hit counter script
Siemens SITRANS F C MASSFLO MASS 6000 Operating Manual
Hide thumbs Also See for SITRANS F C MASSFLO MASS 6000:

Advertisement

s
SITRANS F C MASSFLO
MASS flowmeters
Signal converter type MASS 6000
Order no.: FDK:521H0991
SFIDK.PS.028.M1.02 -
A5E00253658
[
Operating Manual
    
*083R9089*
]

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS F C MASSFLO MASS 6000

  • Page 1 Operating Manual      SITRANS F C MASSFLO MASS flowmeters Signal converter type MASS 6000 Order no.: FDK:521H0991 *083R9089* SFIDK.PS.028.M1.02 - A5E00253658...
  • Page 2: Table Of Contents

    1. Installation of sensor SITRANS F C MASSFLO      Installation of sensor ..................... 2 Contents Installation of signal converter ..................3 Compact installation ....................... 3 2.2.1 Remote Installation ......................4 At the sensor ........................4 2.2.2 Remote installation ......................5 Wall mounting .........................
  • Page 3: Installation Of Signal Converter

    SITRANS F C MASSFLO      2. Installation of signal converter Remove and discard the terminal box lid of the Installation of signal converter sensor. 2.1 Compact installation Fit the PG 13.5 cable glands for the supply and output cables.
  • Page 4: Remote Installation

    2. Installation of signal converter SITRANS F C MASSFLO      2.2.1 Remote Installation Mount the adaptor on top of the sensor inter- At the sensor face, if not already mounted. When fitting the multiple plug, please make sure that it is correctly oriented (note the little tap).
  • Page 5: Remote Installation

    SITRANS F C MASSFLO      2. Installation of signal converter Mount the wallbracket on a wall, pipe or in the 2.2.2 Remote installation back of a panel. Wall mounting Compact IP 67 version Take the SENSORPROM ®...
  • Page 6: Remote Installation

    2. Installation of signal converter SITRANS F C MASSFLO      2.2.3 Remote installation Signal converter in 19" insert ® 1. Fit the SENSORPROM unit on the connection board supplied with the signal converter. The SENSORPROM ® unit is supplied with the sensor.
  • Page 7: Technical Data

    SITRANS F C MASSFLO      3. Technical data Technical data 3.1 Signal converter MASS 6000 MASS 6000 Compact IP 67 and 19" IP 20 version Measurement of Mass flow [kg/s], volume flow [l/s], fraction [%], Brix, density [kg/m ], temperature [°C] Current output Current...
  • Page 8: Electrical Connection

    4. Electrical connection SITRANS F C MASSFLO      Electrical connection 4.1 Signal converter MASS 6000 Installation 1) Mains supply 115 to 230 V a.c. from building installation Class II. A switch or circuit-breaker (max. 15 A) shall be included in the building installation. It must be in close proximity to the equipment and within easy reach of the OPERATOR, and it shall be marked as the disconnecting device for the equipment.
  • Page 9: Output Characteristics Mass 6000

    SITRANS F C MASSFLO      4. Electrical connection 4.2 Output characteristics Output characteristics Bidirectional mode Unidirectional mode MASS 6000 0-20 mA 4-20 mA Frequency Pulse output Relay Power supply off Power supply on Error relay No error Error Limit switch or 1 set point...
  • Page 10: Commissioning

    SITRANS F C MASSFLO      5. Commissioning Commissioning 5.1 Menu overview SFIDK.PS.028.M1.02...
  • Page 11: Menu Details

    SITRANS F C MASSFLO      5. Commissioning Menu details Basic settings menu Comma for flowrate, totalizer 1 and totalizer 2 can be individually positioned. • open the respective window. • ensure that the cursor is positioned below the comma. Use the SELECT KEY •...
  • Page 12: Outputs Setting Menu

    SITRANS F C MASSFLO      5. Commissioning 5.3 Outputs setting menu Current output The current output must be set off when not used. Digital output Pulse Digital output Frequency SFIDK.PS.028.M1.02...
  • Page 13 5. Commissioning SITRANS F C MASSFLO      Digital output Batch Relay output Error level (Also possible through digital output) Acceptance level is set in the basic settings menu. Error number (Also possible through digital output) Limit switch & direction switch (Also possible through digital output)
  • Page 14: Service

    SITRANS F C MASSFLO      6. Service Service Error Error text #Comment Outputs Input 6.1 List of error numbers Remedy text status status I1 - Power on Power on has happened Active Active I2 - Add-on Module Applied A new module has been applied to the system Active...
  • Page 15: Trouble Shooting Mass 6000

    SITRANS F C MASSFLO      6. Service 6.2 Trouble shooting Symptom Output Error Cause Remedy MASS 6000 signals code Empty display Minimum 1. Supply voltage 1. Check supply voltage 2. MASS 6000 defective 2. Replace MASS 6000 No flow signal Minimum 1.

Table of Contents