hit counter script
Download Print this page
Siemens ABHW-4BZ Installation Instructions Manual
Siemens ABHW-4BZ Installation Instructions Manual

Siemens ABHW-4BZ Installation Instructions Manual

Intelligent audible base

Advertisement

Quick Links

Installation Instructions
Model ABHW-4BZ
Intelligent Audible Base
Introduction
Application
note
A6V10806895_en--_d
The Model ABHW-4BZ audible
Inc. consists of a standard base combined with an audible
device.
It is an intelligent supervised audible base which
provides 6 selectable tone patterns, 2 volume levels and 2
different power types for alarm (loop power or external power)
by using system configuration tool when ABHW-4BZ used with
the FD-UL compatible detectors (refer to "Compatible fire
alarm control panels", "Compatible detector ","Detector
Placement" and "Tone and Volume Selection"). The ABHW-
4BZ audible bases in the same device loop are fully
synchronized with FD-UL detectors and also support RL-HC,
RL-HW remote lamp. The ABHW-4BZ provides Steady,
Temporal 3, Temporal 4, Temporal 4 low power, March time
120 and Canadian March time 30.
ABHW-4BZ is fully compatible with all Siemens addressable
detectors (see Compatible detectors section) and recognizes
the detector type automatically.
The ABHW-4BZ is a UL268 & ULC-S529 listed smoke detector
supplementary device which combines detector base and
audible device functions. It meets or exceeds 85dB at 10 foot
audibility requirement as specified in UL268. When used in
conjunction with listed, compatible Siemens equipment, the
ABHW-4BZ may be used in lieu of single/multiple station smoke
alarms to achieve enhanced, system-level functionality.
The ABHW-4BZ can also meet requirement specified in UL464,
UL2075 and ULC-525 except 520Hz requirements for "Sleeping
Area".
base
from Siemens Industry,
Siemens Industry,
Building Technologies Division
Inc.

Advertisement

loading

Summary of Contents for Siemens ABHW-4BZ

  • Page 1 120 and Canadian March time 30. ABHW-4BZ is fully compatible with all Siemens addressable detectors (see Compatible detectors section) and recognizes the detector type automatically. The ABHW-4BZ is a UL268 & ULC-S529 listed smoke detector Application supplementary device which combines detector base and note audible device functions.
  • Page 2 8.0 mA Low dBA: 3.5 mA Constraints 1. If the alarm current of ABHW-4BZ is energized by an external power supply, any UL listed 24VDC regulated power supply including the aux power output of XLS, FC2005/FC901, FC2025/FC2050/FV2025/FV2050, FC922/FC924/FV922/FV924 and PAD-3/PAD-4/PAD-5 can be used (refer to Figure 1);...
  • Page 3 FC2005/FC901 (refer to Figure 4.1) or NAC from FC2025/FC2050/FV2025/FV2050, FC922/ FC924/FV922/FV924 (refer to Figure 4.2). 2. The alarm current of ABHW-4BZ CAN’T be energized by a 24V FWR power supply. 3. The maximum number of ABHW-4BZ is related to the max.
  • Page 4 The detector base comes from the factory prewired. All mounting signaling and initiating circuits are connected directly to the back of the ABHW-4BZ audible base using the four position terminal blocks. Base 1. Route all wires out from the outlet box.
  • Page 5 4 and 6 inches from the ceiling. If questions arise regarding detector placement, it is extremely important that the drawings provided or approved by Siemens Industry, Inc., or by its authorized distributors be followed! The detector placements shown on these drawings were chosen after a careful evaluation of all facets of protecting the area.
  • Page 6 1. RPR-1 remote relay and HTRI are used for 24VDC power supervision. 24VDC wire open will cause trouble reported by HTRI. Refer to Installation Instruction of RPR-1 (315-096055). 2. ABHW-4BZ terminals 5-6 are polarity insensitive. Line 1 and Line 2 can be either line of device loop.
  • Page 7 ZIC-4A Note: 1. Polarity shown in active state at terminals 1 and 2 of ABHW-4BZ and 1-4 of ZIC-4A. Proper polarity must be maintained or audible base will not operate properly. Each audible base must be tested to verify operation.
  • Page 8 NAC outputs of PAD-3/ PAD-4/PAD-5 Note: The NAC circuit shown in the diagram is the active state at terminal 1 and 2 of ABHW-4BZ. ABHW-4BZ terminals 5-6 are polarity insensitive. Line 1 and Line 2 can be either line of device loop.
  • Page 9 Periphery NAC outputs Note: The NAC circuit shown in the diagram is the active state at terminal 1 and 2 of ABHW-4BZ. ABHW-4BZ terminals 5-6 are polarity insensitive. Line 1 and Line 2 can be either line of device loop.
  • Page 10 FC922/FC924/FV922/FV924 SYSTEM Note: The ABHW-4BZ terminal 3 should be connected to RL-HC/RL-HW TB1 The ABHW-4BZ terminal 4 should be connected to RL-HC/RL-HW TB2 or TB3 Figure7 ABHW-4BZ Audible Base Terminal Blocks (only for FDO421, FDOT421, FDT421, FDOOT441, FDOOTC441, OP921, OH921, HI921, OOH941 and OOHC941 detectors.)
  • Page 11 Zeus ver 10.02 or later • DLC ver 06.01 or later 2. When the audible base ABHW-4BZ works with FD-UL series detectors. Up to 6 tone patterns and 2 volume levels can be selected by user with system configuration tool; there are two power types for ABHW-4BZ during alarm, “Loop...
  • Page 12 APPENDIX: Max. number of loop powered ABHW-4BZ audible bases in one loop 1. The max. number of loop powered ABHW-4BZ audible bases in one device loop depends on the available load current for ABHW-4BZ audible bases. The available load current for loop powered ABHW-4BZs (I) can be calculated by: I = I –...
  • Page 13 2. The max. number of loop powered ABHW-4BZ for the worst case scenario (All detectors wired at the end of 50 ohms cable) Detector Loaded Current available Max number of loop powered ABHW-4BZ in one DLC for ABHW-4BZ High dBA...
  • Page 14 Siemens’ portfolio undergoes continuous development to make it more secure. Siemens strongly recommends that updates are applied as soon as they are available and that the latest versions are used. Use of versions that are no longer supported, and failure to apply the latest updates may increase your exposure to cyber threats.