8.9
Program example for resetting the inverter at inverter error
The following is a program example for resetting station 1 inverter.
SW80.0
X0
X0F
X1
0
M0 X101A X20
7
Error status flag
11
NOTE
• The above inverter reset using RY1A may be made only when an inverter error occurs. When Pr.349 Communication
reset selection is set to "0", inverter reset is available in any operation mode.
• When using the instruction code execution request (RYF) with the instruction code (HFD) and data (H9696) to reset the
inverter, set a value other than "0" in Pr.340 Communication startup mode selection (refer to
operation mode to the network operation mode. (For the program example, refer to
• Refer to
page 43
for operation conditions of inverter reset.
M0
Check the data link status of the station 1
Turn on the error reset request flag (RY1A)
Y101A
Turn off the error reset request flag (RY1A)
when the error status flag (RX1A) is off.
END
page
85)
PROGRAMMING EXAMPLES
page
34) or change the
93
8