/group
15 A/group
13 A/group
300 m max. unshielded
5 V, 100 mA typical
39.0 W
Jumper in front connector
Between two groups: 2000 V AC
Between group and ground point: 1500 V AC
40 mm x 255 mm x 195 mm
Approx. 0.7 kg
1)
Protected by a fuse
2)
Contactors of Series 3TJ can only be operated at 115 V AC.
Specification Sheets for the Modules
1)
2)
6 A max. per 4 outputs
2)
4 A max. per 4 outputs
8
8 - 61

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-135uSimatic s5

Table of Contents

Save PDF