    Content About this document ..................3 Validity ........................... 3 Target group ........................3 Safety ........................ 3 Symbols and advices ..................... 3 Basic safety precautions ....................4 2.2.1 Product safety ........................ 4 2.2.2 Personnel-related measures ................... 4 2.2.3 Organisational measures ....................4 Description ......................
  • Page 3: About This Document

    About this document These operating instructions are part of the POLIM®-C surge arrester and describe safe and proper use for all phases of operation. Language of the original operating instructions: German Validity These operating instructions are valid only for the POLIM®-C surge arrester. Target group The target group of these operating instructions is professionals in the field of high-voltage technolo- The POLIM®-C may only be commissioned and maintained by persons instructed in proper use and...
  • Page 4: Basic Safety Precautions

    Basic safety precautions 2.2.1 Product safety The POLIM®-C has been constructed using state-of-the-art technology and officially recognised safety-related rules. Danger to life and health of the user or third parties could arise or damage of the POLIM®-C and other property could occur while the POLIM®-C is in use, however. The POLIM®-C is only to be used when it is in technically sound condition, for the intended pur- pose, and with safety and the possible dangers in mind while observing the operating instructions.
  • Page 5: Technical Data

    Thanks to its high energy absorbing capability and mechanical strength, the POLIM®-C is especially suited for overvoltage protection of ƒ transformers ƒ cables and cable sheat ƒ capacitors ƒ rotating machines ƒ apparatuses in railway applications ƒ other low- and medium-voltage apparatuses and systems Variants of the surge arrester POLIM®-C suitable for the use in a.c.
  • Page 6: Application Guidelines

    3.3.2 Application guidelines The following guidelines apply for the use of POLIM®-C surge arresters: ƒ „Application guidelines - Overvoltage protection“ Dimensioning, testing and application of metal-oxide surge arrresters in medium voltage systems, pamphlet 1HC0075561 ƒ „Application guidelines - Overvoltage pRotection“ Dimensioning, testing and application of metal-oxide surge arrresters in railway facilities, pamphlet 1HC0075573 3.3.3...
  • Page 7: Storage

    Storage The original packaging materials can be used for storage. Store surge arresters in a well-ventilated, clean room. Remove plastic film to prevent the formation of condensation water. Commissioning Safety DANGER! System uses high voltage. Death, serious bodily harm and damage to the switching gear may result from an electric shock. Allow only authorised professionals to perform work on the surge arrester.
  • Page 8: Mounting

    Damage to the switching gear and the surge arrester. Do not use surge arresters intended for a.c. systems in d.c. systems. Observe the „Application guidelines“ from ABB Switzerland Ltd. Before mounting, ensure that the characteristic data on the rating plate of the surge arrester matches the requirements of the power system.
  • Page 9: Connections

    5.4.4 Connections The base for the surge arrester must be flat, clean and suitable for the loads that arise. The following materials made of stainless or galvanised steel are to be provided by the customer: ƒ bolts ƒ nuts ƒ bolt locks The design of the surge arrester POLIM®-C is symmetrical.
  • Page 10: Maintenance, Upkeep

    Maintenance, upkeep Safety DANGER! System uses high voltage. Death, serious bodily harm and damage to the switching gear may result from an electric shock. Allow only authorised professionals to perform work on the surge arrester. Observe the safety rules of EN 50110-1 before working on the system: à...
  • Page 11: Disposal

    Disposal POLIM®-C surge arresters are environmentally-friendly products which must be disposed of based on the respective applicable regional regulations in an environmentally-friendly manner. The materials should be given up for recycling. Constituent components are: ƒ silicone rubber (not halogenated) for the external insulation ƒ...
  • Page 12 High Voltage Products prior notice. With regard to purchase Surge Arresters orders, the agreed particulars Jurastrasse 45 shall prevail. ABB does not accept any responsibility whatsoever for CH-5430 Wettingen potential errors or possible lack of Phone: +41 58 585 29 11 information in this document.