Generator protection REG670 2.1 IEC
Product version: 2.1
Table 17. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity
Rated voltage
Number of outputs
Impedance open state
Test voltage across open contact, 1 min
Current carrying capacity:
Continuous
1.0s
Making capacity at capacitive load with the
maximum capacitance of 0.2 μF :
0.2s
1.0s
Breaking capacity for DC with L/R ≤ 40ms
Operating time
Table 18. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Function of quantity
Max system voltage
Number of outputs
Test voltage across open contact, 1 min
Current carrying capacity:
Continuous
1.0s
Making capacity at capacitive load with the maximum capacitance of
0.2 μF:
0.2s
1.0s
Breaking capacity for DC with L/R ≤ 40ms
ABB
SEMOD175395-2 v6
Static binary output trip
48 - 60 VDC
6
~300 kΩ
No galvanic separation
5A
10A
30A
10A
48V / 1A
60V / 0.75A
<1ms
Trip and signal relays
250V AC/DC
6
1000V rms
8A
10A
30A
10A
48V / 1A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A
1MRK 502 068-BEN D
110 - 250 VDC
6
~810 kΩ
No galvanic separation
5A
10A
30A
10A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A
<1ms
45