NOTICE!
Risk of damage to I/O modules!
Do not perform hot swapping if any I/O module with firmware version lower than
3.0.14 is part of the I/O configuration.
For min. required device index see table below.
Hot swapping is only allowed for I/O modules.
Processor modules and communication interface modules must not be removed
or inserted during operation.
3ADR024117M02xx, 11, en_US
Min. required device index for I/O module as of
FW Version 3.0.14
D2
D4
D2
B2
B2
B3
D2
B2
D2
D2
B2
D1
D2
D2
D2
D2
B2
A2
D2
B2
B2
B2
A1
A3
A2
A0
B2
A2
B3
2019/11/15