Siemens SIPROTEC 6MD665 Manual page 71

Bay processing unit
Table of Contents

Advertisement

Commands
Input indications
6MD665 Manual
C53000-G1876-C103-3
calculated measured values of the synchronisation function.
• Indications,
Indications on the command procedure (such as CO+/CO-).
• Settings,
Settings for configuring properties.
Table 2-8
Start conditions check phase, operating mode analysis
Code
Command ON/OFF
to SyncSD
Command abort
- to SyncSD, or
- to all
The input indications are enabled once per synchronisation settings group. For this
reason, they are configured as often as synchronisation settings groups are required.
Control command from different initiators.
ON: Control command for switching the control device on. (with or
without synchronisation procedure)
OFF: Control command for switching the control device off. (with-
out synchronisation procedure)
Abort command, a running command procedure, the synchronisa-
tion or switching procedure must be aborted.
Abort of the synchronisation procedure is without conditions.
Abort of the synchronisation procedure is only possible for a
command with operating mode "impulse, interruptible".
2.7 Circuit breaker synchronisation
Explanation
57