System Indoor Unit (2 Series) INSTALLATION MANUAL Type: Ceiling Concealed Duct - High Static IMPORTANT • Please read this installation manual completely before installing the product. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
IMPORTANT! Please read this instruction sheet completely before installing the product. This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. WARNING •...
Ceiling Concealed Duct - High Static Type Indoor Unit Installation Manual TABLE OF CONTENTS Required Parts Required Tools Installation Requirements Features ........4 Safety Precautions ....5 ❏ Level gauge Installation ❏ Four type "A" screws ❏ Screw driver ❏ Connecting cable ❏...
Safety Precautions Safety Precautions To prevent injury to the user or other people and property damage, the following instructions must be followed. I Be sure to read before installing the air conditioner. I Be sure to observe the cautions specified here as they include important items related to safety. I Incorrect operation due to ignoring instruction will cause harm or damage.
Page 6
Safety Precautions Do not modify or extend the Do not let the air conditioner Be cautious when unpacking power cable. run for a long time when the and installing the product. humidity is very high and a door or a window is left open. •...
Page 7
Safety Precautions I Installation Always check for gas (refriger- Install the drain hose to ensure Keep level even when installing ant) leakage after installation or that water is drained away prop- the product. repair of product. erly. • Low refrigerant levels may cause •...
Installation Installation Read completely, then follow step by step. Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unit’s weight. •...
Installation Ceiling dimension and hanging bolt location I Installation of Unit BH/BG/BR Chassis Install the unit above the ceiling correctly. CASE 1 POSITION OF SUSPENSION BOLT • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. [Unit:mm(inch)] Dimension Chassis (36-9/13)
Installation Indoor Unit Installation • Select and mark the position for fixing bolts. • Insert the set anchor and washer onto the suspen- • Drill the hole for set anchor on the face of ceiling. sion bolts for locking the suspension bolts on the ceiling.
Installation Connection method of the connecting cable(Example) Lock nut 1(L1) 2(L2) 3(A) 4(B) Conduit Conduit mounting plate Power Supply Transmission High Voltage (208/230V) WARNING : Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazzard may also exist. Therefore, be sure all wiring is tightly connected.
Page 12
Installation CAUTION 1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 5mm. Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation.
Installation CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit.
Installation Installation of Wired Remote Controller 1. Connect the wired remote controller cable to the wired remote controller installation board as shown in the right picture. 12V SIG GND Red wire Yellow Yellow wire Black Black wire Remote Controller ❊ The wired remote controller cable is connected as factory default. Cable 2.
Page 15
Installation 5. Use the connecting cable to connect the indoor unit and the wired remote controller. Check whether the connector is connected correctly. Indoor unit side Connecting cable 6. When the distance between the wired remote controller and the indoor unit is 10m and above, use the extension cable.
Installation Optional Operation of Wired Remote Controller Two Thermistor System 1. Press button for 4 seconds to enter the installer setting mode until timer segment display “01:01”. 2. Repeat pressing button to select Function code 04. 04:01 Function Code Thermistor setting 3.
Installation Dip Switch Setting Function Description Setting Off Setting On Default Communication N/A (Default) Cycle N/A (Default) Group Control Selection of Master or Slave Master Slave Dry Contact Mode Selection of Dry Contact Wired/Wireless remote Mode controller Auto Selection of Manual or Auto operation Mode Installation CST –...
Installation Group Control Setting 1. Group Control 1 I Wired remote controller 1 + Indoor units LGAP Network System Master Slave Slave Slave Signal 12 V Display Error Message Only connect serial signal and GND lines between slave indoor unit Master 1.
Installation 2. Group Control 2 I Wired remote controllers + Indoor units LGAP Network System Slave Slave Slave Signal Master 12 V Don’t connect serial 12V line Display Error Message Master Slave 1. It is possible to control N indoor units by wired remote controller M units. (M+N≤17 Units) Set only one indoor unit to Master, set the others to Slave.
Page 20
Installation 3. 2 Remote Control I Wired remote controller 2 + Indoor unit 1 LGAP Network System Master Signal 12 V Display Error Message Master Slave 1. It is possible to connect two wired remote controllers with one indoor unit. 2.
How to Set E.S.P? How to Set E.S.P? What is an E.S.P function? This is the function that decides the strength of the wind for each wind level and because this function is to make the installation easier, please do not use this function when using the remote controller. If you set ESP incorrectly, the air conditioner may malfunction.