11 REFERENCE
SELECT
11.01
KEYPAD REF SEL
REF1 (rpm)
REF2 (%)
11.02
EXT1/EXT2 SELECT
EXT1
EXT2
COMM.CW
DI7
DI8
DI9
DI10
PARAM 11.09
11.03
EXT REF1 SELECT
KEYPAD
AI1
AI2
AI3
Description
Panel reference type, external control location selection and external reference
sources and limits
Selects the type of the reference given from panel.
Speed reference in rpm. (Frequency reference (Hz) if parameter
SCALAR.)
%-reference. The use of REF2 vary depending on the application. For
example, if the Torque Control using M/F is selected, REF2 is the torque
reference.
Defines the source from which the drive reads the signal that selects between
the two external control locations, EXT1 or EXT2.
Note: In M/F configuration, EXT2 should be used for control in M/F mode and
EXT1 for stand-alone mode.
EXT1 active. The control signal sources are defined with parameter
11.03.
EXT2 active. The control signal sources are defined with parameter
11.06.
Fieldbus Control Word. See
250.
Digital input DI7 is the signal source.
Digital input DI8 is the signal source.
Digital input DI9 is the signal source.
Digital input DI10 is the signal source.
Source selected with parameter 11.09.
Selects the signal source for external reference REF1
Note: In M/F configuration, EXT2 should be used for M/F mode and EXT1 for
stand-alone mode.
Control panel. The first line on the display shows the reference value.
Analogue input AI1.
Note: If the signal is bipolar (±10 V DC), use the selection AI1 BIPOLAR. (The
selection AI1 ignores the negative signal range.)
Analogue input AI2.
Analogue input AI3.
03.01 MAIN CONTROL WORD
FbEq
99.04
is
1
2
10.01
and
1
10.02
and
2
bit 11 on page
3
4
5
6
7
8
1
2
3
4
Actual signals and parameters
161